Multiple quadrants displacement tracking control of independent metering electro-hydraulic system

Open access
Meng, Wang, Lutang, Li, Aihong, Wang, Hong, Ren, Youshan, Gao · 2024 · Scientific Reports

The DOI matches its Crossref record; 30 of the 30 references it cites were found in a registry or an index; 1 of the 24 sources its claims cite were checked for support.

Abstract

Aiming at the oscillation caused by the hydraulic cylinder of independent metering system (IMS) running between multiple working quadrants, a novel multiple quadrants switching displacement tracking control strategy is proposed in this paper. In this control strategy, both the cylinder chamber pressure under resistance and overrunning conditions are controlled by the inlet valve, and the outlet valve is utilized to control the displacement of cylinder. This method allows the hydraulic cylinder to always run in energy-efficient. When the working quadrant changes, the valve's working modes are unchanged, which avoids oscillation caused by changes of valves working modes in principle. And a reduced-order active disturbance rejective displacement controller and an active disturbance rejective pressure controller are designed to get high-precision tracking of the displacement and pressure. Numerous experimental results show that the proposed method is reasonable and effective, hydraulic cylinder operates smoothly between multiple quadrants, the pressure and displacement controllers have good anti-interference ability and robustness, and the energy consumption can be reduced by more than 23% compared to the traditional constant pressure valve control system.

Overview

CoChat Summary

## TL;DR

The paper proposes a multiple-quadrants displacement tracking control strategy for an independent metering electro-hydraulic system (IMS) that keeps valve operating modes unchanged while switching smoothly between resistance and overrunning conditions. Experiments on a test bench report stable displacement/pressure control and lower energy use than traditional constant-pressure valve control.

## Key findings

  • The proposed method controls the return-chamber pressure in resistance conditions and the inlet-chamber pressure in overrunning conditions using the inlet valve, while displacement is controlled by the outlet valve in both cases, allowing smooth quadrant switching without changing valve working modes.
  • In the RETOE experiment, displacement tracking error was maintained at about 3.5 mm, and in the OETRE experiment it was about 4.5 mm; the paper states the error did not oscillate after quadrant changes.
  • Compared with traditional constant pressure valve control (TCPVC), the proposed strategy reduced energy consumption from 11.92 kJ to 9.18 kJ in RETOE, a reduction of 2.74 kJ or 23%.
  • In OETRE, the proposed strategy used 8.4 kJ versus 13.1 kJ for TCPVC, reported as a 35.9% reduction; at system pressures of 90 bar, 100 bar, and 110 bar, energy consumption was reduced by 26.0%, 26.5%, and 27.8%, respectively, and the paper states energy saving was more than 40% at different pressures overall.

## Methods

  • The paper proposes a control strategy based on active disturbance rejection control (ADRC), with a reduced-order ADRC displacement controller and an ADRC pressure controller.
  • The study uses an IMS hydraulic test bench with a hydraulic cylinder, two proportional servo valves, a pump, a motor, load cylinder, reducing valves, transducers, and dSPACE control hardware; the sampling frequency is 1000 Hz.
  • Experimental verification includes quadrant-switching tests for resistance extension to overrunning extension (RETOE) and overrunning extension to resistance extension (OETRE), plus comparisons against traditional constant pressure valve control (TCPVC) and tests at different maximum system pressures.

## Limitations

  • The paper states that the process is verified by experiments on a test bench, and that future work will study more variable working conditions, apply the method to actual construction machinery, and compare it with existing control methods.
  • Evident from the text: the validation is limited to the reported bench experiments and the specific tested quadrants/pressure settings; the paper does not report field trials in real machinery.
  • Evident from the text: the controller design relies on simplified models and on measuring chamber pressures; the paper notes the hydraulic system is nonlinear and an accurate mathematical model cannot be established.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

Crossref · 10.1038/s41598-024-71147-2

Cites

30 of 30 references verified0 citation errors · 0 not checkable

Statistics

Nothing to recompute.

