The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions
Open accessAbstract
In hot dry regions, the building envelope receives abundant solar radiation, which contributes to heat stress and indoor thermal discomfort. To mitigate overheating inside spaces, cooling is the main basic requirement during most of the year. However, due to the harsh climatic conditions, buildings fail to provide passively the required comfort conditions. Consequently, they are fully dependent on-air conditioning systems, which are huge energy consumers. As roofs are exposed to the sun throughout the daytime, they are estimated to be the main source of heat stress. In return, they can contribute significantly to achieve optimum comfort and energy savings when efficient design strategies are used in an early design stage. To examine the potential for cooling load reduction and thermal comfort enhancement by using cooling roof techniques in residential buildings, a study was performed in the city of Biskra (southern Algeria). Accordingly, an in-field measurement campaign was carried out on test-cells during five days in summer. Three different cooling roof techniques were addressed: (a) cool reflective white paint (CR), (b) white ceramic tiles (CT) and (c) a cool-ventilated roof (C-VR). These roofing alternatives were investigated by monitoring both roof surface temperatures and indoor temperatures. Comparative analysis showed that a cool-ventilated roof is the most efficient solution, reducing the average indoor temperature by 4.95 °C. A dynamic simulation study was also performed based on TRNSYS software to determine the best roofing system alternatives in terms of thermal comfort and energy consumption, considering the hottest month of the year. Simulation tests were run on a base-case model representing the common individual residential buildings in Biskra. Results showed that a double-skin roof combined with cool-reflective paint is the most efficient roofing solution. By comparison to a conventional flat roof, meaningful improvements have been achieved, including reducing thermal discomfort hours by 45.29% and lowering cooling loads from 1121.91 kWh to 741.09 kWh.
Overview
CoChat Summary
TL;DR
This study evaluated three passive roof cooling techniques in hot-arid Biskra, Algeria, using test cells and TRNSYS simulations. The cool-ventilated roof (C-VR) performed best overall, with the largest reductions in indoor temperature, cooling load, and CO₂ emissions.
Key findings
- In field measurements over five summer days, the C-VR reduced indoor temperature the most and achieved a maximum average heat-gain reduction of 17.12 °C compared with the reference roof.
- The cool reflective roof (CR) lowered the external roof surface temperature from 57.22 °C to 37.27 °C, with a maximum decrease of 20.52 °C.
- Over 744 h in July, overheating hours were reduced from 721 h (96%) in the base case to 337 h (45.30%) with C-VR and to 342 h (45.96%) with CR.
- In the simulation, monthly cooling demand for the reference case was 1121.91 kWh and 729.24 kgCO₂; C-VR reduced this to 380.82 kWh and 247.53 kgCO₂, while CR reduced it to 613.31 kWh and 398.65 kgCO₂. The paper also reports average cooling reductions of 66.06% for C-VR and 45.33% for CR, and a reduction of 4.95 °C in average indoor temperature for C-VR.
Methods
- Comparative study in Biskra, southern Algeria, combining experimental monitoring of four identical test cells (reference roof, CR, CT, C-VR) and dynamic simulation with TRNSYS V17.
- Field monitoring was conducted in July over five successive days (5–9 July 2021), with measurements of indoor/outdoor air temperature, relative humidity, roof and ceiling surface temperatures, and air velocity in the roof cavity.
- The simulation model used a two-story single-family house representative of Biskra, was calibrated against measured indoor and outdoor temperatures using ASHRAE Guideline 14 metrics (MBE and CV(RMSE)), and then used to estimate thermal comfort, cooling energy use, and CO₂ emissions for July.
Limitations
- The paper states that the simulation covered only the hottest month (July), so it does not assess annual performance or cold-season effects.
- The authors note that further studies are needed to test the roof techniques on real-scale residential roofs under ambient conditions.
