Assessing the efficiency of measures to enhance electric power quality in variable-frequency drive for scraper conveyors
Open accessThe DOI matches its Crossref record; 10 of the 10 references it cites were found in a registry or an index; 1 of the 11 sources its claims cite were checked for support.
Abstract
The study develops a simulation model of a scraper conveyor VFD system and analyzes the impact of harmonic filters, reactors, and sine filters on electric power quality. It determines harmonic composition under maximum distortion conditions and develops practical recommendations for improving VFD power quality.
Overview
CoChat Summary
TL;DR
This paper uses a simulation model of a mine power distribution system with a variable-frequency drive for scraper conveyors to assess harmonic filters, reactors, and sine filters for electric power quality. It finds that reactors plus 5th/7th harmonic filters reduce voltage and current harmonic coefficients before the converter, but these measures have little effect on harmonic composition in insulation-leakage and residual-current-device circuits.
Key findings
- In the modeled system, without compensation the total voltage harmonic coefficient KU% before the converter was 2.81/2.77 and total current harmonic coefficient KI% was 80.45/80.89 (symmetrical/single-phase leakage modes). Reactors plus FCU-5 and FCU-7 reduced these to KU% = 0.51/0.31 and KI% = 5.63/3.46 before the converter; after the converter values remained about KU% ≈ 1.35 and KI% ≈ 0.29.
- A sine filter after the converter without FCU increased KU% to 5.68/5.67. Combined reactors + FCU-5 + FCU-7 + sine filter gave KU% = 0.40/0.37 and KI% = 1.89/1.08 before the converter, and KU% = 1.69/1.69 and KI% = 0.25/0.26 after the converter.
- Leakage-circuit harmonic composition was mainly determined by the output voltage modulated by the autonomous inverter. In symmetrical leakage, the largest current harmonic was the 7th, and the largest voltage harmonics were the 0th and 7th; in single-phase leakage through Rу = 1 kΩ, the largest current distortions were the 0th and 7th, and the largest voltage distortions were the 0th and 3rd. Table 2 reports total KI/KU of 56.91%/8.83% in symmetrical leakage and 33.03%/32.79% in single-phase leakage.
- The presence of harmonic filters, reactors, and sine filters had practically no effect on either the harmonic composition or the magnitudes of harmonic coefficients of phase voltage relative to ground and leakage currents through insulation. In RCD measuring circuits, the third harmonic was pronounced; in single-phase leakage KU(0) increased to 25%, KU(3) to 16%, and KI(3) to 8.5%, and an added filter improved RCD performance.
Methods
- Mathematical simulation modeling based on an equivalent circuit of a mine combined electrical network feeding a scraper conveyor VFD. The model included a mine transformer, automatic switch, AZUR-type residual-current device, magnetic starters, explosion-proof frequency converters, cable length 400–600 m, and 2–4 asynchronous motors SG3-450L-8/4 rated 110–400 kW, with a 250 kW equivalent motor and a WANTAI frequency converter; phase voltage was UF = 660 V.
- Insulation and leakage parameters: RI ≥ 300 kΩ/phase at industrial frequency; variable-frequency section RIA–RIC = 31.5–300 kΩ/phase and CIA–CIC = 0.01–1 µF/phase; single-phase leakage simulated with Rу = 1 kΩ as a human-body equivalent. A sine filter prototype PD-SIN-0.5-300 was used.
- The study analyzed spectral composition of higher harmonic voltage and current in power circuits, insulation-leakage circuits, and RCD measuring circuits under maximum distortion and with harmonic filters, reactors, and sine filters.
Limitations
- The paper does not include an explicit limitations section.
- Evident from the text: the analysis is based on simulation rather than field measurement, and the authors state that sine-filter analysis in underground networks may be only theoretical because of design limitations and difficulty selecting/tuning sine-filter parameters.
- Evident from the text: explosion-proof harmonic filters and sine filters for voltage classes up to 1140 V are not produced, with restrictions on mass-size parameters and a need for forced ventilation, which constrains practical installation.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Figures







Verification
Claims the paper makes
0 Valid · 6 Not valid · 7 Not checked · 25 Own results and interpretations
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The harmonic composition of voltage and current in the mine power distribution system is determined under maximum distortion conditions and in the presence of HFs, reactors, and sine filters.”
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
The paper states this without a source or data behind it here, so there is nothing to check it against. The quote shows it is in the paper.
In the paper
“It is noted that the harmonic composition of leakage voltage and current is primarily influenced by the parameters of the output voltage modulated by the autonomous frequency converter inverter.”
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: unclear — It is unclear why the paper says it holds.
The paper states this without a source or data behind it here, so there is nothing to check it against. The quote shows it is in the paper.
In the paper
“Interestingly, the presence of HFs, reactors, and sine filters does not significantly impact the harmonic composition or the magnitudes of coefficients of the harmonic components in the phase voltage of the system concerning ground and leakage currents through insulation.”
