Designing a New Controller in the Operation of the Hybrid PV-BESS System to Improve the Transient Stability
Open accessAbstract
The main aim of this paper is to design a local controller for DC/DC converter in a battery energy storage system (BESS) and a controller based on a virtual synchronous generator (VSG) for photovoltaic (PV) converter connected to AC grid. In the DC/DC converter design, the state feedback method is used so that the voltage and current control loops are combined, leading to higher flexibility and improved damping. This flexibility, which maintains the state of charge (SOC) of BESS, is supported by the design of virtual resistance and virtual capacitor statically and dynamically. In this design method, the BESS can be independently connected to each DC bus node and detect disturbances through local measurements. In addition, the improved Pre-Parallelism (PREP) method has been used to improve the transient performance caused by the disconnection and connection of additional loads, the existence of faults, and the inherent inertia difference in parallel operation between VSG and synchronous generator (SG). In this method, the problem of phase jump caused by transient disturbances is solved by considering a cosine function in VSG design. Also, to solve the problem of inertia difference between the units, a small signal model has been presented, in which, by considering the capacity ratio of the units on the AC side, the necessary inertia for VSG can be included in the design. The proposed method is simulated by considering different scenarios in MATLAB software, so the results demonstrate the superiority of the proposed controller compared to other existing methods.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Figures























Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
The source backs part of the claim, not all of it — or backs it for a different population, condition or comparison.
In the citing paper
“Modern control theory-based stabilizer design has some technical limitations, requiring extensive knowledge of the power system, extensive processing time for online parameter determination, and significant implementation cost [110,111].”
From A Comprehensive Review on the Role of Artificial Intelligence in Power System Stability, Control, and Protection: Insights and Future Directions (2024) · cites this paper as [111]
Experimental — accuracy not yet measuredThe source backs part of the claim, not all of it — or backs it for a different population, condition or comparison.
In the citing paper
“Alanazi et al. [111] suggested a recurrent neural network (RNN) stabilization controller to enhance the transient stability of power systems under various operating conditions and parametric uncertainties.”
From A Comprehensive Review on the Role of Artificial Intelligence in Power System Stability, Control, and Protection: Insights and Future Directions (2024) · cites this paper as [111]
Experimental — accuracy not yet measured
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Self-Synchronized Synchronverters: Inverters Without a Dedicated Synchronization Unit
Zhong, Q.-C., Nguyen, P.-L., Ma, Z., & Sheng, W. (2014) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2013.2258684 · Cited by 1,026 · cited 1×
“In this regard, one of the methods of reducing phase disturbances in the synchronization of the inverter connected to the grid is the use of virtual impedance in VSG [37].”
MethodLi, X., Hui, D., & Lai, X. (2013) · IEEE Transactions on Sustainable Energy · doi:10.1109/tste.2013.2247428 · Cited by 898 · cited 1×
“In [14], to improve the fluctuations caused by wind and PV energy, a BESS station is used to adjust BESS power levels based on the variations of the units and the SOC levels.”
MethodSerban, I., & Marinescu, C. (2014) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2013.2283298 · Cited by 274
Cheng, H., Shuai, Z., Shen, C., Liu, X., Li, Z., & Shen, Z. J. (2020) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2020.2965152 · Cited by 254 · cited 1×
“In [33] and [34], the difference in inertia between inverters and SGs has been analyzed concerning frequency fluctuations and weak transient power sharing.”
BackgroundLong, B., Liao, Y., Chong, K. T., Rodríguez, J., & Guerrero, J. M. (2020) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2020.3027051 · Cited by 158 · cited 2×
“In [32], the Model Predictive Controller (MPC) method is also presented to control the DC/AC converter in BESS.”
BackgroundMethodMohamed, M. M., Zoghby, H. M. E., Sharaf, S., & Mosa, M. A. (2022) · Journal of Energy Storage · doi:10.1016/j.est.2022.104317 · Cited by 154 · cited 1×
“Themain advantage of load shedding is the lack of additional investment in additional and complex control elements [26].”
BackgroundSukumar, S., Marsadek, M. B., Ramasamy, A. K., & Mokhlis, H. (2018) · Journal of Energy Storage · doi:10.1016/j.est.2018.09.013 · Cited by 136 · cited 1×
“In [16], the control design for the PV converter using the droop method is presented in more detail to increase the PV power during disturbances.”
