Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data From Phasor Measurement Units
Open accessThe DOI matches its Crossref record; 18 of the 18 references it cites were found in a registry or an index; none of the 12 sources its claims cite is checked for support yet.
Abstract
An end-to-end supervised learning method is proposed for fault detection in the electric grid using Big Data from multiple Phasor Measurement Units (PMUs). The approach consists of preprocessing steps aimed at reducing data noise and dimensionality, followed by utilization of six classification models considered for detecting faults. Three of the models were variants of Convolutional Neural Network (CNN) architectures that consider a single type of measurement (voltage, current or frequency) at all PMUs or all types together also at all PMUs. CNN based models were compared to traditional methods of Logistic Regression (LR), Multi-layer Perceptron (MLP) and Support Vector Machine (SVM). Evaluation was conducted on two-year data measured by PMUs at 37 locations in a large electric grid. The response variable for classification were extracted from the grid-wide outage event log. Experiments show that CNN-based models outperformed traditional methods on one year out-of-sample outage detection over the entire grid.
Overview
CoChat Summary
TL;DR
The paper proposes an end-to-end supervised fault-detection pipeline for PMU big data, using automated preprocessing and CNN variants to detect line outages. On two years of data from 37 PMUs in the Western U.S. interconnection, CNN-based models achieved the best out-of-sample performance, with SCE-CNN reaching AUC 0.8316.
Key findings
- CNN-based models outperformed traditional LR, MLP, and SVM on one-year out-of-sample outage detection over the entire grid; best AUC was 0.8316 from multi-channel SCE-CNN, followed by PCE-CNN 0.8151 and SC-CNN voltage 0.8016.
- Among single-channel models, voltage was most informative: SC-CNN(V) accuracy 0.7464, AUC 0.8016; current and frequency were lower (SC-CNN(I) AUC 0.7654; SC-CNN(f) AUC 0.7305). Traditional models on voltage: LR AUC 0.7846, MLP 0.7455, SVM 0.7937.
- Multi-channel CNNs improved SC-CNN(voltage) accuracy by ~5% and AUC; PCE-CNN and SCE-CNN both had accuracy 0.7971, with SCE-CNN AUC 0.8316. Training time was under 20 seconds and inference under a second using the described hardware.
- Model performance stabilized at 20–25 PMUs; visual inspection of top 10 misclassifications found most were false labels from the event log rather than true model errors (e.g., 9 false labels vs 1 false prediction for LR/MLP/SVM, SC-CNN voltage, and SCE-CNN).
Methods
- Data: 37 PMUs from the Western U.S. interconnection, 2 years (2016, 2017) at 30–60 FPS, anonymized; 3 channels used: positive sequence voltage magnitude (V), positive sequence current magnitude (I), frequency (f). Train on 2016, test on 2017: 704 training signals (176 line outages), 848 test signals (212 line outages); total measurements 838,080 (train 380,160; test 547,920).
- Preprocessing: 1-minute windows, downsampled to 30 FPS, labeled by intersecting with event log; kept [t−Δ1, t+Δ2] with Δ1=3 min 6 s and Δ2=54 s (4 min total) around events; line outage faults only. Downsampling used non-overlapping windows of size 10 summarized by range (1,800 to 180 points); smoothed p-centers computed with Soft-DTW and dynamic standard-deviation-based weights.
- Models/analysis: six classifiers—SC-CNN, PCE-CNN, SCE-CNN vs LR, MLP, SVM. CNN settings: 1-D kernel size 30, stride 30, 150 output filters; embedding dimension 30 for fully connected models except LR; SVM linear kernel with regularization parameter 1. Metrics: accuracy and AUC. Number-of-PMUs experiment used SCE-CNN with 10 random PMU selections per count.
Limitations
- Stated: event log labels were not fully accurate, not accurately representing fault start or duration of visibility in PMU measurements; visual inspection of top 10 misclassifications showed many apparent errors were false labels.
- Stated: PMUs are sparsely located, typically covering less than 5% of system electrical buses, with uneven placement density; event log lacks fault location or proximity to PMUs, and the dataset is anonymized.
- Evident: only line-outage faults were considered; traditional models were reported only for voltage because that input performed best; the misclassification inspection was limited to the top 10 cases per model.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
0 Valid · 4 Not valid · 12 Not checked · 58 Own results and interpretations
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“One characteristic of fault-related line outages is that a sudden disturbance is seen in the PMU measurements, the realization reached by manually examining a certain number of faults across different time periods.”