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: unclear — It is unclear why the paper says it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“При этом в режиме симметричной утечки величины KU(3) и KI(3) постоянной составляющей тре-тьей гармоники кратно превышают свои значения по сравнению с первой гармоникой.”
plainstates an association- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
The paper states this without a source or data behind it here, so there is nothing to check it against. The quote shows it is in the paper.
In the paper
“Это объясняется тем, что параметры силовой сети и параметры изоляции цепи утечки тока (вторичные цепи) различаются на 3–4 порядка.”
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: unclear — It is unclear why the paper says it holds.
15 more claims
Create a free account to see all 38 claims and every source verdict.
- It may state two separate claims as one. 15
- Probably not a substantial claim. 6
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
“Наибольшее искажение имеют 0-я и 7-я гармоники тока, а также 0-я и 3-я гар-моники напряжения.”
“0 1,05 9,92 41,43 41,45 2 0,40 0,20 0,57 0,57 3 10,5 3,52 25,95 25,85 4 0,75 0,19 3,07 3,05 5 11,10 2,23 19,60 19,40 6 3,02 0,51 1,45 1,43 7 52,58 7,59 1,95 1,87”
Citations
Cites
MINING INFORMATIONAL AND ANALYTICAL BULLETIN
(2024) · Горный информационно-аналитический бюллетень (научно-технический журнал) · doi:10.25018/0236_1493 · Cited by 214
Klyuev, R. V., Bosikov, I., Gavrina, O. A., & Lyashenko, V. I. (2021) · Gornye nauki i tekhnologii = Mining Science and Technology (Russia) · doi:10.17073/2500-0632-2021-3-211-220 · Cited by 25
Research on switching operation transient electromagnetic environment of substations in a coal mine
Feng, D., Lu, M., Lan, J., et al. (2016) · IET Generation Transmission & Distribution · doi:10.1049/iet-gtd.2016.0292 · Cited by 19
StecuĹ‚a, K., Brodny, J., & Tutak, M. (2017) · CBU International Conference Proceedings · doi:10.12955/cbup.v5.1099 · Cited by 13
Improving Energy Performance in Networks with Semiconductor Converters
Shevyrev, Y. V., Pichuev, A., & Shevyreva, N. Y. (2019) · doi:10.1109/icieam.2019.8743020 · Cited by 8
Self-citationPichuev, A. V., & Petrov, V. L. (2023) · Gornye nauki i tekhnologii = Mining Science and Technology (Russia) · doi:10.17073/2500-0632-2023-01-72 · Cited by 6
Self-citationPower quality in coal longwalls
Babokin, G. I., Shevyrev, Y. V., & Shevyreva, N. Y. (2021) · Gornyi Zhurnal · doi:10.17580/gzh.2021.07.14 · Cited by 4
Research on Dynamic Tension Control Theory for Heavy Scraper Conveyor
Shi, J. G., Mao, J., & Wei, X. H. (2010) · Applied Mechanics and Materials · doi:10.4028/www.scientific.net/amm.34-35.1956 · Cited by 4
Influence of process flow diagram and longwall length on specific energy consumption of shearers
Babokin, G. (2021) · Горный информационно-аналитический бюллетень (научно-технический журнал) · doi:10.25018/0236-1493-2021-2-0-139-149 · Cited by 4
ANALYSIS OF ELECTRICAL EQUIPMENT OPERATING MODES OF THE EXCAVATION SITE OF A MODERN COAL MINE
Kuzbass State Technical University after T. F. Gorbachev, VORONIN, V., NEPSHA, F., Kuzbass State Technical University after T. F. Gorbachev, ERMAKOV, A., Kuzbass State Technical University after T. F. Gorbachev, KANTOVICH, L., & MISIS, N. (2021) · Sustainable Development of Mountain Territories · doi:10.21177/1998-4502-2021-13-4-599-607 · Cited by 3
Research works printed but not linked: 5
- Пустоветов М. Ю. Опыт разработки синус-фильтра для силовой схемы частотно-регулируемого асин-хронного электропривода. Известия Томского политехнического университета. 2014;324(4):84–94. URL: http://earchive.tpu.ru/handle/11683/5238 Pustovetov M. Yu. Experience in developing sine-wave filter for power circuit of VVVF-drive with induction motor. Bulletin of the Tomsk Polytechnic University. 2014;324(4):84–94. (In Russ.) URL: http://earchive.tpu. ru/handle/11683/5238
- Наличие наводимых в цепях утечки тока выс-ших гармонических составляющих в симметричном режиме и режиме однофазной утечки тока может привести к нарушению магнитной совместимости при работе электронной измерительной схемы, блока питания и компенсатора емкостного тока утечки УЗО и представлять потенциальную опасность в случае прикосновения к токоведущим частям электрообору-дования. 69 ГОРНЫЕ НАУКИ И ТЕХНОЛОГИИ MINING SCIENCE AND TECHNOLOGY (RUSSIA) Petrov V. L., Pichuev A. V. Assessing the efficiency of measures to enhance electric power quality... 2024;9(1):60–69 https://mst.misis.ru/ eISSN 2500-0632 Pichuev A. V., Petrov V. L. Equivalent circuit for mine power distribution systems for the analysis of insulation leakage current. Mining Science and Technology (Russia). 2023;8(1):78–86. https://doi.org/10.17073/2500-0632-2023-01-72 · DOI · Paper page
- Бабокин Г. И., Куницкий В. Г., Шеленев П. И. Защитное отключение на постоянном оперативном токе для комбинированных шахтных сетей. Горный информационно-аналитический бюллетень. 2009;(S8):285–288. Babokin G. I., Kunitsky V. G., Shelenev P. I. Protective switching-off on a direct operating current for combined mine networks. Mining Informational and Analytical Bulletin. 2009;(S8):285–288. (In Russ.)
