Airborne Asbestos Exposures from Warm Air Heating Systems in Schools
Open accessThe DOI matches its Crossref record; 20 of the 20 references it cites were found in a registry or an index.
Abstract
The aim of this study was to investigate the concentrations of airborne asbestos that can be released into classrooms of schools that have amosite-containing asbestos insulation board (AIB) in the ceiling plenum or other spaces, particularly where there is forced recirculation of air as part of a warm air heating system. Air samples were collected in three or more classrooms at each of three schools, two of which were of CLASP (Consortium of Local Authorities Special Programme) system-built design, during periods when the schools were unoccupied. Two conditions were sampled: (i) the start-up and running of the heating systems with no disturbance (the background) and (ii) running of the heating systems during simulated disturbance. The simulated disturbance was designed to exceed the level of disturbance to the AIB that would routinely take place in an occupied classroom. A total of 60 or more direct impacts that vibrated and/or flexed the encapsulated or enclosed AIB materials were applied over the sampling period. The impacts were carried out at the start of the sampling and repeated at hourly intervals but did not break or damage the AIB. The target air volume for background samples was ~3000 l of air using a static sampler sited either below or ~1 m from the heater outlet. This would allow an analytical sensitivity (AS) of 0.0001 fibres per millilitre (f ml(-1)) to be achieved, which is 1000 times lower than the EU and UK workplace control limit of 0.1 f ml(-1). Samples with lower volumes of air were also collected in case of overloading and for the shorter disturbance sampling times used at one site. The sampler filters were analysed by phase contrast microscopy (PCM) to give a rapid determination of the overall concentration of visible fibres (all types) released and/or by analytical transmission electron microscopy (TEM) to determine the concentration of asbestos fibres. Due to the low number of fibres, results were reported in terms of both the calculated concentration and the statistically relevant limits of quantification (LOQ), which are routinely applied. The PCM fibre concentrations were all below the LOQ but analytical TEM showed that few of the fibres counted in the background samples were asbestos. The background TEM asbestos concentrations for the individual samples analysed from all three schools were at or below the AS, with a pooled average below the LOQ (<0.00005 f ml(-1)). At the two CLASP schools, there was no significant increase in the airborne amosite concentration in the classrooms during simulated disturbance conditions. At the third school, four of the five classrooms sampled gave measurable concentrations of amosite by TEM during simulated disturbance conditions. The highest concentration of amosite fibres countable by PCM was 0.0043 f ml(-1) with a pooled average of 0.0019 f ml(-1). The air sampling strategy was effective and worked well and the results provide further important evidence to inform the sampling and management of asbestos in schools.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Figures
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Ibrahim, A. H., Dunn, P. F., & Brach, R. M. (2003) · Journal of Aerosol Science · doi:10.1016/s0021-8502(03)00031-4 · Cited by 213 · cited 1×
“Even when resuspension does occur, wind tunnel studies show an initial release in the first few seconds were some two to three orders of magnitude higher than the release that followed (Hall and Reed, 1989; Wu et al., 1992; Nicholson, 1993; Ibrahim et al., 2003).”
BackgroundBoulanger, G., Andujar, P., Pairon, J.-C., Billon-Galland, M.-A., Dion, C., Dumortier, P., Brochard, P., Sobaszek, A., Bartsch, P., Paris, C., et al. (2014) · Environmental Health · doi:10.1186/1476-069x-13-59 · Cited by 176 · cited 1×
“Even though their health effects are uncertain, short asbestos fibres are considered helpful in detecting if very low emissions are present (AFSSET, 2009; Boulanger et al., 2014).”
BackgroundWind tunnel experiments on the resuspension of particulate material
Nicholson, K. W. (1993) · Atmospheric Environment Part A General Topics · doi:10.1016/0960-1686(93)90349-4 · Cited by 118 · cited 2×
“Even when resuspension does occur, wind tunnel studies show an initial release in the first few seconds were some two to three orders of magnitude higher than the release that followed (Hall and Reed, 1989; Wu et al., 1992; Nicholson, 1993; Ibrahim et al., 2003).”
BackgroundRe-entrainment of Particles from a Plane Surface
Corn, M., & Stein, F. (1965) · American Industrial Hygiene Association Journal · doi:10.1080/00028896509342739 · Cited by 105 · cited 2×
“Other authors found that air velocities of 50 and 117 m s−1 were needed to resuspend ~11-μm particles (Corn and Stein, 1965; Jiang et al., 2008).”
