Impedance-based fault location experience
The DOI matches its Crossref record; 3 of the 3 references it cites were found in a registry or an index; none of the 20 sources its claims cite is checked for support yet.
Abstract
We describe one- and two-ended impedance-based fault location experiences. We define terms associated with fault location and describe several impedance-based methods of fault location (simple reactance, Takagi, zero-sequence current with angle correction, and two-ended negative-sequence). We examine several system faults and analyze the performance of the fault locators given possible sources of error (short fault window, nonhomogeneous system, incorrect fault type selection, etc.). Finally, we show the laboratory testing results of a two-ended method, where we automatically extracted a two-ended fault location estimate from a single end.
Overview
CoChat Summary
TL;DR
This paper reviews impedance-based fault-location methods and applies them to actual transmission and distribution faults, comparing one-ended and two-ended negative-sequence estimates. It also reports lab tests showing that a two-ended negative-sequence fault location can be calculated automatically from one end using exchanged analog quantities.
Key findings
- In Example 1, a 345 kV line fault was actually 17.8–17.9 miles from Terminal G; one-ended estimates were 17.28 and 10.00 miles, and the two-ended estimate was 17.46 miles, with all estimates within 2%.
- In Example 2, incorrect fault-type selection produced a reported fault location of -143.2 miles on a 115 kV line; the actual C-G fault was 6.8 miles, while an A-B-G calculation gave -137 miles.
- In Example 3, a 345 kV failed-insulator fault was actually 33.26 miles from Terminal E; one-ended estimates were 28.55 miles local and 6.29 miles remote, while the two-ended negative-sequence method gave the best estimate.
- In lab tests on the 345 kV Example 2 case, actual location was 90.7 miles; one-ended estimates were 93.64 miles local and 67.01 miles remote, while two-ended estimates were 91.2 miles (Mathcad point), 90.7 miles (Mathcad average), and 91.25 miles (relay).
Methods
- The paper describes impedance-based fault-location methods: simple reactance, Takagi, modified Takagi with zero-sequence current angle correction, and two-ended negative-sequence impedance.
- It analyzes actual system faults, including a distribution feeder and 345 kV/115 kV transmission examples, and performs lab tests by replaying time-aligned COMTRADE files into relays.
- For the lab two-ended-from-one-end method, relays exchange 3I2 and Z2S values, capture data 1.5 cycles after fault detection, and solve a quadratic equation for fault location; results are compared against known or patrolled fault locations.
Limitations
- The paper states one-ended fault location can be degraded by fault resistance combined with load, zero-sequence mutual coupling, zero-sequence modeling errors, system nonhomogeneity, system infeeds, and inaccurate relay, instrument transformer, or line parameters.
- The paper states short fault windows and low sampling rates challenge fault location, and that lab testing confirmed viability mainly for stable, longer-lasting events; developments are needed for automatic two-ended fault location on all lines and faults.
- Evident from the text: the lab results table reports only one case study, and the transmission examples are selected case studies rather than a broad statistical validation.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
0 Valid · 0 Not valid · 8 Not checked · 58 Own results and interpretations
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“However, the relay produced a fault location estimate of -143 miles.”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“An observation from Figure 6 is that the negative-sequence fault voltage ( )2FV is the same when viewed from all ends of the protected line.”
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The actual fault occurred where the sprinkler system was found, between 17.8 and 17.9 miles (m = .633) from Terminal G (based on patrol map tower locations).”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The fault was interrupted just as the relay filtering (one-cycle cosine filter) had processed the data.”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The fault was a fast clearing fault (approximately two cycles).”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
24 more claims
Create a free account to see all 66 claims and every source verdict.
- Probably not a substantial claim. 20
- It may state two separate claims as one. 22
- The quote only partly states this claim. 4
- Borderline: one of the tests for a substantial claim is unclear. 1
Citations
Cites
Development of a New Type Fault Locator Using the One-Terminal Voltage and Current Data
Takagi, T., Yamakoshi, Y., Yamaura, M., Kondow, R., & Matsushima, T. (1982) · IEEE Transactions on Power Apparatus and Systems · doi:10.1109/tpas.1982.317615 · Cited by 635 · cited 2×
“It improves upon the simple reactance method [2] by reducing the effect of load flow and minimizing the effect of fault resistance.”