- Evident from the text: the experimental campaign was short (five days) and conducted under clear, sunny, no-wind conditions, so the results may not capture broader weather variability.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
0 Valid · 0 Not valid · 34 Not checked · 73 Own results and interpretations
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“As can be seen in Figure 10a, the daily variation of external surface temperature of C-VR and CR are quite similar during the whole time.”
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.1. Comparing Improvements in Thermal Behavior
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“In more detail, the profiles of C-VR and CR show the strong impact of the cool coating on the surface temperature distribution.”
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.1. Comparing Improvements in Thermal Behavior
boostedstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Likewise, using shading, ventilation and high solar reflectance proprieties can generate an important temperature reduction of about 19.39 °C.”
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.1. Comparing Improvements in Thermal Behavior
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“results of the simulations indicate an important decrease in the external surface temperature of the base-case roof that dropped from 57.22 °C to 37.27 °C due to the application of a cool paint on the rooftop.”
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.1. Comparing Improvements in Thermal Behavior
hedgedstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“When solar radiation intensity reached 745.90 W/m 2 , CR external surface temperature reached 37.27 °C at 16 pm.”
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.1. Comparing Improvements in Thermal Behavior
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
52 more claims
Create a free account to see all 107 claims and to verify the 8 references still open.
- It may state two separate claims as one. 40
- Probably not a substantial claim. 14
- The quote only partly states this claim. 2
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated major: it would touch a result — a value a result rests on, reported and recomputed p-values on opposite sides of the significance level, two passages that conflict with no sign which is right, or a cited work retracted before this paper was published.
In the paper
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.2. Improvement of Thermal Comfort
“For the base-case model (REF), the overheating period is extensive and adds up to 721 h over the month (96%).Accordingly, thermal comfort conditions are potentially ensured only for 5.24% of the relevant period (Figure 12).”
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.2. Improvement of Thermal Comfort
“For the base-case model (REF), the overheating period is extensive and adds up to 721 h over the month (96%).”
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 5.2.3. Energy Consumption and CO₂ Emissions
“Simulation results reveal that for CR (cool roof), the peak cooling consumption reached 612.01 kWh, which means that the solution cuts the electrical energy cooling demand by 45.45%, and thus substantially reduces the energy consumption by 508.60 kWh and CO₂ emissions by 330.59 KgCO₂.”
§ The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions > 6. Conclusions
“| CR | 613.31 | 508.60 | 45.33 | 398.65 |”
Citations
Cites
Passive building energy savings: A review of building envelope components
Sadineni, S. B., Madala, S., & Boehm, R. F. (2011) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2011.07.014 · Cited by 1,427
Santamouris, M., Synnefa, A., & Karlessi, T. (2011) · Solar Energy · doi:10.1016/j.solener.2010.12.023 · Cited by 970
Synnefa, A., Santamouris, M., & Akbari, H. (2007) · Energy and Buildings · doi:10.1016/j.enbuild.2007.01.004 · Cited by 566
Thermal assessment of extensive green roofs as passive tool for energy savings in buildings
Coma, J., Pérez, G., Solé, C., Castell, A., & Cabeza, L. F. (2016) · Renewable Energy · doi:10.1016/j.renene.2015.07.074 · Cited by 205
A study on the comparative review of cool roof thermal performance in various regions
Rawat, M., & Singh, R. N. (2022) · Energy and Built Environment · doi:10.1016/j.enbenv.2021.03.001 · Cited by 197
Dabaieh, M., Wanas, O., Hegazy, M. A., & Johansson, E. (2015) · Energy and Buildings · doi:10.1016/j.enbuild.2014.12.034 · Cited by 190
Self-citationSynnefa, A., Saliari, M., & Santamouris, M. (2012) · Energy and Buildings · doi:10.1016/j.enbuild.2012.01.044 · Cited by 186
Passive alternatives to mechanical air conditioning of building: A review
Samuel, D. G. L., Nagendra, S. M. S., & Maiya, M. P. (2013) · Building and Environment · doi:10.1016/j.buildenv.2013.04.016 · Cited by 184
Thermal performance of reflective materials applied to exterior building components—A review
Hernández-Pérez, I., Álvarez, G., Xamán, J., Zavala-Guillén, I., Arce, J., & Simá, E. (2014) · Energy and Buildings · doi:10.1016/j.enbuild.2014.05.008 · Cited by 167
Performance of different passive techniques for cooling of buildings in arid regions
Nahar, N. M., Sharma, P., & Purohit, M. M. (2003) · Building and Environment · doi:10.1016/s0360-1323(02)00029-x · Cited by 140
Research works printed but not linked: 1
- Akbari, H., Levinson, R., Miller, W., and Berdahl, P. (2020, July 10). Cool Colored Roofs to Save Energy and Improve Air Quality, Available online: http://www.osti.gov/scitech//servlets/purl/860746-D3V0Ei/.