- Пичуев А. В., Петров В. Л. Обоснование схемы замещения шахтной подземной электрической сети для анализа режимов утечки тока через изоляцию. Горные науки и технологии. 2023;8(1):78-86. https://doi.org/10.17073/2500-0632-2023-01-72 Pichuev A. V., Petrov V. L. Equivalent circuit for mine power distribution systems for the analysis of insulation leakage current. Mining Science and Technology (Russia). 2023;8(1):78–86. https://doi.org/10.17073/2500-0632-2023-01-72 · DOI · Paper page
- Сыромятников И. А. Режимы работы асинхронных и синхронных двигателей. Под ред. Л. Г. Мами-конянца. 4-е изд., перераб. и доп. М.: Энергоатомиздат; 1984. 240 с. Syromyatnikov I. A. Operating modes of asynchronous and synchronous motors. Mamikonyants L. G. (Ed.) 4th ed., revised and additional. Moscow: Energoatomizdat; 1984. 240 p. (In Russ.)
Cited by
Analytical Diagnostic and Control System of Energy and Mechanical Efficiency of Electric Drives
Korolev, N. (2025) · Energies · doi:10.3390/en18092266 · Cited by 6
Pustovetov, M. (2024) · WSEAS Transactions on Circuits and Systems archive · doi:10.37394/23201.2024.23.23 · Cited by 2
Петров, В. Л., Burmatova, E. K., & Pichuev, A. (2025) · Gornye nauki i tekhnologii = Mining Science and Technology (Russia) · doi:10.17073/2500-0632-2025-09-461 · Cited by 1
Self-citationSemenov, A. S., Semenova, M. N., & Bebikhov, Y. V. (2025) · doi:10.1109/rusautocon65989.2025.11177305 · Cited by 1
Difficulties in Choosing Sine-Wave Filter Capacitances and Inductances
Pustovetov, M. (2025) · International Journal of Electrical Engineering and Computer Science · doi:10.37394/232027.2025.7.6 · Cited by 1
Metadata
- Authors
- Petrov, V. L., & Pichuev, A. V.
- Affiliations
- University of Science and Technology MISIS
- National University of Science and Technology (RU)
- Venue
- Gornye nauki i tekhnologii = Mining Science and Technology (Russia)
- Published
- 2024-04-03
- Volume
- 9
- Issue
- 1
- Pages
- 60-69
- ISSN
- 2500-0632 (ISSN-L)
- OpenAlex
- W4393987600
- Cited by
- 10
- References
- 10
- Citations by year
- 2026: 3 · 2025: 5 · 2024: 2
- FWCI
- 1.04
- Type
- journal article
- Language
- en
- Open access
- diamond
- doi.org
- Locations
- Gornye nauki i tekhnologii = Mining Science and Technology (Russia) (publishedVersion, cc-by)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Power Quality and Harmonics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Electric Power Systems and Control
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Electromagnetic Compatibility and Noise Suppression
- Keywords
- power quality, variable frequency drive, scraper conveyor, underground mining, higher harmonics, harmonic filters, reactors, residual current devices, electrical safety
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
The claim verdicts this report counts are experimental: their accuracy is not yet measured.
A language model drew the claims from the paper on 2026-09-30, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-09-30 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: Assessing the efficiency of measures to enhance electric power quality in variable-frequency drive for scraper conveyors. https://app.cochat.ai/papers/10.17073/2500-0632-2024-01-198
- The paper
- Petrov, V. L., & Pichuev, A. V. (2024). Assessing the efficiency of measures to enhance electric power quality in variable-frequency drive for scraper conveyors. Gornye nauki i tekhnologii = Mining Science and Technology (Russia). https://doi.org/10.17073/2500-0632-2024-01-198
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.