- Also stated in: § 2) Computing smoothed 𝑝-centers. · hedged
“By correlating the event log with the collected measurements, sudden disturbances are usually seen when a fault-related line outage happens.”
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > 2) Computing smoothed 𝑝-centers.
plainstates an association- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Also stated in: § 2) Computing smoothed 𝑝-centers. · hedged
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Experiments show that CNN-based models outperformed traditional methods on one year out-of-sample outage detection over the entire grid.”
- Also stated in: § D. Contribution and Advantages · plain
“In the conducted experiments, CNN-based models outperformed traditional methods on one year out-of-sample outage detection over the entire grid, providing evidence that the convolution operations leveraged in CNN models seem to capture the sub-signal patterns relevant to fault detection missed by traditional approaches.”
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > Abstract
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Also stated in: § D. Contribution and Advantages · plain
In the paper
“Among the CNN variants, the multi-channel CNNs trained yield the largest accuracy and AUC.”
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > C. Fault Detection Performance
What the sources say
- Not matchedcites Table II
This doesn’t read as a citation we can look up.
plainstates an association- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Not matched
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The best AUC (0.83) was obtained from the multi-channel model SCE-CNN.”
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > D. Contribution and Advantages
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The labeled sub-signals created in this process become hugely unbalanced due to inherited characteristics of PMU data where the majority of the data is not labeled as events (normal operations).”
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > 1) Extracting labeled sub-interval signals.
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
31 more claims
Create a free account to see all 74 claims and to verify the 1 reference still open.
- Probably not a substantial claim. 23
- It may state two separate claims as one. 24
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
“the total number of measurements (i.e. the total number of samples over all signals) in the dataset was 838,080; out of which 380,160 were contained in the training set, while the test set contained the remaining 547,920.”
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > B. Experimental Setup 1) Data split.
Reported 838080 · recomputed 928080
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > C. Fault Detection Performance
“In contrast, one should use SCE-CNN in case a slight decrease in performance is allowed for the benefit of having a simpler model.”
§ Fault Detection Utilizing Convolution Neural Network on Timeseries Synchrophasor Data from Phasor Measurement Units > C. Fault Detection Performance
“PCE-CNN 𝑉, 𝐼, 𝑓 0.7971* 0.8151* SCE-CNN 𝑉, 𝐼, 𝑓 0.7971* 0.8316*”
Citations
Cites
Bagnall, A., Lines, J., Bostrom, A., Large, J., & Keogh, E. (2017) · Data Mining and Knowledge Discovery · doi:10.1007/s10618-016-0483-9 · Cited by 1,377 · cited 1×
“Some reported results include feature-based techniques [9], shapelet subsequence matching methods [10], timeseries modeling [11], techniques with adapted distance matrices and kernels methods such as SVM with Dynamic Time Warping.”
MethodSoft-DTW: a Differentiable Loss Function for Time-SeriesPreprint
Cuturi, M., & Blondel, M. (2017) · arXiv (Cornell University) · doi:10.48550/arxiv.1703.01541 · Cited by 1,012
Aggarwal, C. C. (2015) · doi:10.1007/978-3-319-14142-8 · Cited by 433
Time series shapelets: a novel technique that allows accurate, interpretable and fast classification
Ye, L., & Keogh, E. (2011) · Data Mining and Knowledge Discovery · doi:10.1007/s10618-010-0179-5 · Cited by 406
Dimensionality Reduction of Synchrophasor Data for Early Event Detection: Linearized Analysis
Xie, L., Chen, Y., & Kumar, P. R. (2014) · IEEE Transactions on Power Systems · doi:10.1109/tpwrs.2014.2316476 · Cited by 266
Feature-based classification of time-series data
Νανόπουλος, Α., Alcock, R. J., & Manolopoulos, Y. (2001) · Cited by 259
Li, W., Deka, D., Chertkov, M., & Wang, M. (2019) · IEEE Transactions on Power Systems · doi:10.1109/tpwrs.2019.2917794 · Cited by 183
Real-Time Multiple Event Detection and Classification Using Moving Window PCA