BackgroundMethodNew multi-ended fault location design for two- or three-terminal lines
(2001) · doi:10.1049/cp:20010183 · Cited by 122
Development of a New Type Fault Locator Using the One-Terminal Voltage and Current Data
Takagi, T., Yamakoshi, Y., Yamaura, M., et al. (1982) · IEEE Power Engineering Review · doi:10.1109/mper.1982.5519781
Research works printed but not linked: 2
- [3] Edmund O. Schweitzer, III, "A Review of Impedance-Based Fault Locating Experience," Proceedings of the 15th Annual Western Protective Relay Conference, Spokane, WA, October 24-27, 1988.
- [1] IEEE Standard PC37.114, "Draft Guide For Determining Fault Location on AC Transmission and Distribution Lines," 2004.
Cited by
Yusuff, A. A., Fei, C., Jimoh, A. A.-G., & Munda, J. L. (2011) · Electric Power Systems Research · doi:10.1016/j.epsr.2010.12.016 · Cited by 99
Yusuff, A. A., Jimoh, A. A.-G., & Munda, J. L. (2014) · Electric Power Systems Research · doi:10.1016/j.epsr.2014.01.002 · Cited by 78
Distribution Fault-Locating Algorithms Using Current Only
(2012) · doi:10.1109/tpwrd.2012.2191422 · Cited by 48
DC Offset Removal Algorithm for Improving Location Estimates of Momentary Faults
Min, K. W., & Santoso, S. (2017) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2017.2688981 · Cited by 47
Mashifane, L. D., Mendu, B., & Monchusi, B. B. (2025) · IEEE Access · doi:10.1109/access.2025.3546861 · Cited by 53
Integrated Fault Location System for Power Distribution Feeders
(2013) · doi:10.1109/tia.2013.2252596 · Cited by 43
A CNN-LSTM-based fault classifier and locator for underground cables
Swaminathan, R., Mishra, S., Routray, A., & Swain, S. C. (2021) · Neural Computing and Applications · doi:10.1007/s00521-021-06153-w · Cited by 42
Fault Location for the NEPTUNE Power System
Chan, T., Liu, C., Howe, B. M., & Kirkham, H. (2007) · IEEE Transactions on Power Systems · doi:10.1109/tpwrs.2007.894855 · Cited by 32
Using PQ Monitoring and Substation Relays for Fault Location on Distribution Systems
Short, T. A., Sabin, D. D., & McGranaghan, M. F. (2007) · IEEE Rural Electric Power Conference (REPC) · doi:10.1109/repcon.2007.369552 · Cited by 31
Earth fault location determination independent of fault impedance for distribution networks
Elsadd, M. A., Elkalashy, N. I., Kawady, T. A., & Taalab, A. I. (2016) · International Transactions on Electrical Energy Systems · doi:10.1002/etep.2307 · Cited by 23
Nature of fault determination on transmission lines for single phase autoreclosing applications
Nikoofekr, I., & Sadeh, J. (2017) · IET Generation Transmission & Distribution · doi:10.1049/iet-gtd.2017.1058 · Cited by 23
Fault location in distribution systems from analysis of the energy of sequence component waveforms
Moraes, T. F., Lovisolo, L., & Monteiro, L. F. C. (2018) · IET Generation Transmission & Distribution · doi:10.1049/iet-gtd.2017.0693 · Cited by 19
A Comparative Review of Fault Location/Identification Methods in Distribution Networks
Haleem, A. M. I., Sharma, M., Sajan, K. S., & Babu, K. N. D. (2018) · 2018 1st International Conference on Advanced Research in Engineering Sciences (ARES) · doi:10.1109/aresx.2018.8723300 · Cited by 14
Lessons Learned Analyzing Transmission Faults
(2008) · doi:10.1109/cpre.2008.4515068 · Cited by 13
Self-citationFault Detection, Classification, and Location in Underground Cables
Jena, S., Mishra, D. P., & Salkuti, S. R. (2023) · Lecture notes in electrical engineering · doi:10.1007/978-981-99-2066-2_10 · Cited by 12
Fault Location for Power Transmission Systems Using Magnetic Field Sensing Coils
Ferreira, K. J. (2007) · Digital WPI · Cited by 13
Distribution fault location using short-circuit fault current profile approach
Das, S., Kulkarni, S., Karnik, N., et al. (2011) · IEEE Power and Energy Society General Meeting (PESGM) · doi:10.1109/pes.2011.6039423 · Cited by 13
