Optimal design of fan-supplied tube-fin evaporators subjected to frosting conditions aiming at minimum energy consumption

Ribeiro, Rafael S., da Silva, Diogo L., Hermes, Christian J. L. · 2018 · Journal of the Brazilian Society of Mechanical Sciences and Engineering

The DOI matches its Crossref record; 27 of the 27 references it cites were found in a registry or an index; 3 of the 11 sources its claims cite were checked for support.

Abstract

This work is focused on the optimal sizing of fan-supplied tube-fin evaporators for light commercial refrigerators operating under frosting conditions. Quasi-steady-state algebraic models were put forward for the refrigeration cycle and its components for computing not only the cooling capacity depletion due to the evaporator frosting over time, but also the changes experienced by the evaporating temperature and its effect on the compression power. Transient algebraic models were also advanced to account for the temperature and humidity variations inside the refrigerated compartment, and so the compressor runtime. Both component-level and system-level optimization exercises were performed for sizing the evaporator. The former was focused on the local entropy generation minimization, considering the irreversibilities due to heat transfer, mass transfer and pressure drop that take place at the evaporator, whereas the latter was aimed at the overall energy consumption of the refrigerator, including not only the compression power, but also the heat dissipation within the refrigerated compartment by the defrost heater and the evaporator fan. Notwithstanding the time-averaged cooling capacity and the evaporator envelope have been held constrained, the component-level and the system-level optimization procedures led to different evaporator designs.

Overview

CoChat Summary

TL;DR

This paper simulates and optimizes fan-supplied tube-fin evaporators for a 200-can beverage cooler under frosting, comparing component-level entropy generation minimization with system-level energy consumption minimization. It finds different optimal geometries at each level, with system energy consumption minimized near \(N_{tr}=N_{lo}=4\) at about 128 kWh/month and robust across several aspect ratios.

Key findings

  • Component-level optimization, considering only external evaporator irreversibilities with volume and height constrained (3-L, \(N_{tr}=6\)), gave sub-optimal \(N_{fin}\approx75\) and \(N_{lo}\approx4\).
  • System-level entropy generation optimization, including internal and external irreversibilities, shifted the sub-optimum to \(N_{lo}\approx5\) and \(N_{fin}\approx60\), with higher entropy generation than the component-level case.
  • Final system-level energy consumption minimization, with volume and width constrained (3-L, \(N_{fin}=103\)), reached a minimum of \(\approx128\) kWh/month for non-integer \(N_{tr}\) and \(N_{lo}\) close to \(N_{tr}=N_{lo}=4\); configurations \((3\times6)\), \((4\times4)\), and \((6\times3)\) all led to about 129 kWh/month.
  • The system runtime to reach periodic-steady-state conditions was quite insensitive to evaporator geometry, and the model validation followed experimental trends satisfactorily, especially after early transients from 10 min on.

Methods

  • Algebraic submodels were coupled for the refrigeration loop, refrigerated compartment, evaporator heat and mass transfer, and frost growth/densification; the system was a 200-can beverage cooler with R134a, fixed condensing temperature at 40 °C, on-off control to keep the cabinet load at 5 °C ± 2.5 °C, and surroundings at 32 °C and 80% RH.
  • The equation set was solved iteratively with a 60 s time step, and simulations ran over longer periods (~12 h) until average cooling capacity reached the average cabinet thermal load; defrost occurred whenever frost blocked 70% of the evaporator face area (\(A_c/WH<0.3\)).
  • Optimization used exhaustive search by varying two of \(N_{fin}\), \(N_{tr}\), and \(N_{lo}\) while holding the third fixed and applying volume/height/width constraints; objective functions were time-averaged entropy generation and total energy consumption including compressor, fan, and defrost heater.
  • Validation compared calculated cooling capacity and air flow rate against experimental data from [26] for different fin numbers (71, 103, 151) at \(T_w=-10\) °C, \(T_i=2.5\) °C, and \(\omega_i=3.9\) g/kg.