BackgroundControlled Wind Tunnel Experiments for Particle Bounceoff and Resuspension
Wu, Y.-L., Davidson, C. I., & Russell, A. G. (1992) · Aerosol Science and Technology · doi:10.1080/02786829208959574 · Cited by 78 · cited 2×
“Even when resuspension does occur, wind tunnel studies show an initial release in the first few seconds were some two to three orders of magnitude higher than the release that followed (Hall and Reed, 1989; Wu et al., 1992; Nicholson, 1993; Ibrahim et al., 2003).”
BackgroundAirborne asbestos in buildings
Lee, R. J., & Van Orden, D. R. (2008) · Regulatory Toxicology and Pharmacology · doi:10.1016/j.yrtph.2007.10.005 · Cited by 70
Goldasteh, I., Ahmadi, G., & Ferro, A. R. (2012) · Journal of Adhesion Science and Technology · doi:10.1080/01694243.2012.747729 · Cited by 66
Jiang, Y., Matsusaka, S., Masuda, H., & Qian, Y. (2007) · Powder Technology · doi:10.1016/j.powtec.2007.11.041 · Cited by 63 · cited 1×
“Other authors found that air velocities of 50 and 117 m s−1 were needed to resuspend ~11-μm particles (Corn and Stein, 1965; Jiang et al., 2008).”
BackgroundAsbestos exposure in a Yale building
Sawyer, R. N. (1977) · Environmental Research · doi:10.1016/0013-9351(77)90013-5 · Cited by 59 · cited 2×
“…buildings and/or the areas where the ACMs were in poor condition and had the potential to give increased airborne asbestos concentrations (Sawyer, 1977; Sebastien et al., 1980; Burdett et al., 1984; Burdett, 1986; Burdett and Jaffrey, 1986, Burdett et al., 2009; Nicholson et al.,…”
BackgroundBoor, B. E., Siegel, J. A., & Novoselac, A. (2013) · Aerosol Science and Technology · doi:10.1080/02786826.2013.794929 · Cited by 38 · cited 2×
“While the particle size, deposit density, agglomeration, and the amount of dust are important determinants of resuspension (Boor et al., 2013); other environmental variables such as relative humidity, temperature, and moisture content will also modify resuspension (EN 15051-1, 2013).”
BackgroundAIRBORNE ASBESTOS CONCENTRATIONS IN BUILDINGS
(1986) · The Annals of Occupational Hygiene · doi:10.1093/annhyg/30.2.185 · Cited by 34 · cited 2×
“5 ng m−3) containing mainly sprayed chrysotile, amosite, and crocidolite, respectively under various levels of occupancy (Pinchin, 1982; Burdett et al., 1984).”
BackgroundSelf-citationThe time dependence of the resuspension of particles
Hall, D., & Reed, J. (1989) · Journal of Aerosol Science · doi:10.1016/0021-8502(89)90094-3 · Cited by 21 · cited 2×
“Even when resuspension does occur, wind tunnel studies show an initial release in the first few seconds were some two to three orders of magnitude higher than the release that followed (Hall and Reed, 1989; Wu et al., 1992; Nicholson, 1993; Ibrahim et al., 2003).”
BackgroundASBESTOS CONTAMINATION IN UNITED STATES SCHOOLS FROM USE OF ASBESTOS SURFACING MATERIALS*
Nicholson, W. J., Swoszowski, E. J., Rohl, A. N., Todaro, J. D., & Adams, A. (1979) · Annals of the New York Academy of Sciences · doi:10.1111/j.1749-6632.1979.tb18763.x · Cited by 18 · cited 1×
“…areas where the ACMs were in poor condition and had the potential to give increased airborne asbestos concentrations (Sawyer, 1977; Sebastien et al., 1980; Burdett et al., 1984; Burdett, 1986; Burdett and Jaffrey, 1986, Burdett et al., 2009; Nicholson et al., 1978, 1979; Nolan and Langer, 2001).”
BackgroundSterling, T. D., Collett, C. W., Rosenbaum, W. L., & Weinkam, J. J. (1993) · American Journal of Industrial Medicine · doi:10.1002/ajim.4700240613 · Cited by 10
Burdett, G., Guen, J. M. M. L., & Rood, A. P. (1984) · The Annals of Occupational Hygiene · doi:10.1093/annhyg/28.1.31 · Cited by 9
Self-citationAsbestos in Buildings: The Difficulties of a Reliable Exposure Assessment
Guillemin, M. P., Madelaine, P., Litzistorf, G., Buffat, P., & Iselin, F. (1989) · Aerosol Science and Technology · doi:10.1080/02786828908959315 · Cited by 7 · cited 1×
“…be minimal, even on friable sprayed surfaces in return-air plenums (Nicholson et al., 1975; Sebastien et al., 1980; Burdett and Jaffrey, 1986), at ventilation outlets directed across friable sprayed ACM (Guillemin et al., 1989) and in specific experiments (Burdett, 1986; Keyes and Chesson, 1990)’.”