Rafferty, M., Liu, X. A., Laverty, D., & McLoone, S. (2016) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2016.2559444 · Cited by 158
Supervisory Protection and Automated Event Diagnosis Using PMU Data
Biswal, M., Brahma, S., & Cao, H. (2016) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2016.2520958 · Cited by 158
Wavelet-Based Event Detection Method Using PMU Data
Kim, D.-I., Chun, T. Y., Yoon, S.-H., Lee, G., & Shin, Y. (2015) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2015.2478421 · Cited by 153
Frequency Disturbance Event Detection Based on Synchrophasors and Deep Learning
Wang, W., Yin, H., Chen, C., Till, A., Yao, W., Deng, X., & Liu, Y. (2020) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2020.2971909 · Cited by 114
Comprehensive Clustering of Disturbance Events Recorded by Phasor Measurement Units
Dahal, O. P., Brahma, S., & Cao, H. (2013) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2013.2285097 · Cited by 101
Big data analytics for future electricity grids
Kezunovic, M., Pinson, P., Obradovic, Z., Grijalva, S., Hong, T., & Bessa, R. (2020) · Electric Power Systems Research · doi:10.1016/j.epsr.2020.106788 · Cited by 81
Self-citationPower Grid Online Surveillance Through PMU-Embedded Convolutional Neural Networks
Wang, S., Dehghanian, P., & Li, L. (2019) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2019.2958786 · Cited by 60
Signal features for classification of power system disturbances using PMU data
Biswal, M., Hao, Y., Chen, P., Brahma, S., Cao, H., & Leon, P. L. D. (2016) · Power Systems Computation Conference · doi:10.1109/pscc.2016.7540867 · Cited by 55
Identifying Overlapping Successive Events Using a Shallow Convolutional Neural Network
Li, W., & Wang, M. (2019) · IEEE Transactions on Power Systems · doi:10.1109/tpwrs.2019.2914774 · Cited by 30
Data Mining Techniques and Tools for Synchrophasor Data
Farantatos, E., Amidan, B., Arghandeh, R., Bienstock, D., Etingov, P., & Murphy, S. (2019) · doi:10.13140/rg.2.2.22389.22242 · Cited by 20
Kesici, M., Saner, C. B., Mahdı, M., Yaslan, Y., & Genc, I. V. M. (2019) · International Istanbul Smart Grids and Cities Congress and Fair (ICSG) · doi:10.1109/sgcf.2019.8782365 · Cited by 15
Cited by
A comprehensive review of AI-driven approaches for smart grid stability and reliability
Ahmadi, M., Aly, H. H., & Gu, J. J. (2025) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2025.116424 · Cited by 87
Deep Graph Neural Network for Fault Detection and Identification in Distribution Systems
Ngo, Q.-H., Nguyen, B. L.-H., Zhang, J., Schoder, K., Ginn, H. L., & Vu, T. (2024) · Electric Power Systems Research · doi:10.1016/j.epsr.2025.111721 · Cited by 83
Missing Value Replacement for PMU Data via Deep Learning Model With Magnitude Trend Decoupling
Cheng, Y., Foggo, B., Yamashita, K., & Yu, N. (2023) · IEEE Access · doi:10.1109/access.2023.3254448 · Cited by 26
Harish, A., Asok, P., & Jayan, M. V. (2023) · Energy and AI · doi:10.1016/j.egyai.2023.100301 · Cited by 25
Sarkar, D. U., & Prakash, T. (2023) · Neural Computing and Applications · doi:10.1007/s00521-023-09323-0 · Cited by 21
Metadata
- Authors
- Alqudah, M., Pavlovski, M., Dokic, T., Kezunovic, M., Hu, Y., & Obradovic, Z.
- Affiliations
- Temple University (US)
- Texas A&M University (US)
- Texas A&M University, College Station, TX, USA
- Quanta Technology (United States) (US)
- Venue
- IEEE Transactions on Power Systems
- Published
- 2022-09
- Volume
- 37
- Issue
- 5
- Pages
- 3434-3442
- ISSN
- 0885-8950 (ISSN-L)
- 1558-0679
- OpenAlex
- W4206736509
- Semantic Scholar
- ed0b69dd26033cb6b4eace7d70652a2e6d0577a5
- Cited by
- 55
- References
- 18
- Citations by year
- 2026: 13 · 2025: 23 · 2024: 2 · 2023: 13 · 2022: 4
- FWCI
- 1.32
- Type
- journal article
- Language
- en
- Open access
- green
- www.osti.gov
- Licence
- Locations
- IEEE Transactions on Power Systems (publishedVersion)
- OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) (submittedVersion)
- Funders
- U.S. Department of Energy (DE-OE0000913)
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Power System Optimization and Stability
- Physical Sciences › Engineering › Control and Systems Engineering › Power Systems Fault Detection
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Smart Grid and Power Systems
- Keywords
- fault detection, power grid, phasor measurement units, synchrophasor data, convolutional neural networks, outage detection, time series classification, supervised learning, dimensionality reduction, data noise reduction
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
A language model drew the claims from the paper on 2026-11-24, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-11-24 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.