Optimal design of fan-supplied tube-fin evaporators subjected to frosting conditions aiming at minimum energy consumption
The DOI matches its Crossref record; 27 of the 27 references it cites were found in a registry or an index; 3 of the 11 sources its claims cite were checked for support.
Abstract
This work is focused on the optimal sizing of fan-supplied tube-fin evaporators for light commercial refrigerators operating under frosting conditions. Quasi-steady-state algebraic models were put forward for the refrigeration cycle and its components for computing not only the cooling capacity depletion due to the evaporator frosting over time, but also the changes experienced by the evaporating temperature and its effect on the compression power. Transient algebraic models were also advanced to account for the temperature and humidity variations inside the refrigerated compartment, and so the compressor runtime. Both component-level and system-level optimization exercises were performed for sizing the evaporator. The former was focused on the local entropy generation minimization, considering the irreversibilities due to heat transfer, mass transfer and pressure drop that take place at the evaporator, whereas the latter was aimed at the overall energy consumption of the refrigerator, including not only the compression power, but also the heat dissipation within the refrigerated compartment by the defrost heater and the evaporator fan. Notwithstanding the time-averaged cooling capacity and the evaporator envelope have been held constrained, the component-level and the system-level optimization procedures led to different evaporator designs.
Overview
CoChat Summary
TL;DR
This paper simulates and optimizes fan-supplied tube-fin evaporators for a 200-can beverage cooler under frosting, comparing component-level entropy generation minimization with system-level energy consumption minimization. It finds different optimal geometries at each level, with system energy consumption minimized near \(N_{tr}=N_{lo}=4\) at about 128 kWh/month and robust across several aspect ratios.
Key findings
- Component-level optimization, considering only external evaporator irreversibilities with volume and height constrained (3-L, \(N_{tr}=6\)), gave sub-optimal \(N_{fin}\approx75\) and \(N_{lo}\approx4\).
- System-level entropy generation optimization, including internal and external irreversibilities, shifted the sub-optimum to \(N_{lo}\approx5\) and \(N_{fin}\approx60\), with higher entropy generation than the component-level case.
- Final system-level energy consumption minimization, with volume and width constrained (3-L, \(N_{fin}=103\)), reached a minimum of \(\approx128\) kWh/month for non-integer \(N_{tr}\) and \(N_{lo}\) close to \(N_{tr}=N_{lo}=4\); configurations \((3\times6)\), \((4\times4)\), and \((6\times3)\) all led to about 129 kWh/month.
- The system runtime to reach periodic-steady-state conditions was quite insensitive to evaporator geometry, and the model validation followed experimental trends satisfactorily, especially after early transients from 10 min on.
Methods
- Algebraic submodels were coupled for the refrigeration loop, refrigerated compartment, evaporator heat and mass transfer, and frost growth/densification; the system was a 200-can beverage cooler with R134a, fixed condensing temperature at 40 °C, on-off control to keep the cabinet load at 5 °C ± 2.5 °C, and surroundings at 32 °C and 80% RH.
- The equation set was solved iteratively with a 60 s time step, and simulations ran over longer periods (~12 h) until average cooling capacity reached the average cabinet thermal load; defrost occurred whenever frost blocked 70% of the evaporator face area (\(A_c/WH<0.3\)).
- Optimization used exhaustive search by varying two of \(N_{fin}\), \(N_{tr}\), and \(N_{lo}\) while holding the third fixed and applying volume/height/width constraints; objective functions were time-averaged entropy generation and total energy consumption including compressor, fan, and defrost heater.
- Validation compared calculated cooling capacity and air flow rate against experimental data from [26] for different fin numbers (71, 103, 151) at \(T_w=-10\) °C, \(T_i=2.5\) °C, and \(\omega_i=3.9\) g/kg.
Limitations
- Stated: the frost growth model assumes uniform frost formation, distributing frost mass evenly over the evaporator surface, whereas real frost is more likely to build up at the first rows due to higher mass transfer coefficient and humidity gradient; a distributed evaporator frosting model is needed.
- Stated: earlier entropy-generation analyses used fixed air-side conditions at the evaporator inlet, which is not realistic for refrigerators under on-off control, and did not account for defrost in those comparisons.