Figures

Fig. 1 Schematic diagram of IMS.
Fig. 1 Schematic diagram of IMS.CC BY-NC-ND · PubMed Central
Fig. 2 Multiple quadrants displacement tracking control strategy for IMS.
Fig. 2 Multiple quadrants displacement tracking control strategy for IMS.CC BY-NC-ND · PubMed Central
Fig. 3 Control structure diagram.
Fig. 3 Control structure diagram.CC BY-NC-ND · PubMed Central
Fig. 4 Picture and schematic diagram of the test bench.
Fig. 4 Picture and schematic diagram of the test bench.CC BY-NC-ND · PubMed Central
Fig. 5 Displacement control of RETOE.
Fig. 5 Displacement control of RETOE.CC BY-NC-ND · PubMed Central
Fig. 6 Pressure control of RETOE.
Fig. 6 Pressure control of RETOE.CC BY-NC-ND · PubMed Central
Fig. 7 Estimation of total disturbance.
Fig. 7 Estimation of total disturbance.CC BY-NC-ND · PubMed Central
Fig. 8 Input signals of vales.
Fig. 8 Input signals of vales.CC BY-NC-ND · PubMed Central
Fig. 9 Power and torque of motor.
Fig. 9 Power and torque of motor.CC BY-NC-ND · PubMed Central
Fig. 10 TCPVC displacement tracking errors of RETOE.
Fig. 10 TCPVC displacement tracking errors of RETOE.CC BY-NC-ND · PubMed Central
Fig. 11 Displacement control at different system pressures.
Fig. 11 Displacement control at different system pressures.CC BY-NC-ND · PubMed Central
Fig. 12 Pressure control at different system pressures.
Fig. 12 Pressure control at different system pressures.CC BY-NC-ND · PubMed Central
Fig. 13 Estimated total disturbance at different system pressures.
Fig. 13 Estimated total disturbance at different system pressures.CC BY-NC-ND · PubMed Central
Fig. 14 Input signals of valves at different system pressures.
Fig. 14 Input signals of valves at different system pressures.CC BY-NC-ND · PubMed Central
Fig. 15 Power and torque of motor at different system pressures.
Fig. 15 Power and torque of motor at different system pressures.CC BY-NC-ND · PubMed Central
Fig. 16 Energy consumption of motor at different pressures.
Fig. 16 Energy consumption of motor at different pressures.CC BY-NC-ND · PubMed Central
Fig. 17 Displacement control of OETRE.
Fig. 17 Displacement control of OETRE.CC BY-NC-ND · PubMed Central
Fig. 18 Pressure control of OETRE.
Fig. 18 Pressure control of OETRE.CC BY-NC-ND · PubMed Central
Fig. 19 Estimated total disturbances of OETRE.
Fig. 19 Estimated total disturbances of OETRE.CC BY-NC-ND · PubMed Central
Fig. 20 Input signals of valves.
Fig. 20 Input signals of valves.CC BY-NC-ND · PubMed Central
Fig. 21 Power and torque of motor.
Fig. 21 Power and torque of motor.CC BY-NC-ND · PubMed Central
Fig. 22 TCPVC displacement tracking errors of OETRE.
Fig. 22 TCPVC displacement tracking errors of OETRE.CC BY-NC-ND · PubMed Central
Fig. 23 Displacement control of OETRE at different pressures.
Fig. 23 Displacement control of OETRE at different pressures.CC BY-NC-ND · PubMed Central
Fig. 24 Pressure control of OETRE at different pressures.
Fig. 24 Pressure control of OETRE at different pressures.CC BY-NC-ND · PubMed Central
Fig. 25 Estimated total disturbances at different pressures.
Fig. 25 Estimated total disturbances at different pressures.CC BY-NC-ND · PubMed Central
Fig. 26 Input signals at different pressures.
Fig. 26 Input signals at different pressures.CC BY-NC-ND · PubMed Central
Fig. 27 Motor power and torque at different pressures.
Fig. 27 Motor power and torque at different pressures.CC BY-NC-ND · PubMed Central
Fig. 28 Motor energy consumption at different pressures.
Fig. 28 Motor energy consumption at different pressures.CC BY-NC-ND · PubMed Central

Verification

Claims the paper makes

1 Valid · 2 Not valid · 10 Not checked · 96 Own results and interpretations

43 more claims

Create a free account to see all 109 claims and to verify the 23 references still open.