Limitations

  • Stated: the frost growth model assumes uniform frost formation, distributing frost mass evenly over the evaporator surface, whereas real frost is more likely to build up at the first rows due to higher mass transfer coefficient and humidity gradient; a distributed evaporator frosting model is needed.
  • Stated: earlier entropy-generation analyses used fixed air-side conditions at the evaporator inlet, which is not realistic for refrigerators under on-off control, and did not account for defrost in those comparisons.
  • Evident from the text: the evaporator model assumes uniform surface temperature over the coil and one-dimensional air flow, and the condensing temperature is held fixed at 40 °C, which may limit generality.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

Crossref · 10.1007/s40430-018-1401-4

Cites

27 of 27 references verified0 citation errors · 0 not checkable

Statistics

Nothing to recompute.

Verification

Claims the paper makes

3 Valid · 0 Not valid · 7 Not checked · 17 Own results and interpretations

17 more claims

Create a free account to see all 27 claims and to verify the 1 reference still open.

See all claims — free account
  • It may state two separate claims as one. 4
  • Probably not a substantial claim. 2

Create a free account to see these claims.

Self-check

Percentages, sums and reported differences re-computed from the paper’s own numbers.

Each contradiction between two passages listed here was confirmed by an independent check.

3 of 3

Citations

Cites

Show all 27 references

Research works printed but not linked: 2

  1. 10. Stoecker WF (1957) How frost formation on coils affects refrigeration systems. Refrig Eng 65(2):42-46
  2. 28. Ribeiro RS (2016) Thermodynamic analysis of tube-fin evaporators subjected to frosting conditions. MEng thesis, Department of Mechanical Engineering, Federal University of Paraná, CuritibaPR, Brazil (in Portuguese) <!-- image -->

Cited by

See all 1

Metadata

Authors
Ribeiro, R. S., da Silva, D. L., & Hermes, C. J. L.
Affiliations
  • Universidade Federal do Paraná (BR)
  • Universidade Federal de Santa Catarina (BR)
Corresponding author
Hermes, Christian J. L.
Venue
Journal of the Brazilian Society of Mechanical Sciences and Engineering
Published
2018-09-12
Volume
40
Issue
10
ISSN
  • 1678-5878 (ISSN-L)
  • 1806-3691
OpenAlex
W2891534289
Cited by
1
References
26
Citations by year
2021: 1
FWCI
0.16
Type
journal article
Language
en
Open access
closed
Licence
www.springer.com/tdm (tdm)
Locations
Journal of the Brazilian Society of Mechanical Sciences and Engineering (publishedVersion)
Funders
CNPq (441603/2014-9)
Topics
  • Physical Sciences › Engineering › Mechanical Engineering › Refrigeration and Air Conditioning Technologies
  • Physical Sciences › Engineering › Mechanical Engineering › Heat Transfer and Optimization
  • Physical Sciences › Engineering › Mechanical Engineering › Adsorption and Cooling Systems
Keywords
entropy generation minimization, refrigeration cycle modeling, energy optimization, irreversibility

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

The claim verdicts this report counts are experimental: their accuracy is not yet measured.

A language model drew the claims from the paper on 2026-10-21, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).

A second model labelled each claim on 2026-10-21 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Cited sources are checked with a language model’s help (gpt-6-sol).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

How to cite

Cite CoChat for the checks on this page, and the paper for its own findings.

This page
CoChat. (2026). Citation check: Optimal design of fan-supplied tube-fin evaporators subjected to frosting conditions aiming at minimum energy consumption. https://app.cochat.ai/papers/10.1007/s40430-018-1401-4
The paper
Ribeiro, R. S., da Silva, D. L., & Hermes, C. J. L. (2018). Optimal design of fan-supplied tube-fin evaporators subjected to frosting conditions aiming at minimum energy consumption. Journal of the Brazilian Society of Mechanical Sciences and Engineering. https://doi.org/10.1007/s40430-018-1401-4

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.