BackgroundAirborne fibre and asbestos concentrations in system built schools
Burdett, G., Cottrell, S., & Taylor, C. (2009) · Journal of Physics Conference Series · doi:10.1088/1742-6596/151/1/012023 · Cited by 5 · cited 5×
“This guidance was based on the findings from a programme of HSE inspections and air measurements in schools (Burdett et al., 2009).”
BackgroundMethodSelf-citationDawson, M. (2012) · Journal of building survey, appraisal & valuation · doi:10.69554/onoq1986 · Cited by 5 · cited 1×
“…be minimal, even on friable sprayed surfaces in return-air plenums (Nicholson et al., 1975; Sebastien et al., 1980; Burdett and Jaffrey, 1986), at ventilation outlets directed across friable sprayed ACM (Guillemin et al., 1989) and in specific experiments (Burdett, 1986; Keyes and Chesson, 1990)’.”
BackgroundINDOOR ASBESTOS LEVELS ON A HOUSING ESTATE (DETERMINED BY TRANSMISSION ELECTRON MICROSCOPY)
Gazzi, D., & Crockford, G. W. (1987) · The Annals of Occupational Hygiene · doi:10.1093/annhyg/31.4a.429 · Cited by 3 · cited 1×
“Gazzi and Crockford (1987) reported TEM asbestos fibre concentrations in UK residential apartments with an amosite-containing AIB lined airing cupboard with a recirculating warm air heater below.”
BackgroundBurdett, G., & Health and Safety Executive (HSE), L. (. K. R. L. A. S. D. (1985) · OpenGrey (Institut de l'Information Scientifique et Technique) · Cited by 1
Self-citation
Research works printed but not linked: 16
- AFSSET, 2009, Influence of asbestos fibres dimensions to the health risk characterization: Toxicological, metrological and epidemiological data review in order to carry out a health risk assessment for the general population and the Workers (in French)
- 8. EN 15051-1. (2013) Workplace exposure -measurement of the dustiness of bulk materials Part 1: Requirements and choice of test methods. British Standards Institute, ISBN 978 0 580 76532 2. Available at http://shop.bsigroup.com. Accessed 20 March 2015.
- 13. HEI-AR. (1991) Asbestos in public and commercial build- ings: a literature review and synthesis of current knowledge. Health Effects Institute -Asbestos Research. Available at http://pubs.healtheffects.org. Accessed 20 March 2015.
- 14. HEI-AR. (1992) Asbestos in public and commercial buildings: Supplementary analyses of selected data previously consid- ered by the literature review panel. Health Effects Institute -Asbestos Research. Available at http://pubs.healtheffects. org. Accessed 20 March 2015.
- 15. HSE. (1998) MDHS
- 22. Ibrahim AH, Dunn PF, Brach RM. (2003) Microparticle detachment from surfaces exposed to turbulent air flow: controlled experiments and modelling. J Aerosol Sci; 34: 765-82. ISO 10312:95. (1995) Ambient air -determination of asbes- tos fibres -direct transfer transmission electron microscopy procedure. Geneva, Switzerland: International Standards Organisation. Available from British Standards Institute, 389 Chiswick High Road, London. W4 4AL.
- 24. Keyes D, Chesson J. (1990) Summary of the Aspen experiments. Environmental sciences. Tucson, AZ.
- 27. Nicholson WJ, Rohl AN, Weisman I. (1975) Asbestos con- tamination of air in public buildings. Washington, DC: U.S. Environmental Protection Agency, EPA-450/3-76-004, PB-250-980.
- 28. Nicholson WJ, Rohl AN, Weisman I. (1976) Asbestos con- tamination in building air supply systems. Proceedings of the International Conference on Environmental Sensing and Assessment, Las Vegas, NV. No. 29-6. New York, NY: New York Institute of Electrical and Electronic Engineers.
- 29. Nicholson WJ, Rohl AN, Sawyer RN et al. (1978) Control of sprayed asbestos surfaces in school buildings: a feasibility study (NIEHS NOlOES-7-2113). New York, NY: Environmental Sciences Laboratory, Mount Sinai School of Medicine.
- 31. Nolan RP, Langer AM. (2001) Concentration and type of asbestos fibers in air inside buildings. Can Mineral Special Issue; 5: 39-51.