Cited by
Ouanes, S., & Sriti, L. (2023) · Building and Environment · doi:10.1016/j.buildenv.2023.111099 · Cited by 76
Self-citationEnergy retrofitting using advanced building envelope materials for sustainable housing: A review
Ghazwani, K., Beach, T., & Rezgui, Y. (2024) · Building and Environment · doi:10.1016/j.buildenv.2024.112243 · Cited by 60
Affordable green materials for developed cool roof applications: A review
Basyouni, Y. A., & Mahmoud, H. (2024) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2024.114722 · Cited by 44
The effects and mechanisms of heat stress on mammalian oocyte and embryo development
Lang, L. I., Wang, Z. W., Liu, B., Chang-qing, S. H. E. N., Jing-yi, T. U., Shi-cheng, W. A. N. G., Rui-ling, L. E. I., Si-qi, P. E. N. G., Xiong, X. I. A. O., Yong-ju, Z. H. A. O., et al. (2024) · Journal of Thermal Biology · doi:10.1016/j.jtherbio.2024.103927 · Cited by 28
Ukey, R., & Aakash, C. (2024) · Building and Environment · doi:10.1016/j.buildenv.2024.111536 · Cited by 12
Metadata
- Authors
- Athmani, W., Sriti, L., Dabaieh, M., & Younsi, Z.
- Affiliations
- University of Biskra (DZ)
- Malmö University (SE)
- Hautes Études d'Ingénieur (FR)
- Corresponding author
- Athmani, Wafa
- Sriti, Leila
- Venue
- Buildings
- Publisher
- MDPI AG
- Published
- 2022-12-22
- Volume
- 13
- Issue
- 1
- Pages
- 21
- ISSN
- 2075-5309 (ISSN-L)
- OpenAlex
- W4312187223
- Cited by
- 49
- References
- 36
- Citations by year
- 2026: 15 · 2025: 15 · 2024: 13 · 2023: 6
- FWCI
- 3.72
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Licence
- Locations
- Buildings (publishedVersion, cc-by)
- KTH Publication Database DiVA (KTH Royal Institute of Technology) (submittedVersion, other-oa)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion)
- Topics
- Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
- Physical Sciences › Environmental Science › Environmental Engineering › Urban Heat Island Mitigation
- Physical Sciences › Engineering › Building and Construction › Solar Energy Systems and Technologies
- Keywords
- residential buildings, hot arid climate, thermal comfort, cooling load reduction, roof surface temperature, indoor temperature, building energy efficiency, Biskra
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
A language model drew the claims from the paper on 2026-10-10, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-10 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions. https://app.cochat.ai/papers/10.3390/buildings13010021
- The paper
- Athmani, W., Sriti, L., Dabaieh, M., & Younsi, Z. (2022). The Potential of Using Passive Cooling Roof Techniques to Improve Thermal Performance and Energy Efficiency of Residential Buildings in Hot Arid Regions. Buildings. https://doi.org/10.3390/buildings13010021
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.