Thermal comfort in naturally ventilated and air-conditioned buildings in humid subtropical climate zone in China
Abstract
A thermal comfort field study has been carried out in five cities in the humid subtropical climate zone in China. The survey was performed in naturally ventilated and air-conditioned buildings during the summer season in 2006. There were 229 occupants from 111 buildings who participated in this study and 229 questionnaire responses were collected. Thermal acceptability assessment reveals that the indoor environment in naturally ventilated buildings could not meet the 80% acceptability criteria prescribed by ASHRAE Standard 55, and people tended to feel more comfortable in air-conditioned buildings with the air-conditioned occupants voting with higher acceptability (89%) than the naturally ventilated occupants (58%). The neutral temperatures in naturally ventilated and air-conditioned buildings were 28.3 degrees C and 27.7 degrees C, respectively. The range of accepted temperature in naturally ventilated buildings (25.0-31.6 degrees C) was wider than that in air-conditioned buildings (25.1-30.3 degrees C), which suggests that occupants in naturally ventilated buildings seemed to be more tolerant of higher temperatures. Preferred temperatures were 27.9 degrees C and 27.3 degrees C in naturally ventilated and air-conditioned buildings, respectively, both of which were 0.4 degrees C cooler than neutral temperatures. This result suggests that people of hot climates may use words like "slightly cool" to describe their preferred thermal state. The relationship between draught sensation and indoor air velocity at different temperature ranges indicates that indoor air velocity had a significant influence over the occupants' comfort sensation, and air velocities required by occupants increased with the increasing of operative temperatures. Thus, an effective way of natural ventilation which can create the preferred higher air movement is called for. Finally, the indoor set-point temperature of 26 degrees C or even higher in air-conditioned buildings was confirmed as making people comfortable, which supports the regulation in China that in public and office buildings the set-point temperature of air-conditioning system should not be lower than 26 degrees C.
Integrity signals
Registry
Cites
Statistics
Claims the paper makes
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
Several papers report that the adaptation to the local climate is more pronounced in occupants of naturally-ventilated buildings than in people usually staying in air-conditioned buildings.
“Importantly, several papers report that the adaptation to the local climate is more pronounced in occupants of naturally-ventilated buildings than in people usually staying in air-conditioned buildings [92–94].”
From Drivers of diversity in human thermal perception – A review for holistic comfort models (2018) · cites this paper as [94]
Cites
(1998) · eScholarship (California Digital Library) · Cited by 1,934 · see citing works
Thermal comfort in naturally ventilated buildings: revisions to ASHRAE Standard 55
de Dear, R., & Brager, G. S. (2002) · Energy and Buildings · doi:10.1016/s0378-7788(02)00005-1 · Cited by 1,440 · see citing works
Understanding the adaptive approach to thermal comfort
Humphreys, & Nicol, F. (1998) · OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · Cited by 477 · see citing works
Adaptive thermal comfort standards in the hot–humid tropics
Nicol, F. (2004) · Energy and Buildings · doi:10.1016/j.enbuild.2004.01.016 · Cited by 439 · see citing works
Thermal comfort for naturally ventilated houses in Indonesia
Feriadi, H., & Ng, E. (2004) · Energy and Buildings · doi:10.1016/j.enbuild.2004.01.011 · Cited by 370 · see citing works
Thermal comfort in classrooms in the tropics
Ng, E., & Khoo, S. S. (2003) · Energy and Buildings · doi:10.1016/s0378-7788(02)00109-3 · Cited by 359 · see citing works
Thermal comfort: use of controls in naturally ventilated buildings
Raja, I. A., Nicol, F., McCartney, K. J., & Humphreys, M. (2001) · Energy and Buildings · doi:10.1016/s0378-7788(00)00087-6 · Cited by 305 · see citing works
Field experiments on thermal comfort in campus classrooms in Taiwan
Hwang, R., Lin, T., & Kuo, N.-J. (2005) · Energy and Buildings · doi:10.1016/j.enbuild.2005.05.001 · Cited by 255 · see citing works
de Dear, R., Leow, K.-Y., & Foo, S. C. (1991) · International Journal of Biometeorology · doi:10.1007/bf01041840 · Cited by 229 · see citing works
Report on thermal comfort and building energy studies in Jakarta—Indonesia
Karyono, T. H. (2000) · Building and Environment · doi:10.1016/s0360-1323(98)00066-3 · Cited by 205 · see citing works