Spielböck, T., & Beláň, A. (2018) · Electric Power Systems Research · doi:10.1016/j.epsr.2018.03.013 · Cited by 13
Automated fault location system for nonhomogeneous transmission networks
Gong, Y., Mynam, M. V., Guzmán, A., et al. (2012) · Conference for Protective Relay Engineers · doi:10.1109/cpre.2012.6201245 · Cited by 13
A new fault location method for underground cables in distribution systems
Naidu, O. D., George, N., & Pradhan, D. (2016) · International Conference on Sustainable Green Buildings and Communities (SGBC) · doi:10.1109/sgbc.2016.7936076 · Cited by 12
Piesciorovsky, E. C., & Rodriguez, M. E. M. (2022) · International Transactions on Electrical Energy Systems · doi:10.1155/2022/1951836 · Cited by 13
Abdel-Qader, I. M., & Alsafasfeh, Q. (2010) · Cited by 10
Impedance-based fault location techniques for transmission lines
Hashim, M. M. I., Ping, H. W., & Ramachandaramurthy, V. K. (2009) · IEEE Region 10 Conference (TENCON) · doi:10.1109/tencon.2009.5396253 · Cited by 9
Earth fault location based on a Modified Takagi Method for MV distribution networks
Le, T. D., & Petit, M. (2016) · IEEE International Energy Conference (ENERGYCON) · doi:10.1109/energycon.2016.7513910 · Cited by 8
Traveling Wave Fault Location Using Layer Peeling
Robson, S., Haddad, A. M., & Griffiths, H. (2018) · Energies · doi:10.3390/en12010126 · Cited by 8
Evaluation of transmission line fault-locating techniques using variance-based sensitivity measures
Živanović, R. (2008) · Adelaide Research & Scholarship (AR&S) (University of Adelaide) · Cited by 7
Modelling and simulation of transmission line to detect single line to ground fault location
Birajdar, A., & Tajane, S. (2016) · IEEE International Conference on Power Electronics, Intelligent Control and Energy Systems · doi:10.1109/icpeices.2016.7853231 · Cited by 7
Power System Faults: A Hindrance to Sustainability and Reliability
Ajenikoko, G. A., & Sangotola, S. O. (2014) · International Journal of Engineering Research · doi:10.17950/ijer/v3s11/1116 · Cited by 7
Analysis of a relay operation for an intercircuit fault
(2015) · doi:10.1109/cpre.2015.7102185 · Cited by 6
Fault location using impedance-based algorithms on non-homogeneous feeders
Kulkarni, S., Karnik, N., Das, S., et al. (2011) · IEEE Power and Energy Society General Meeting (PESGM) · doi:10.1109/pes.2011.6039257 · Cited by 6
Real-time evaluation of impedance-based fault location algorithms
Costa, C. A. B. D., Brito, N. S. D., & de Souza, B. A. (2016) · IEEE International Conference on Industry Applications · doi:10.1109/induscon.2016.7874579 · Cited by 5
Yablokov, A. A., Иванов, И. Е., Kulikov, F. A., et al. (2023) · International Youth Conference on Radio Electronics, Electrical and Power Engineering (REEPE) · doi:10.1109/reepe57272.2023.10086766 · Cited by 5
Monitoring Fault Diagnosis Based on Phasor Measurement Unit at Wide Area Systems
Zakri, A. A., Mustafa, M. W., Syaibi, H., et al. (2019) · IEEE Conference on Energy Conversion · doi:10.1109/cencon47160.2019.8974748 · Cited by 4
Živanović, R. (2011) · Reliability Engineering & System Safety · doi:10.1016/j.ress.2011.12.005 · Cited by 4
Application of fault location methods in distribution circuits with SCADA
Rangel-Damián, A., Melgoza, E., & Ruiz-Paredes, H. F. (2017) · IEEE International Autumn Meeting on Power, Electronics and Computing (ROPEC) · doi:10.1109/ropec.2017.8261652 · Cited by 3
Knezev, M. (2009) · OakTrust (Texas A&M University Libraries) · Cited by 3
Impedance-based ground fault location for transmission lines
Sun, H., & Sood, V. K. (2010) · doi:10.1109/ccece.2010.5575192 · Cited by 3
Fault Location Algorithms in Transmission Grids
Harrysson, M. (2014) · KTH Publication Database DiVA (KTH Royal Institute of Technology) · Cited by 2
Methodology for designing the fuzzy resolver for a radial distribution system fault locator
Li, J. (2006) · OakTrust (Texas A&M University Libraries) · Cited by 2
