The DOI matches its Crossref record; 1 of the 1 references it cites were found in a registry or an index.
Modelling and testing a passive night-sky radiation system
Open accessAbstract
The as-built and tested passive night-sky radiation cooling/heating system considered in this investigation consists of a radiation panel, a cold water storage tank, a hot water storage tank, a room and the interconnecting pipework. The stored cold water can be used to cool a room during the day, particularly in summer. A theoretical time-dependent thermal performance model was also developed and compared with the experimental results and it is shown that the theoretical simulation model captures the experimental system performance to within a reasonable degree of accuracy. A natural circulation experimental set-up was constructed and subsequently used to show that under local (Stellenbosch, South Africa) conditions the typical heat-removal rate from the water in the tank is 55 W/m2 of radiating panel during the night; during the day the water in the hot water-storage tank was heated from 24 °C to 62 °C at a rate of 96 W/m2. The system was also able to cool the room at a rate of 120 W/m3. The results thus confirmed that it is entirely plausible to design an entirely passive system, that is, without the use of any moving mechanical equipment such as pumps and active controls, for both room-cooling and water-heating. It is thus concluded that a passive night-sky radiation cooling/heating system is a viable energy-saving option and that the theoretical simulation, as presented, can be used with confidence as an energy-saving system design and evaluation tool. Keywords: passive cooling and heating, buoyancy-driven fluid flow, theoretical simulation, experimental verification Highlights:Passively driven renewable energy heating and cooling systems are considered.Time-dependent mathematical simulation model is presented.Experimental buoyancy-driven heating and cooling system built and tested.Experimental results demonstrate the applicability of the theoretical simulation model.Saving and evaluation design tool.
Overview
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
Sky radiative cooling's restorative capacity after heatwaves is rated low to moderate, because cooling capacity can be reduced by increased humidity and outdoor temperatures at night.
“After heatwaves, the sky radiative cooling's restorative capacity was rated as low to moderate, as the cooling capacity could be reduced by increased humidity and outdoor temperatures also during night time [92,225,228].”
From Resilient cooling strategies – A critical review and qualitative assessment (2021) · cites this paper as [225]
Night sky radiative cooling is ready for market implementation because it can be employed through existing technologies such as solar collectors and PV/Ts.
“Moreover, it is ready for market implementation since it can be employed through existing technologies such as solar collectors and PV/Ts [222,223,225].”
From Resilient cooling strategies – A critical review and qualitative assessment (2021) · cites this paper as [225]
An increase in relative humidity (50 to 100%) and outdoor air temperature (9 K) can reduce the cooling power of thermal solar collectors by 18% to 41%, respectively.
“For example, an increase in relative humidity (50 to 100%) and outdoor air temperature (9 K) could reduce the cooling power of thermal solar collectors by 18% to 41%, respectively [225].”
From Resilient cooling strategies – A critical review and qualitative assessment (2021) · cites this paper as [225]
Citations
Cites
A study of a polymer-based radiative cooling system
Meir, M. G., Rekstad, J. B., & LØvvik, O. M. (2002) · Solar Energy · doi:10.1016/s0038-092x(03)00019-7 · Cited by 125
Flagged first, then by citations
Cited by
Sorted by citations
Resilient cooling strategies – A critical review and qualitative assessment
Zhang, C., Kazanci, O. B., Levinson, R., Heiselberg, P., Olesen, B. W., Chiesa, G., Sodagar, B., Ai, Z., Selkowitz, S., Zinzi, M., et al. (2021) · Energy and Buildings · doi:10.1016/j.enbuild.2021.111312 · Cited by 180
Metadata
- Authors
- Joubert, G. D., & Dobson, R. T.
- Affiliations
- Stellenbosch University (ZA)
- Venue
- Journal of Energy in Southern Africa
- Publisher
- Academy of Science of South Africa
- Published
- 2017-03-23
- Volume
- 28
- Issue
- 1
- Pages
- 76
- ISSN
- 1021-447X (ISSN-L)
- 2413-3051
- OpenAlex
- W2603730521
- Cited by
- 9
- References
- 1
- Citations by year
- 2026: 1 · 2022: 1 · 2021: 2 · 2019: 4 · 2017: 1
- FWCI
- 1.43
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Licence
- Locations
- Journal of Energy in Southern Africa (publishedVersion, cc-by-sa)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
- SUNScholar (Stellenbosch University) (submittedVersion)
- Topics
- Physical Sciences › Engineering › Civil and Structural Engineering › Thermal Radiation and Cooling Technologies
- Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
- Physical Sciences › Engineering › Building and Construction › Solar Energy Systems and Technologies
- Keywords
- passive heating, hot water storage tank, natural circulation, buoyancy-driven flow, room cooling, water heating, Stellenbosch
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review