Impedance-based fault location experience
The DOI matches its Crossref record; 3 of the 3 references it cites were found in a registry or an index; none of the 20 sources its claims cite is checked for support yet.
Abstract
We describe one- and two-ended impedance-based fault location experiences. We define terms associated with fault location and describe several impedance-based methods of fault location (simple reactance, Takagi, zero-sequence current with angle correction, and two-ended negative-sequence). We examine several system faults and analyze the performance of the fault locators given possible sources of error (short fault window, nonhomogeneous system, incorrect fault type selection, etc.). Finally, we show the laboratory testing results of a two-ended method, where we automatically extracted a two-ended fault location estimate from a single end.
Overview
CoChat Summary
TL;DR
This paper reviews impedance-based fault-location methods and applies them to actual transmission and distribution faults, comparing one-ended and two-ended negative-sequence estimates. It also reports lab tests showing that a two-ended negative-sequence fault location can be calculated automatically from one end using exchanged analog quantities.
Key findings
- In Example 1, a 345 kV line fault was actually 17.8–17.9 miles from Terminal G; one-ended estimates were 17.28 and 10.00 miles, and the two-ended estimate was 17.46 miles, with all estimates within 2%.
- In Example 2, incorrect fault-type selection produced a reported fault location of -143.2 miles on a 115 kV line; the actual C-G fault was 6.8 miles, while an A-B-G calculation gave -137 miles.
- In Example 3, a 345 kV failed-insulator fault was actually 33.26 miles from Terminal E; one-ended estimates were 28.55 miles local and 6.29 miles remote, while the two-ended negative-sequence method gave the best estimate.
- In lab tests on the 345 kV Example 2 case, actual location was 90.7 miles; one-ended estimates were 93.64 miles local and 67.01 miles remote, while two-ended estimates were 91.2 miles (Mathcad point), 90.7 miles (Mathcad average), and 91.25 miles (relay).
Methods
- The paper describes impedance-based fault-location methods: simple reactance, Takagi, modified Takagi with zero-sequence current angle correction, and two-ended negative-sequence impedance.
- It analyzes actual system faults, including a distribution feeder and 345 kV/115 kV transmission examples, and performs lab tests by replaying time-aligned COMTRADE files into relays.
- For the lab two-ended-from-one-end method, relays exchange 3I2 and Z2S values, capture data 1.5 cycles after fault detection, and solve a quadratic equation for fault location; results are compared against known or patrolled fault locations.
Limitations
- The paper states one-ended fault location can be degraded by fault resistance combined with load, zero-sequence mutual coupling, zero-sequence modeling errors, system nonhomogeneity, system infeeds, and inaccurate relay, instrument transformer, or line parameters.
- The paper states short fault windows and low sampling rates challenge fault location, and that lab testing confirmed viability mainly for stable, longer-lasting events; developments are needed for automatic two-ended fault location on all lines and faults.
- Evident from the text: the lab results table reports only one case study, and the transmission examples are selected case studies rather than a broad statistical validation.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
0 Valid · 0 Not valid · 8 Not checked · 58 Own results and interpretations
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“However, the relay produced a fault location estimate of -143 miles.”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“An observation from Figure 6 is that the negative-sequence fault voltage ( )2FV is the same when viewed from all ends of the protected line.”
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The actual fault occurred where the sprinkler system was found, between 17.8 and 17.9 miles (m = .633) from Terminal G (based on patrol map tower locations).”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The fault was interrupted just as the relay filtering (one-cycle cosine filter) had processed the data.”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The fault was a fast clearing fault (approximately two cycles).”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
24 more claims
Create a free account to see all 66 claims and every source verdict.
- Probably not a substantial claim. 20
- It may state two separate claims as one. 22
- The quote only partly states this claim. 4
- Borderline: one of the tests for a substantial claim is unclear. 1
Citations
Cites
Development of a New Type Fault Locator Using the One-Terminal Voltage and Current Data
Takagi, T., Yamakoshi, Y., Yamaura, M., Kondow, R., & Matsushima, T. (1982) · IEEE Transactions on Power Apparatus and Systems · doi:10.1109/tpas.1982.317615 · Cited by 635 · cited 2×
“It improves upon the simple reactance method [2] by reducing the effect of load flow and minimizing the effect of fault resistance.”
BackgroundMethodNew multi-ended fault location design for two- or three-terminal lines
(2001) · doi:10.1049/cp:20010183 · Cited by 122
Development of a New Type Fault Locator Using the One-Terminal Voltage and Current Data
Takagi, T., Yamakoshi, Y., Yamaura, M., et al. (1982) · IEEE Power Engineering Review · doi:10.1109/mper.1982.5519781
Research works printed but not linked: 2
- [3] Edmund O. Schweitzer, III, "A Review of Impedance-Based Fault Locating Experience," Proceedings of the 15th Annual Western Protective Relay Conference, Spokane, WA, October 24-27, 1988.
- [1] IEEE Standard PC37.114, "Draft Guide For Determining Fault Location on AC Transmission and Distribution Lines," 2004.
Cited by
Yusuff, A. A., Fei, C., Jimoh, A. A.-G., & Munda, J. L. (2011) · Electric Power Systems Research · doi:10.1016/j.epsr.2010.12.016 · Cited by 99
Yusuff, A. A., Jimoh, A. A.-G., & Munda, J. L. (2014) · Electric Power Systems Research · doi:10.1016/j.epsr.2014.01.002 · Cited by 78
Distribution Fault-Locating Algorithms Using Current Only
(2012) · doi:10.1109/tpwrd.2012.2191422 · Cited by 48
DC Offset Removal Algorithm for Improving Location Estimates of Momentary Faults
Min, K. W., & Santoso, S. (2017) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2017.2688981 · Cited by 47
Metadata
- Authors
- Zimmerman, K., & Costello, D.
- Affiliations
- Schweitzer Engineering Laboratories (United States) (US)
- Venue
- 58th Annual Conference for Protective Relay Engineers, 2005.
- Publisher
- IEEE
- Published
- 2005
- Pages
- 211-226
- OpenAlex
- W2113559774
- Semantic Scholar
- 8a7fad19d9c68377f9b9e09641bc2e7ba36b9bf6
- Cited by
- 104
- References
- 2
- Citations by year
- 2025: 1 · 2024: 5 · 2023: 6 · 2022: 5 · 2021: 5 · 2020: 4 · 2019: 8 · 2018: 5 · 2017: 7 · 2016: 11 · 2015: 4 · 2014: 6 · 2013: 6 · 2012: 6
- FWCI
- 6.39
- Type
- conference paper
- Language
- en
- Open access
- closed
- Locations
- Conference for Protective Relay Engineers (publishedVersion)
- Topics
- Physical Sciences › Engineering › Control and Systems Engineering › Power Systems Fault Detection
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Power System Optimization and Stability
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Electrical Fault Detection and Protection
- Keywords
- impedance-based fault location, power system faults, inhomogeneous systems, laboratory testing
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
A language model drew the claims from the paper on 2026-10-11, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-11 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.