Machine Learning-Based State Estimation for an Actual Transmission System Using Field PMU Data

Open access

The DOI matches its DataCite record; 27 of the 27 references it cites were found in a registry or an index; none of the 19 sources its claims cite is checked for support yet.

Abstract

Time-synchronized state estimation (SE) plays a critical role in ensuring real-time situational awareness in modern power systems. However, achieving full system observability using phasor measurement units (PMUs) is often impractical due to cost and deployment constraints. Moreover, SE operation at PMU timescales imposes stringent requirements on latency, robustness, and reliability that are difficult to satisfy using conventional iterative hybrid SE techniques under incomplete observability by PMUs. This paper evaluates the feasibility of deploying deep neural networks for PMU-timescale, time-synchronized SE in real-world PMU-unobservable transmission systems using actual data from a US power utility. Key contributions include a systematic assessment of estimation accuracy, scalability, and computational performance under realistic operating conditions.

Overview

CoChat Summary

TL;DR

This paper evaluates deep neural network-based time-synchronized state estimation (DNN-SE) on an actual US transmission system using field PMU data and historical SCADA data, despite only ~9% direct PMU observability. It reports low errors on a held-out synthetic test set and fast inference, while field-data accuracy depends on load variability and requires bad-data detection and replacement.

Key findings

  • On the held-out synthetic test set with exact ground truth, DNN-SE V and DNN-SE VI achieved voltage magnitude MAPE of 0.250% and 0.202%, and phase angle MAE of 0.042° and 0.041°, respectively; DNN-SE VI outperformed DNN-SE V owing to current phasor measurements.
  • On field PMU data under original load variability, DNN-SE VI achieved MAPE 0.396% and MAE 0.851°, versus DNN-SE V MAPE 0.688% and MAE 1.274°; under reduced 5% load variation, DNN-SE VI improved to MAPE 0.083% and MAE 0.177° (DNN-SE V: 0.150% and 0.209°).
  • Voltage magnitude accuracy satisfied the IEEE 1% TVE threshold across all evaluation settings; phase angle accuracy met the corresponding 0.573° threshold under reduced 5% load variability but exceeded it under original load variability.
  • Average online inference times were approximately 1.5 × 10⁻⁴ s for DNN-SE V and 2.0 × 10⁻⁴ s for DNN-SE VI, well within the ≤33 ms PMU reporting interval; BDDR completed within 33 ms and substantially reduced voltage magnitude estimation errors at five anonymized PMU-equipped buses.

Methods

  • Validation study on an anonymized actual US transmission system (“System S”): multi-area network with thousands of buses from 69 kV to 500 kV, 1,493 transmission buses ≥69 kV, and approximately 133 PMU-monitored buses (~9% direct observability). Historical SCADA snapshots covered six months (July 1–December 31, two per day at 2:00 PM and 2:30 PM, ~366 raw files); field PMU data were 1 frame/s over 2:00–3:00 PM on August 15.
  • Offline training used a dominant topology T (mid-July through mid-August) with ~70 SCADA cases (July 12–August 15). KDE-based load characterization and random sampling generated 25,000 operating conditions; PSS/E power flow produced reference voltage magnitudes and angles for all buses, while PMU voltage/current phasors at installed locations served as inputs. Synthetic cases were split 65% training, 20% validation, and 15% test.
  • DNN-SE models were feed-forward fully connected Keras/TensorFlow networks: DNN-SE V input dimension 266, DNN-SE VI input dimension 746, output dimension 2,986; 4 hidden layers with 1,500/2,000 neurons, ReLU, linear output, MSE loss, Adam, learning rate 0.001, dropout 0.3, batch size 300, 300 epochs, and batch normalization. Online evaluation used PMU data from 2:25–2:30 PM (~300 samples), preprocessing (cleaning, reference alignment, angle unwrapping), prior-window normalization, and Wald-test BDDR; evaluation used common states, SCADA snapshots, and a held-out synthetic test set.

Limitations

  • Stated: field PMU validation is limited to one dominant topology and a five-minute evaluation window; future work includes extending validation across topology transitions, adding contingency/extreme-event scenarios, and adding operator flags for BDDR-identified bad measurements.
  • Stated: no exact ground-truth state labels exist for field PMU data; SCADA snapshots are not time-synchronized and only approximate system state; PF-derived states are treated as best-available reference labels rather than exact ground truth; and a training/test distribution mismatch exists because training uses synthetic SCADA/PF data while testing uses field PMU streams.
  • Evident from the text: historical SCADA data were limited (~70 cases for topology T, ~366 raw files over six months), requiring KDE-based augmentation; the analysis is based on an anonymized single utility system and one selected topology, so generalization to other systems or topologies is not demonstrated; and phase angle errors exceeded the IEEE threshold under original load variability.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

DataCite · 10.48550/arxiv.2609.25566

Cites

27 of 27 references verified0 citation errors · 0 not checkable

Statistics

Nothing to recompute.

Verification

Claims the paper makes

0 Valid · 0 Not valid · 13 Not checked · 45 Own results and interpretations

33 more claims

Create a free account to see all 58 claims and to verify the 12 references still open.

See all claims — free account
  • It may state two separate claims as one. 18
  • Probably not a substantial claim. 6
  • The quote only partly states this claim. 1

Create a free account to see these claims.

Citations

Cites

Research works printed but not linked: 2

  1. Azimian, B., Moshtagh, S., Pal, A., & Ma, S. (2023). Analytical verification of performance of deep neural network based time-synchronized distribution system state estimation. Journal of Modern Power Systems and Clean Energy, 12(4), 1126-1134.
  2. Mendel, J. M. (1995). Lessons in estimation theory for signal processing, communications, and control. Prentice Hall.

Cited by

Still being checked.

Metadata

Authors
Moshtagh, S., Thakkar, N., Pal, A., & Farantatos, E.
Affiliations
  • Arizona State University (US)
  • Electric Power Research Institute (US)
Venue
arXiv
Publisher
arXiv
Published
2026
ISSN
2331-8422 (ISSN-L)
OpenAlex
W7214093354
Cited by
0
References
25
Type
posted content
Language
en
Open access
Locations
arXiv (Cornell University) (submittedVersion)
Funders
  • National Science Foundation (2145063)
  • U.S. Department of Energy
  • Electric Power Research Institute
  • Division of Electrical, Communications and Cyber Systems
Topics
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Power System Optimization and Stability
  • Physical Sciences › Engineering › Control and Systems Engineering › Smart Grid Security and Resilience
  • Physical Sciences › Engineering › Control and Systems Engineering › Power Systems Fault Detection
Keywords
state estimation, phasor measurement units, deep neural network, transmission systems, incomplete observability, real-time situational awareness, hybrid state estimation, estimation accuracy, computational performance

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

A language model drew the claims from the paper on 2026-11-24, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).

A second model labelled each claim on 2026-11-24 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.