- 32. Pinchin DJ. (1982) Asbestos in buildings. Study No.8. Toronto, Ontario, Canada: Ontario Ministry of Government Services, Publications Services Branch.
- 33. RCO. (1982) Report of the Royal Commission on matters of health and safety arising from the use of asbestos in Ontario. Volumes 1-3, Ontario Ministry of the Attorney General. Available at: https://archive.org/details/reportofroyasbes t02onta.Accessed 20 March 2015.
- 35. Sawyer RN, Spooner CM. (1978) Sprayed asbestos-containing materials in buildings: a guidance document. EPA-450/2-78- 014 (Orange Book Part 2).
- 36. Sebastien P, Billion-Galland MA, Dufour G. et al. (1980) Measurement of asbestos air pollution inside buildings sprayed with asbestos. USEPA 560/13-80-026.
- 37. WHO. (1997) Determination of airborne fibre number concentra- tion. A recommended method by phase-contrast optical micros- copy (membrane filter method). Geneva, Switzerland: World Health Organisation.
Cited by
Bolan, S. S., Kempton, L., McCarthy, T. J., Wijesekara, H., Piyathilake, I. D. U. H., Jasemizad, T., Padhye, L. P., Zhang, T., Rinklebe, J., Wang, H., et al. (2023) · The Science of The Total Environment · doi:10.1016/j.scitotenv.2023.163456 · Cited by 72
Mokhtari, M., Jafari, N., Mohammadi, A., Hajizadeh, Y., Ghanbari, R., Nemati, S., & Abdolahnejad, A. (2018) · International Journal of Environmental Science and Technology · doi:10.1007/s13762-018-1858-9 · Cited by 27
Spatio-seasonal variation of airborne asbestos concentration in urban areas of Shiraz, Iran
Fathabadi, M. K. F., Abdolahnejad, A., Teiri, H., & Hajizadeh, Y. (2017) · International Journal of Occupational and Environmental Health · doi:10.1080/10773525.2018.1436016 · Cited by 18
Reid, A., Franklin, P., Berry, G., Peters, S., Sodhi‐Berry, N., Brims, F., Musk, A. W., & de Klerk, N. H. (2018) · Occupational and Environmental Medicine · doi:10.1136/oemed-2018-105108 · Cited by 14
“6 29 30 A common source of asbestos exposure in those schools is from poorly maintained, disturbed or damaged asbestos insulation or asbestos cement-containing products that released fibres into the air.”
BackgroundObmiński, A. (2024) · Scientific Reports · doi:10.1038/s41598-024-70631-z · Cited by 9
Metadata
- Authors
- Burdett, G. J., Dewberry, K., & Staff, J.
- Affiliations
- HSE Science and Research Centre (GB)
- Corresponding author
- Burdett, Garry J.
- Venue
- Annals of Occupational Hygiene
- Publisher
- Oxford University Press (OUP)
- Published
- 2015-08-26
- Volume
- 60
- Issue
- 1
- Pages
- mev062
- ISSN
- 0003-4878 (ISSN-L)
- 1475-3162
- PMC
- PMC4689185
- OpenAlex
- W1900668233
- Cited by
- 10
- References
- 20
- Citations by year
- 2024: 1 · 2023: 2 · 2022: 1 · 2021: 1 · 2020: 1 · 2019: 1 · 2018: 2 · 2017: 1
- FWCI
- 0.79
- Type
- journal article
- Language
- en
- Open access
- hybrid
- doi.org
- Licence
- cc-by-nc-nd
- Locations
- The Annals of Occupational Hygiene (publishedVersion, cc-by-nc-nd)
- PubMed Central (publishedVersion, cc-by-nc-nd)
- PubMed (publishedVersion)
- Topics
- Health Sciences › Medicine › Pulmonary and Respiratory Medicine › Occupational and environmental lung diseases
- Physical Sciences › Environmental Science › Health, Toxicology and Mutagenesis › Indoor Air Quality and Microbial Exposure
- Health Sciences › Medicine › Public Health, Environmental and Occupational Health › Occupational Health and Safety in Workplaces
- Keywords
- airborne asbestos fibers, amosite, school classrooms, limit of quantification, phase contrast microscopy, analytical transmission electron microscopy, indoor air quality
- MeSH terms
- Air Pollutants, Environmental Monitoring, Heating, Humans, Microscopy, Phase-Contrast, Schools, Occupational Exposure, Asbestos, Amosite, Risk Assessment, Inhalation Exposure, Microscopy, Electron, Transmission
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.