An Experimental and Analytical Study of a Radiative Cooling System with Flat Plate Collectors
Open accessAbstract
A nocturnal radiative cooling system with flat plate solar collectors in Beijing, is assessed both experimentally and numerically. A cooling loop, including a radiator, a storage tank, pump, radiant floor and connecting pipes has been studied experimentally. The heat loss of an uncovered night-sky radiator was analysed according to radiation and convection theory. The water is circulated through the flat-plate radiator having 2 m2 of collector area at night to be cooled by convection and radiation to sky. The results indicate that the minimum temperature of the floor surface is 19.5 °C. Vertical temperature field is uniform. Design temperature can increase 1 °C compared with conventional heat convection. The average net cooling reached 26 W/m2, as condensation does not occur. It is possible to increase the total cooling capacity while maintaining a low pressure drop. It demonstrates the feasibility of cooling using fluid medium through nocturnal radiation.
Integrity signals
Registry
Cites
Statistics
Claims the paper makes
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
TABS needs to be installed in the construction phase of a building, which limits its use in renovation projects.
“However, TABS needs to be installed in the construction phase of a building, which limits the use of TABS in renovation projects.”
From Resilient cooling strategies – A critical review and qualitative assessment (2021) · cites this paper as [230]
The main function of ventilation systems is to regulate humidity and provide fresh air to indoor spaces.
“The main function of ventilation systems is to regulate humidity (i.e., to dehumidify the air) and provide fresh air to indoor spaces [230].”
From Resilient cooling strategies – A critical review and qualitative assessment (2021) · cites this paper as [230]
When using sky radiative cooling actively, parameters such as the flow rate of the heat storage medium can be controlled, allowing higher exploitation (higher recovery speed), especially during periods when the potential is high.
“Furthermore, when using the technology actively, parameters such as the flow rate of the heat storage medium can be controlled [220,221,223,229], allowing higher exploitation (higher recovery speed), especially during periods when the potential is high, thus using the available resources in a timely manner.”
From Resilient cooling strategies – A critical review and qualitative assessment (2021) · cites this paper as [229]
The citation lists haven’t been fetched yet
References 8 · Cited by 26
- Authors
- Xu, X., Niu, R., & Feng, G.
- Affiliations
- Shenyang Jianzhu University (CN)
- Beijing University of Civil Engineering and Architecture (CN)
- Corresponding author
- Feng, Guohui
- Venue
- Procedia Engineering
- Publisher
- Elsevier BV
- Published
- 2015
- Volume
- 121
- Pages
- 1574-1581
- ISSN
- 1877-7058 (ISSN-L)
- OpenAlex
- W2353938356
- Cited by
- 26
- References
- 8
- Citations by year
- 2026: 2 · 2024: 2 · 2023: 1 · 2022: 2 · 2021: 2 · 2020: 3 · 2019: 7 · 2018: 1 · 2017: 3 · 2016: 3
- FWCI
- 9.60
- Type
- conference paper
- Language
- en
- Open access
- diamond
- doi.org
- Licence
- Locations
- Procedia Engineering (publishedVersion, cc-by-nc-nd)
- Topics
- Physical Sciences › Engineering › Civil and Structural Engineering › Thermal Radiation and Cooling Technologies
- Physical Sciences › Energy › Renewable Energy, Sustainability and the Environment › Solar Thermal and Photovoltaic Systems
- Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
- Keywords
- flat plate solar collector, radiant floor cooling, cooling loop, heat loss analysis, floor surface temperature, cooling capacity, pressure drop, storage tanks
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review