The DOI matches its Crossref record.
Energy Saving Lighting Control Systems for Open-Plan Offices: A Field Study
Abstract
We conducted a field study in a deep-plan office building equipped with suspended direct-indirect luminaires located centrally in cubicle workstations. In order to reduce lighting energy use, the luminaires employed integral occupancy sensors and light sensors (daylight harvesting), as well as individual dimming control accessed through occupants' computer screens. Data were collected from 86 workstations over a year to examine the energy savings and power reduction attributable to the controls, and how the controls were used. An awareness campaign that used e-mail reminders to encourage the occupants to use the individual control feature of the lighting system was also conducted. Results indicate that the lighting system generated substantial energy savings and peak power reductions compared to a conventional fluorescent lighting system installed on a neighboring floor. The installed lighting power was 42 percent lower than that of the conventional system. The three controls combined saved 42 to 47 percent in lighting energy use compared to the same lights used at full power during work-hours; this translated into overall savings of 67 to 69 percent compared to the conventional lighting system. If the three lighting controls systems had been installed separately, occupancy sensors would have saved, on average, 35 percent if used alone, light sensors (daylight harvesting) 20 percent, and individual dimming 11 percent. The light sensor savings were, as expected, higher in perimeter workstations, and would have matched the performance of the occupancy sensors with some modifications to the control parameters. The average daily peak power demand for lighting was also reduced by a similar amount, which resulted in an average effective lighting power density of only 3 W/m2. Although not detailed in this paper, surveys indicated that the studied lighting system was also associated with higher occupant satisfaction. This was likely due to the individual dimming control, although use of this control beyond an initial preferred setting was rare.
Overview
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cited by
Dubois, M.-C., & Blomsterberg, Å. (2011) · Energy and Buildings · doi:10.1016/j.enbuild.2011.07.001 · Cited by 361
A review of smart building sensing system for better indoor environment control
Dong, B., Prakash, V., Feng, F., & O'Neill, Z. (2019) · Energy and Buildings · doi:10.1016/j.enbuild.2019.06.025 · Cited by 360
O'Brien, W., & Gunay, H. B. (2014) · Building and Environment · doi:10.1016/j.buildenv.2014.03.024 · Cited by 294
A critical review of field implementations of occupant-centric building controls
Park, J. Y., Ouf, M. M., Gunay, B., Peng, Y., O'Brien, W., Kjærgaard, M. B., & Nagy, Z. (2019) · Building and Environment · doi:10.1016/j.buildenv.2019.106351 · Cited by 274
Boyano, A., Hernandez, P., & Wolf, O. (2013) · Energy and Buildings · doi:10.1016/j.enbuild.2013.05.039 · Cited by 189
Metadata
- Authors
- Galasiu, A. D., Newsham, G. R., Suvagau, C., & Sander, D. M.
- Venue
- LEUKOS
- Publisher
- Informa UK Limited
- Published
- 2007-07-01
- Volume
- 4
- Issue
- 1
- Pages
- 7-29
- ISSN
- 1550-2716 (ISSN-L)
- 1550-2724
- OpenAlex
- W1577582053
- Cited by
- 198
- References
- 0
- FWCI
- 22.98
- Type
- journal article
- Language
- en
- Open access
- closed
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: Energy Saving Lighting Control Systems for Open-Plan Offices: A Field Study. https://app.cochat.ai/papers/10.1582/leukos.2007.04.01.001
- The paper
- Galasiu, A. D., Newsham, G. R., Suvagau, C., & Sander, D. M. (2007). Energy Saving Lighting Control Systems for Open-Plan Offices: A Field Study. LEUKOS. https://doi.org/10.1582/leukos.2007.04.01.001
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.