Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond

Open access
Diahovchenko, Illia, Najafi, Ehsan, O'Donnell, Terence · 2026 · IEEE Access

The DOI matches its Crossref record; 22 of the 34 references it cites were found in a registry or an index, and 3 are not checked yet; none of the 27 sources its claims cite is checked for support yet.

Abstract

Variable frequency drives are extensively utilized to control the speed of motors supplied with alternating current, enhancing efficiency and productivity. However, their nonlinear nature distorts electrical waveforms, generating harmonics besides the fundamental frequency. This paper analyses and compares several commercially available solutions for harmonic alleviation, including multipulse converters, broadband passive filters, and active filtering technologies. Two case studies are presented with simulations and experimental measurements.

Checked 2026-11-23 · 3 references not checked yet

Overview

CoChat Summary

TL;DR

This paper compares 18-pulse drives, broadband/high-performance passive harmonic filters, and active harmonic filters for industrial VFD loads across an MV/LV workshop simulation and a university-campus heat pump case study with measurements. It finds that passive filters can achieve full IEC and IEEE compliance in the workshop, while the AHF meets low-order limits but injects supraharmonics and can worsen transformer derating and telephone interference risk.

Key findings

  • In the industrial workshop base case, THD V was 14%, exceeding the EN 50160 8% limit; the 5th and 13th voltage harmonics were 11.7% and 3.1% and exceeded limits; the system failed IEC 61000-3-12 and IEEE 519, and cable connections 2, 3, and 4 were overloaded. 18-pulse drives reduced THD V to 7.2%, meeting EN 50160, but the 17th and 19th harmonics were 3.3% and 2.7% and exceeded limits; IEC 61000-3-12 was fully met, but IEEE 519 was not met for TDD I and individual current harmonics. Broadband AUHFs reduced THD V to 5.3% and TDD I from 22.3% to 7.2% (67.7% reduction), meeting IEC 61000-3-12 but not IEEE 519 until additional AUHFs for the 75 kW loads 6 and 7 raised installed filter power to 1000 kW; an AUHF-HP arrangement reached IEEE 519 at 860 kW.
  • For the heat pump base case, THD V was 9.1%, exceeding the EN 50160 8% limit; the 5th and 19th voltage harmonics were 7.1% and 1.6%, beyond the 6.0% and 1.5% limits; the system failed IEC 61000-3-12 and IEEE 519, and the I-T product was 107642. An AUHF gave THD V of 2.5% and THD I of 5.6%, satisfying EN 50160 and IEC 61000-3-12 but not IEEE 519. The AHF experimentally mitigated harmonics up to the 25th, bringing EN 50160 compliance, but violated IEC 61000-3-12 PWHD limits and IEEE 519 TDD I and the 29th and 35th current harmonics; simulation TDD I was within limits because the simulated AHF was not limited to the 25th harmonic.
  • The measured AHF injected supraharmonics up to 0.14% of the fundamental current around 20 kHz, while the VFD switching frequency was around 10 kHz. Transformer derating analysis indicated the AHF can improve overall transformer loading by up to 20% when supraharmonics are included; extending the spectrum from the 100th to the 600th order reduced loading by 1.38% with the AHF versus 7.30% without filtering. TIF/I-T products remained high: 219737 for the industrial workshop, above the IEEE 519 threshold of 25000, and 42077 for the heat pump with AUHF.
  • Overall, passive filters can meet standards but may introduce resonance risk; supraharmonics remain unregulated and are not covered by IEC/IEEE limits up to the 50th harmonic or EN 50160 limits up to the 25th, motivating updated standards.