Thermal comfort evaluation of naturally ventilated public housing in Singapore
Wong, N. H., Feriadi, H., Lim, P., et al. (2002) · Building and Environment · doi:10.1016/s0360-1323(01)00103-2 · Cited by 191 · see citing works
Thermal comfort in Japanese schools
Kwok, A. G., & Chun, C. (2003) · Solar Energy · doi:10.1016/s0038-092x(03)00147-6 · Cited by 162 · see citing works
A comparative analysis of short-term and long-term thermal comfort surveys in Iran
Heidari, S., & Sharples, S. (2002) · Energy and Buildings · doi:10.1016/s0378-7788(02)00011-7 · Cited by 159 · see citing works
Adaptive comfort temperature model of air-conditioned building in Hong Kong
Mui, K. W., & Chan, W. T. (2003) · Building and Environment · doi:10.1016/s0360-1323(03)00020-9 · Cited by 147 · see citing works
Upper limits for indoor air humidity to avoid uncomfortably humid skin
Toftum, J., Jørgensen, A. S., & Fanger, P. O. (1998) · Energy and Buildings · doi:10.1016/s0378-7788(97)00017-0 · Cited by 141 · see citing works
Field study of a thermal environment and adaptive model in Shanghai
Ye, X., Zhou, Z., Lian, Z., et al. (2006) · Indoor Air · doi:10.1111/j.1600-0668.2006.00434.x · Cited by 125 · see citing works
Thermal Comfort Investigation of Naturally Ventilated Classrooms in a Subtropical Region
Zhang, G., Zheng, C., Yang, W. H., et al. (2007) · Indoor and Built Environment · doi:10.1177/1420326x06076792 · Cited by 122 · see citing works
Self-citationYa, F. (2004) · Energy and Buildings · doi:10.1016/j.enbuild.2003.08.003 · Cited by 121 · see citing works
Validation of the predicted mean vote model of thermal comfort in six Australian field studies
de Dear, R., & Auliciems, A. (1985) · ASHRAE winter conference papers · Cited by 106 · see citing works
Gagge, A. P. (1973) · Medical Entomology and Zoology · Cited by 62 · see citing works
de Dear, R., Leow, K.-Y., & Ameen, A. (1991) · National University of Singapore · Cited by 59 · see citing works
Fountain, M. (1991) · eScholarship (California Digital Library) · Cited by 24 · see citing works
Wu, S. (2006) · Journal of Subtropical Resources and Environment · Cited by 12 · see citing works
Flagged first, then by citations
Cited by
Sorted by citations
A review of human thermal comfort in the built environment
Rupp, R. F., Vásquez, N. G., & Lamberts, R. (2015) · Energy and Buildings · doi:10.1016/j.enbuild.2015.07.047 · Cited by 907 · see citing works
Field studies on human thermal comfort — An overview
Mishra, A. K., & Ramgopal, M. (2013) · Building and Environment · doi:10.1016/j.buildenv.2013.02.015 · Cited by 336 · see citing works
Drivers of diversity in human thermal perception – A review for holistic comfort models
Schweiker, M., Huebner, G. M., Kingma, B. R. M., Kramer, R., & Pallubinsky, H. (2018) · Temperature · doi:10.1080/23328940.2018.1534490 · Cited by 231 · see citing works
The influence of relative humidity on adaptive thermal comfort
Vellei, M., Herrera, M., Fosas, D., & Natarajan, S. (2017) · Building and Environment · doi:10.1016/j.buildenv.2017.08.005 · Cited by 188 · see citing works
- Authors
- Yang, W., & Zhang, G.
- Affiliations
- Hunan University (CN)
- Corresponding author
- Zhang, Guoqiang
- Venue
- International Journal of Biometeorology
- Published
- 2007-12-12
- Volume
- 52
- Issue
- 5
- Pages
- 385-398
- ISSN
- 0020-7128 (ISSN-L)
- 1432-1254
- OpenAlex
- W2053546050
- Cited by
- 134
- References
- 24
- Citations by year
- 2026: 9 · 2025: 9 · 2024: 8 · 2023: 14 · 2022: 7 · 2021: 15 · 2020: 10 · 2019: 6 · 2018: 10 · 2017: 6 · 2016: 2 · 2015: 6 · 2014: 4 · 2013: 11 · 2012: 6
- FWCI
- 8.81
- Type
- journal article
- Language
- en
- Open access
- closed
- Licence
- www.springer.com/tdm (tdm)
- Locations
- International Journal of Biometeorology (publishedVersion)
- PubMed (publishedVersion)
- Victoria University Research Repository (Victoria University) (submittedVersion)
- Topics
- Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
- Physical Sciences › Environmental Science › Environmental Engineering › Urban Heat Island Mitigation
- Physical Sciences › Environmental Science › Environmental Engineering › Wind and Air Flow Studies
- Keywords
- thermal comfort, natural ventilation, air-conditioned buildings, humid subtropical climate, ASHRAE Standard 55, neutral temperature, thermal preference, indoor air velocity, thermal acceptability, occupant thermal perception
- MeSH terms
- Adult, Air Conditioning, China, Clothing, Female, Humans, Humidity, Male, Seasons, Sensation, Temperature, Tropical Climate, Ventilation
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review