- Evident from the text: the evaporator model assumes uniform surface temperature over the coil and one-dimensional air flow, and the condensing temperature is held fixed at 40 °C, which may limit generality.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
3 Valid · 0 Not valid · 7 Not checked · 17 Own results and interpretations
Every source the paper cites for this claim was checked and supports it.
In the paper
“in a prior work, Ribeiro and Hermes [12] advanced a fully algebraic model to simulate the thermal-hydraulic behavior of fan-supplied tube-fin evaporators running under frosting conditions, which is able to predict the capacity depletion caused by the air flow rate reduction due to the frost blocking, and the augmentation in the heat transfer resistance due to the reduced thermal conductivity of”
What the sources say
- Supportedcites [12] 12. Ribeiro RS, Hermes CJL (2014) Algebraic modeling and thermodynamic design of fan-supplied tube-fin evaporators running under frosting conditions. Appl Therm Eng 70:552-559 source
Split into 2 atoms — 2 confirmed, 0 partially supported, 0 disputed, 0 misattributed, 0 unverifiable. Expand the claim to see per-atom verdicts.
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Supported
Every source the paper cites for this claim was checked and supports it.
In the paper
“The analysis leads to an entropy generation minimization path toward higher face areas and heat exchanger lengths (see Fig. 6a), thus contradicting the predictions reported in [12], which pointed out slender (high aspect ratio) designs as the ones which generate the minimum amount of entropy (see Fig. 6b).”
What the sources say
- Supportedcites [12] 12. Ribeiro RS, Hermes CJL (2014) Algebraic modeling and thermodynamic design of fan-supplied tube-fin evaporators running under frosting conditions. Appl Therm Eng 70:552-559 source
The Abstract (p. 2) says high-aspect-ratio designs minimize entropy generation under fixed heat duty and fan-constrained airflow. The Final Remarks (p. 9) likewise report lower entropy generation for slender evaporators, while noting their shorter runtime. (LLM, conf=0.94)
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Supported
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“It can be also noted that the heat exchanger with a high number of fins provides a higher cooling capacity, which is due to the higher heat transfer (finned) surface, while operating under lower air flow rates because of the increased pressure drop.”
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Significantly higher figures for the rate of entropy generation can be observed in Fig. 9 (in comparison with Fig. 8, as both the internal and external irreversibilities are now being taken into account)”
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Hence, in the case where both the evaporator volume and height were set as design constraints (3-L, N tr = 6), a region of minimum entropy generation was observed, as illustrated in Fig. 8, where the bulleted-dashed-line indicates the 3-L volume constraint. Marching along the constraint from the bottom corner up in Fig. 8, one can find out sub-optimal figures for the number of fins ( N fi n ≈ 75)”
- Also stated in: § 6 Concluding remarks · p. 10 · plain
“While the former points out a lower number of longitudinal tubes ( N lo = 4) and a higher number of fins ( N fi n ≈ 75) as the best design”
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Rests on 4 assumptions not shown here.
- Also stated in: § 6 Concluding remarks · p. 10 · plain
17 more claims
Create a free account to see all 27 claims and to verify the 1 reference still open.