See all claims — free account
  • It may state two separate claims as one. 53
  • Probably not a substantial claim. 18
  • The quote only partly states this claim. 4

Create a free account to see these claims.

Self-check

Percentages, sums and reported differences re-computed from the paper’s own numbers.

Each contradiction between two passages listed here was confirmed by an independent check.

1 of 1

Citations

Cites

Show all 30 references

Research works printed but not linked: 4

  1. Jin, M. & Wang, Q. Efficient pump and meter-out control for electrohydraulic system with time-varying negative load. Proc. IMechE Part I J. Syst. Control Eng. 232(9), 1170–1181 (2018).
  2. Chen, G., Wang, J., Wang, S. & Ma, L. Separate meter in and separate meter out energy saving control system using dual servo valves under complex load conditions. Trans. Beijing Inst. Technol. 36(10), 1053–1058 (2016).
  3. Chen, Z. et al. Motion control of independent metering electro-hydraulic system based on chamber pressure planning without mode switch. J. Mech. Eng. 60(02), 302–312 (2024).
  4. Gao, Z. Scaling and bandwidth-parameterization based controller tuning. In Proceedings of the 2003 American Control Conference, Denver, CO, USA 4989–4996 (2003).

Cited by

See all 3

Metadata

Authors
Meng, W., Lutang, L., Aihong, W., Hong, R., & Youshan, G.
Affiliations
Taiyuan University of Science and Technology (CN)
Venue
Scientific Reports
Published
2024-09-20
Volume
14
Issue
1
Pages
21951-21951
ISSN
2045-2322 (ISSN-L)
OpenAlex
W4402713457
Cited by
3
References
30
Citations by year
2026: 3
FWCI
0.40
Type
journal article
Language
en
Open access
Licence
Locations
  • Scientific Reports (publishedVersion, cc-by-nc-nd)
  • PubMed Central (publishedVersion, cc-by-nc-nd)
  • PubMed (publishedVersion)
  • DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
Funders
  • Dr. scientific research Startup Project of Taiyuan University of Science and Technology (20202030)
  • Shanxi Center of Technology Innovation for Electrohydraulic Control and Health Management of Heavy Machinery
  • TAIYUAN UNIVERSITY OF SCIENCE AND TECHNOLOGY SCIENTIFIC RESEARCH INITIAL FUNDING (20242038)
  • Fund Program for the Scientific Activities of Selected Returned 0verseas Professionals in Shanxi Province (20240021)
Topics
  • Physical Sciences › Engineering › Mechanical Engineering › Hydraulic and Pneumatic Systems
  • Physical Sciences › Engineering › Control and Systems Engineering › Adaptive Control of Nonlinear Systems
  • Physical Sciences › Engineering › Mechanical Engineering › Control Systems in Engineering
Keywords
electro-hydraulic systems, active disturbance rejection control, reduced-order control, pressure control, energy efficiency, robustness

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

The claim verdicts this report counts are experimental: their accuracy is not yet measured.

A language model drew the claims from the paper on 2026-10-11, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).

A second model labelled each claim on 2026-10-11 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Cited sources are checked with a language model’s help (qwen3.8-omni-flash).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

How to cite

Cite CoChat for the checks on this page, and the paper for its own findings.

This page
CoChat. (2026). Citation check: Multiple quadrants displacement tracking control of independent metering electro-hydraulic system. https://app.cochat.ai/papers/10.1038/s41598-024-71147-2
The paper
Meng, W., Lutang, L., Aihong, W., Hong, R., & Youshan, G. (2024). Multiple quadrants displacement tracking control of independent metering electro-hydraulic system. Scientific Reports. https://doi.org/10.1038/s41598-024-71147-2

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.