Modeling and recognition of faults in smart distribution grid using maching intelligence technique
Onaolapo, A. K. (2018) · DUT Open Scholar (Durban University of Technology) · doi:10.51415/10321/3250 · Cited by 5
Protection and control concepts for SFC fed railways
(2016) · Cited by 2
A solution to obtain precise fault location using a two-end data algorithm
Dragomir, M., Miron, A., Istrate, M. D., et al. (2016) · International Conference and Exposition on Electrical and Power Engineering (EPE) · doi:10.1109/icepe.2016.7781429 · Cited by 2
Ahire, H., Agrawal, P., Bannalikar, S., et al. (2021) · International Conference on Electrical, Computer, Communications and Mechatronics Engineering (ICECCME) · doi:10.1109/iceccme52200.2021.9591103 · Cited by 2
State of the art analysis of online fault location on AC cables in underground transmission systems
Jensen, C. F., Guðmundsdóttir, U. S., & Bak, C. L. (2011) · VBN Forskningsportal (Aalborg Universitet) · Cited by 2
Bharti, P., Dehankar, A., Raut, S., et al. (2016) · IEEE Power India International Conference · doi:10.1109/poweri.2016.8077452 · Cited by 1
POWER SYSTEM RESTORATION USING ARTIFICIAL NEURAL NETWORKS
George, W. W. (2012) · Cited by 1
A NEW DISTANCE PROTECTION SCHEME BASED ON COMBINATION OF IMPEDANCE AND TRAVELLING WAVE MEASUREMENTS
Mansour, R., Shehab-Eldin, E. H., & Masoud, M. (2013) · Port-Said Engineering Research Journal · doi:10.21608/pserj.2013.43745
Two-Ended Fault Location in Transmission Lines with a Fault Current Limiting Reactor at One End
Quilumba, F. L. (2024) · IEEE MetroCon · doi:10.1109/metrocon62511.2024.10883891
Peixoto, L. D. B., Coelho, R. R. A., Mamede, D. R., et al. (2020) · Anais do ... Simpósio Brasileiro de Sistemas Elétricos · doi:10.48011/sbse.v1i1.2466
The ANN Design Based On PMU Readings For Fault Location Detection
AzriyenniAzhariZakri, RoisKhumaini, M., Syaibi, H., et al. (2021) · International journal of scientific and technology research
FPGA TO POWER SYSTEM THEORIZATION FOR A FAULT LOCATION AND SPECIFICATION ALGORITHM
Yeoman, C. (2013) · UKnowledge (University of Kentucky)
การหาตำแหนงความผดพรองในระบบจำหนายไฟฟาโดยการวเคราะหแรงดนตกชวขณะ
ไกรเกียรติ, ก. (2016) · doi:10.58837/chula.the.2016.967
Improved method for locating faults upstream from distributed generation
Min, K. W., Das, S., & Santoso, S. (2016) · IEEE PES Transmission and Distribution Conference and Exhibition · doi:10.1109/tdc.2016.7519999
Piesciorovsky, E. C., Reno, M. J., Ferrari, M. F., & Summers, A. K. (2024) · Metrology · doi:10.3390/metrology4030023
Metadata
- Authors
- Zimmerman, K., & Costello, D.
- Affiliations
- Schweitzer Engineering Laboratories (United States) (US)
- Venue
- 58th Annual Conference for Protective Relay Engineers, 2005.
- Publisher
- IEEE
- Published
- 2005
- Pages
- 211-226
- OpenAlex
- W2113559774
- Semantic Scholar
- 8a7fad19d9c68377f9b9e09641bc2e7ba36b9bf6
- Cited by
- 104
- References
- 2
- Citations by year
- 2025: 1 · 2024: 5 · 2023: 6 · 2022: 5 · 2021: 5 · 2020: 4 · 2019: 8 · 2018: 5 · 2017: 7 · 2016: 11 · 2015: 4 · 2014: 6 · 2013: 6 · 2012: 6
- FWCI
- 6.39
- Type
- conference paper
- Language
- en
- Open access
- closed
- Locations
- Conference for Protective Relay Engineers (publishedVersion)
- Topics
- Physical Sciences › Engineering › Control and Systems Engineering › Power Systems Fault Detection
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Power System Optimization and Stability
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Electrical Fault Detection and Protection
- Keywords
- impedance-based fault location, power system faults, inhomogeneous systems, laboratory testing
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
A language model drew the claims from the paper on 2026-10-11, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-11 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.