- It may state two separate claims as one. 4
- Probably not a substantial claim. 2
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ 3.1 Frost growth and densification · p. 5
“The frost growth and densification submodel is based on the algebraic approach proposed by Hermes [26], which was originally developed for horizontal flat plates”
§ References · p. 11
“26. Da Silva DL, Hermes CJL, Melo C (2011) Experimental study of frost accumulation on fan-supplied tube-fin evaporators. Appl Therm Eng 31:1013-1020”
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ 5 System-level optimization · p. 8
“summing up the internal (Eq. 12) and external (Eq. 3) irreversibilities in Eq. (17)”
§ 3 Evaporator heat and mass transfer · p. 5
“The rate of entropy generated externally on the evaporator coil was calculated as follows [12]: <!-- formula-not-decoded --> The first term in the right-hand side stands for the entropy generation due to heat transfer, the second term is related to the mass transfer, and the third term to the pumping power. The term related to the conjugate heat and mass transfer was disregarded in this work as it plays a minor role on the total rate of entropy generation. In Eq. (12)”
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ 3 Evaporator heat and mass transfer · p. 4
“y ( t + Δ t ) = b / a + ( y ( t ) -b / a ) exp(a Δ t )”
§ 3 Evaporator heat and mass transfer · p. 4
“d y /d t + ay = b”
Citations
Cites
Stoecker, W. F. (1971) · Virtual Defense Library (Ministerio de Defensa) · Cited by 294
A study of frost growth and densification on flat surfaces
Hermes, C. J. L., Piucco, R. O., Barbosa, J. R., & Melo, C. (2009) · Experimental Thermal and Fluid Science · doi:10.1016/j.expthermflusci.2008.10.006 · Cited by 257
Self-citationNew model for frost growth rate
Na, B., & Webb, R. L. (2004) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2003.09.001 · Cited by 212
Jaluria, Y. (2018) · Handbook of Thermal Science and Engineering · doi:10.1007/978-3-319-26695-4_67 · Cited by 196
Experimental study of frost accumulation on fan-supplied tube-fin evaporators
da Silva, D. L., Hermes, C. J. L., & Melo, C. (2011) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2010.11.006 · Cited by 118
Self-citationAn analytical solution to the problem of frost growth and densification on flat surfaces
Hermes, C. J. L. (2012) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2012.06.070 · Cited by 103
Self-citationModeling for predicting frosting behavior of a fin–tube heat exchanger
Yang, D.-K., Lee, K.-S., & Song, S. (2006) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2005.09.022 · Cited by 94
A mathematical model for frost growth and densification on flat surfaces
ElCheikh, A., & Jacobi, A. M. (2014) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2014.05.054 · Cited by 92
Ye, H.-Y., & Lee, K.-S. (2013) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2013.08.026 · Cited by 70
First-principles modeling of frost accumulation on fan-supplied tube-fin evaporators
da Silva, D. L., Hermes, C. J. L., & Melo, C. (2011) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2011.04.029 · Cited by 70
Self-citationTransient simulation of household refrigerators: A semi-empirical quasi-steady approach
Borges, B. N., Hermes, C. J. L., Gonçalves, J. M., & Melo, C. (2010) · Applied Energy · doi:10.1016/j.apenergy.2010.09.019 · Cited by 69
Self-citationModeling of frost formation over parallel cold plates considering a two-dimensional growth rate
Armengol, J. M., Salinas, C. T., Xamán, J., & Ismail, K. A. R. (2016) · International Journal of Thermal Sciences · doi:10.1016/j.ijthermalsci.2016.01.017 · Cited by 69
Modeling non-uniform frost growth on a fin-and-tube heat exchanger
Padhmanabhan, S. K., Fisher, D. E., Cremaschi, L., & Moallem, E. (2011) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2011.06.005 · Cited by 66
Frost deposition in a parallel plate channel under laminar flow conditions
Lüer, A., & Beer, H. (2000) · International Journal of Thermal Sciences · doi:10.1016/s1290-0729(00)00193-8 · Cited by 64
Fan supplied heat exchanger fin performance under frosting conditions
Chen, H., Thomas, L., & Besant, R. W. (2003) · International Journal of Refrigeration · doi:10.1016/s0140-7007(02)00011-7 · Cited by 59
Effect of frost morphology on the thermal-hydraulic performance of fan-supplied tube-fin evaporators
da Silva, D. L., Melo, C., & Hermes, C. J. L. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.09.165 · Cited by 58
Self-citationHuang, J.-M., Hsieh, W. C., Ke, X.-J., & Wang, C. (2007) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2007.06.020 · Cited by 48
Two design aspects of defrosting refrigerators
Radcenco, V, Vargas, J. V. C., Bejan, A., & Lim, J. S. (1995) · International Journal of Refrigeration · doi:10.1016/0140-7007(94)00003-g · Cited by 42
Machielsen, C., & Kerschbaumer, H. G. (1989) · International Journal of Refrigeration · doi:10.1016/0140-7007(89)90095-9 · Cited by 34
Bejan, A., Vargas, J. V. C., & Lim, J. S. (1994) · International Journal of Heat and Mass Transfer · doi:10.1016/0017-9310(94)90087-6 · Cited by 33
de Loyola, F. R., Junior, V. S. D. N., & Hermes, C. J. L. (2014) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2014.08.055 · Cited by 28
Self-citationOptimal defrost cycle for air coolers revisited: A study of fan-supplied tube-fin evaporators
da Silva, D. L., & Hermes, C. J. L. (2018) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2018.02.009 · Cited by 22
Self-citationOptimal defrost cycle for the air cooler
Zakrzewski, B. (1984) · International Journal of Refrigeration · doi:10.1016/0140-7007(84)90051-3 · Cited by 20 · cited 2×
“Moreover, some efforts have been made to find out the defrost cycle parameters [20–23] that maximize the cooling capacity since Zakrzewski [20] pointed out that there must be an optimal time between two consecutive defrost operations.”