Methods

  • Two case studies were modeled: (i) an MV/LV industrial workshop with one linear and seven nonlinear VFD-driven motor loads, a 2000-meter cable, a 10/0.4 kV 1600 kVA transformer, and two PCCs, simulated in SOLV under base 6-pulse, 18-pulse, AUHF, and AUHF+AUHF-HP scenarios; and (ii) a 400 kW air-to-water university-campus heat pump powered by three 6-pulse VFDs, connected via a 630 kVA delta-star transformer and drawing 340 kW during measurements, modeled in SOLV under base, PHF, and AHF scenarios.
  • Experimental measurements used a Fluke 1777 power quality analyzer with 30 kHz bandwidth at PCC 1 and near the heat pump, with 200 Hz bins in 2–9 kHz and 2 kHz bins in 9–30 kHz; the AHF was also simulated in MATLAB-Simulink. Analysis covered THD V/I, TDD, PWHD, individual harmonics, compliance with IEC 61000-3-12, EN 50160, and IEEE 519, supraharmonics up to 4.15 kHz in SOLV and up to 30 kHz experimentally, plus transformer derating per IEEE C57.110 and telephone interference via TIF/I-T product.

Limitations

  • The paper states that SOLV does not provide AHF equivalents, so active harmonic mitigation could not be assessed in the industrial workshop case study; simulation results are approximate and actual performance may vary due to field conditions. It also states that the simulation model showed slightly better harmonic mitigation than the experiment because background harmonics from neighboring connections were not considered, parasitic elements were not accurately modeled, and the installed AHF had practical limitations such as measurement noise and semiconductor switching performance.
  • The paper states that the AHF design compensates odd harmonics up to the 25th order, and the experimental AHF failed at higher orders; passive filters may introduce resonance risks if system impedance varies or capacitor banks interact with upstream network inductance, although no resonance was observed in the studied cases. It also notes that supraharmonics remain unregulated and that common standards cover only up to the 50th harmonic (IEC/IEEE) or 25th harmonic (EN 50160).
  • The text makes evident additional limitations: the industrial workshop AHF was not tested due to the SOLV limitation; the heat pump AHF experiment was limited to the 25th harmonic while the simulation was not, contributing to the simulation/experiment discrepancy; and supraharmonic assessment was bounded by the SOLV upper limit of 4.15 kHz and the measurement bandwidth of 30 kHz.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

Crossref · 10.1109/access.2026.3682461

Cites

22 of 34 references verified0 citation errors · 9 not checkable

Statistics

Nothing to recompute.

Verification

Claims the paper makes

0 Valid · 2 Not valid · 26 Not checked · 85 Own results and interpretations

42 more claims

Create a free account to see all 113 claims and to verify the 27 references still open.

See all claims — free account
  • It may state two separate claims as one. 53
  • The quote only partly states this claim. 1
  • Probably not a substantial claim. 19

Create a free account to see these claims.

Self-check

Percentages, sums and reported differences re-computed from the paper’s own numbers.

Each contradiction between two passages listed here was confirmed by an independent check.

1 of 1

Citations

Cites

Show all 34 references

Cited by

Metadata

Authors
Diahovchenko, I., Najafi, E., & O'Donnell, T.
Affiliations
  • University College Dublin (IE)
  • 1Energy Institute, University College Dublin, 4
Venue
IEEE Access
Published
2026
Volume
14
Pages
55788-55801
ISSN
2169-3536 (ISSN-L)
OpenAlex
W7152643369
Cited by
0
References
34
FWCI
0.00
Type
journal article
Language
en
Open access
Locations
  • IEEE Access (publishedVersion, cc-by)
  • DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
Funders
Next Generation Energy Systems (NexSys) project (SFI/21/SPP/3756)
Topics
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Power Quality and Harmonics
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Electromagnetic Compatibility and Noise Suppression
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Multilevel Inverters and Converters
Keywords
harmonic compensation, variable frequency drive, supraharmonics, active power filter, voltage distortion, transformer overheating, cable overheating, heat pumps, industrial power quality, power quality standards

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

A language model drew the claims from the paper on 2026-11-23, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).

A second model labelled each claim on 2026-11-23 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.