MethodUnified Modeling and Analysis of Dynamic Power Coupling for Grid-forming Converters
Li, M., Wang, Y., Hu, W., Shu, S., Yu, P., Zhang, Z., & Blaabjerg, F. (2021) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2021.3107329 · Cited by 132 · cited 1×
“In [27], an optimal control method based on reinforcement learning is proposed for the three-phase gridconnected inverter used inVSGs.”
MethodSharing Transient Loads : Causes of Unequal Transient Load Sharing in Islanded Microgrid Operation
Paquette, A. D., Reno, M. J., Harley, R. G., & Divan, D. M. (2014) · IEEE Industry Applications Magazine · doi:10.1109/mias.2013.2288408 · Cited by 124 · cited 1×
“In [33] and [34], the difference in inertia between inverters and SGs has been analyzed concerning frequency fluctuations and weak transient power sharing.”
BackgroundEskandari, M., Rajabi, A., Savkin, A. V., Moradi, M. H., & Dong, Z. Y. (2022) · Journal of Energy Storage · doi:10.1016/j.est.2022.105627 · Cited by 102
Cited by
Alhamrouni, I., Abdul Kahar, N. H., Salem, M., Swadi, M., Zahroui, Y., Kadhim, D. J., Mohamed, F. A., & Alhuyi Nazari, M. (2024) · Applied Sciences · doi:10.3390/app14146214 · Cited by 217
“Modern control theory-based stabilizer design has some technical limitations, requiring extensive knowledge of the power system, extensive processing time for online parameter determination, and significant implementation cost [110,111].”
BackgroundSelf-citationMoore, P., Alimi, O. A., & Abu‐Siada, A. (2025) · Challenges · doi:10.3390/challe16010012 · Cited by 58
“IBR IBR sympathetic tripping occurs when the system’s RoCoF, following a generator trip, causes PLL phase jump errors [29]. sympathetic tripping occurs when the The standard RoCoF limit for steam turbines is 2 Hz/s [7], posing two problems: 1.”
Integration of hybrid PV-wind system for electric vehicle charging: Towards a sustainable future
Kumar, R. T., & Rajan, C. C. A. (2023) · e-Prime - Advances in Electrical Engineering Electronics and Energy · doi:10.1016/j.prime.2023.100347 · Cited by 29
A robust MPPT framework based on GWO-ANFIS controller for grid-tied EV charging stations
Mazumdar, D., Biswas, P. K., Sain, C., Ahmad, F., & Al‐Fagih, L. (2024) · Scientific Reports · doi:10.1038/s41598-024-81937-3 · Cited by 28
Machine learning-based wind speed forecasting: a comparative study
Zabihi, A., Manur, V. B., Dintakurthy, Y., Prasad, K. R. K. V., Rene, P., & Krishna, V. B. M. (2025) · Scientific Reports · doi:10.1038/s41598-025-24640-1 · Cited by 16
Metadata
- Authors
- Alanazi, M., Salem, M., Sabzalian, M. H., Prabaharan, N., Ueda, S., & Senjyu, T.
- Affiliations
- Jouf University (SA)
- Universiti Sains Malaysia (MY)
- Universidad de Santiago de Chile (CL)
- SASTRA University (IN)
- University of the Ryukyus (JP)
- ORCID
- Venue
- IEEE Access
- Published
- 2023
- Volume
- 11
- Pages
- 97625-97640
- ISSN
- 2169-3536 (ISSN-L)
- OpenAlex
- W4386464276
- Cited by
- 17
- References
- 41
- Citations by year
- 2026: 1 · 2025: 8 · 2024: 7 · 2023: 1
- FWCI
- 1.83
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Licence
- Locations
- IEEE Access (publishedVersion, cc-by-nc-nd)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
- Funders
- Deputyship for Research and Innovation, Ministry of Education in Saudi Arabia (223202)
- Topics
- Physical Sciences › Engineering › Control and Systems Engineering › Microgrid Control and Optimization
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Advanced DC-DC Converters
- Physical Sciences › Energy › Energy Engineering and Power Technology › Power Systems and Renewable Energy
- Keywords
- battery energy storage, virtual synchronous generator, state feedback control, transient stability, phase jumps, small-signal modeling, photovoltaic converters, grid-connected inverter
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: Designing a New Controller in the Operation of the Hybrid PV-BESS System to Improve the Transient Stability. https://app.cochat.ai/papers/10.1109/access.2023.3312180
- The paper
- Alanazi, M., Salem, M., Sabzalian, M. H., Prabaharan, N., Ueda, S., & Senjyu, T. (2023). Designing a New Controller in the Operation of the Hybrid PV-BESS System to Improve the Transient Stability. IEEE Access. https://doi.org/10.1109/access.2023.3312180
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.