BackgroundRibeiro, R. S., & Hermes, C. J. L. (2014) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2014.05.012 · Cited by 19 · cited 12×
“It is worth of note that, where it reads ‘dimensionless entropy generation rate’ in [12], it should read instead ‘the product of the dimensionless entropy generation rate by the heat transfer area’.”
BackgroundMethodResultInfluentialSelf-citationNew frost property correlations for a flat-finned-tube heat exchanger
Getu, H. M., & Bansal, P. K. (2011) · International Journal of Thermal Sciences · doi:10.1016/j.ijthermalsci.2010.11.007 · Cited by 12
First-principles simulation of frost accumulation on fan-supplied tube-fin evaporators.
da, S. D. L., Hermes, C. J. L., & Melo, C. (2011) · Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development. · Cited by 11
Self-citationNumerical analysis of the frosting performance of the air-side of a heat pump.
Popovac, M., Seichter, S., Beňovský, P., & al., E. (2015) · Institut International du Froid · doi:10.18462/iir.icr.2015.0028 · Cited by 11
Research works printed but not linked: 2
- 10. Stoecker WF (1957) How frost formation on coils affects refrigeration systems. Refrig Eng 65(2):42-46
- 28. Ribeiro RS (2016) Thermodynamic analysis of tube-fin evaporators subjected to frosting conditions. MEng thesis, Department of Mechanical Engineering, Federal University of Paraná, CuritibaPR, Brazil (in Portuguese) <!-- image -->
Cited by
Ocak, C., Erten, S., Işgen, F., Arslan, E., Koşan, M., DEMİRCİ, E., & Aktaş, M. (2021) · Düzce Üniversitesi Bilim ve Teknoloji Dergisi · doi:10.29130/dubited.840795 · Cited by 1
Metadata
- Authors
- Ribeiro, R. S., da Silva, D. L., & Hermes, C. J. L.
- Affiliations
- Universidade Federal do Paraná (BR)
- Universidade Federal de Santa Catarina (BR)
- Corresponding author
- Hermes, Christian J. L.
- ORCID
- Ribeiro, Rafael S.
- Venue
- Journal of the Brazilian Society of Mechanical Sciences and Engineering
- Published
- 2018-09-12
- Volume
- 40
- Issue
- 10
- ISSN
- 1678-5878 (ISSN-L)
- 1806-3691
- OpenAlex
- W2891534289
- Cited by
- 1
- References
- 26
- Citations by year
- 2021: 1
- FWCI
- 0.16
- Type
- journal article
- Language
- en
- Open access
- closed
- Licence
- www.springer.com/tdm (tdm)
- Locations
- Journal of the Brazilian Society of Mechanical Sciences and Engineering (publishedVersion)
- Funders
- CNPq (441603/2014-9)
- Topics
- Physical Sciences › Engineering › Mechanical Engineering › Refrigeration and Air Conditioning Technologies
- Physical Sciences › Engineering › Mechanical Engineering › Heat Transfer and Optimization
- Physical Sciences › Engineering › Mechanical Engineering › Adsorption and Cooling Systems
- Keywords
- entropy generation minimization, refrigeration cycle modeling, energy optimization, irreversibility
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
The claim verdicts this report counts are experimental: their accuracy is not yet measured.
A language model drew the claims from the paper on 2026-10-21, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-21 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Cited sources are checked with a language model’s help (gpt-6-sol).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.