Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond
Open accessThe DOI matches its Crossref record; 22 of the 34 references it cites were found in a registry or an index, and 3 are not checked yet; none of the 27 sources its claims cite is checked for support yet.
Abstract
Variable frequency drives are extensively utilized to control the speed of motors supplied with alternating current, enhancing efficiency and productivity. However, their nonlinear nature distorts electrical waveforms, generating harmonics besides the fundamental frequency. This paper analyses and compares several commercially available solutions for harmonic alleviation, including multipulse converters, broadband passive filters, and active filtering technologies. Two case studies are presented with simulations and experimental measurements.
Checked 2026-11-23 · 3 references not checked yet
Overview
CoChat Summary
TL;DR
This paper compares 18-pulse drives, broadband/high-performance passive harmonic filters, and active harmonic filters for industrial VFD loads across an MV/LV workshop simulation and a university-campus heat pump case study with measurements. It finds that passive filters can achieve full IEC and IEEE compliance in the workshop, while the AHF meets low-order limits but injects supraharmonics and can worsen transformer derating and telephone interference risk.
Key findings
- In the industrial workshop base case, THD V was 14%, exceeding the EN 50160 8% limit; the 5th and 13th voltage harmonics were 11.7% and 3.1% and exceeded limits; the system failed IEC 61000-3-12 and IEEE 519, and cable connections 2, 3, and 4 were overloaded. 18-pulse drives reduced THD V to 7.2%, meeting EN 50160, but the 17th and 19th harmonics were 3.3% and 2.7% and exceeded limits; IEC 61000-3-12 was fully met, but IEEE 519 was not met for TDD I and individual current harmonics. Broadband AUHFs reduced THD V to 5.3% and TDD I from 22.3% to 7.2% (67.7% reduction), meeting IEC 61000-3-12 but not IEEE 519 until additional AUHFs for the 75 kW loads 6 and 7 raised installed filter power to 1000 kW; an AUHF-HP arrangement reached IEEE 519 at 860 kW.
- For the heat pump base case, THD V was 9.1%, exceeding the EN 50160 8% limit; the 5th and 19th voltage harmonics were 7.1% and 1.6%, beyond the 6.0% and 1.5% limits; the system failed IEC 61000-3-12 and IEEE 519, and the I-T product was 107642. An AUHF gave THD V of 2.5% and THD I of 5.6%, satisfying EN 50160 and IEC 61000-3-12 but not IEEE 519. The AHF experimentally mitigated harmonics up to the 25th, bringing EN 50160 compliance, but violated IEC 61000-3-12 PWHD limits and IEEE 519 TDD I and the 29th and 35th current harmonics; simulation TDD I was within limits because the simulated AHF was not limited to the 25th harmonic.
- The measured AHF injected supraharmonics up to 0.14% of the fundamental current around 20 kHz, while the VFD switching frequency was around 10 kHz. Transformer derating analysis indicated the AHF can improve overall transformer loading by up to 20% when supraharmonics are included; extending the spectrum from the 100th to the 600th order reduced loading by 1.38% with the AHF versus 7.30% without filtering. TIF/I-T products remained high: 219737 for the industrial workshop, above the IEEE 519 threshold of 25000, and 42077 for the heat pump with AUHF.
- Overall, passive filters can meet standards but may introduce resonance risk; supraharmonics remain unregulated and are not covered by IEC/IEEE limits up to the 50th harmonic or EN 50160 limits up to the 25th, motivating updated standards.
Methods
- Two case studies were modeled: (i) an MV/LV industrial workshop with one linear and seven nonlinear VFD-driven motor loads, a 2000-meter cable, a 10/0.4 kV 1600 kVA transformer, and two PCCs, simulated in SOLV under base 6-pulse, 18-pulse, AUHF, and AUHF+AUHF-HP scenarios; and (ii) a 400 kW air-to-water university-campus heat pump powered by three 6-pulse VFDs, connected via a 630 kVA delta-star transformer and drawing 340 kW during measurements, modeled in SOLV under base, PHF, and AHF scenarios.
- Experimental measurements used a Fluke 1777 power quality analyzer with 30 kHz bandwidth at PCC 1 and near the heat pump, with 200 Hz bins in 2–9 kHz and 2 kHz bins in 9–30 kHz; the AHF was also simulated in MATLAB-Simulink. Analysis covered THD V/I, TDD, PWHD, individual harmonics, compliance with IEC 61000-3-12, EN 50160, and IEEE 519, supraharmonics up to 4.15 kHz in SOLV and up to 30 kHz experimentally, plus transformer derating per IEEE C57.110 and telephone interference via TIF/I-T product.
Limitations
- The paper states that SOLV does not provide AHF equivalents, so active harmonic mitigation could not be assessed in the industrial workshop case study; simulation results are approximate and actual performance may vary due to field conditions. It also states that the simulation model showed slightly better harmonic mitigation than the experiment because background harmonics from neighboring connections were not considered, parasitic elements were not accurately modeled, and the installed AHF had practical limitations such as measurement noise and semiconductor switching performance.
- The paper states that the AHF design compensates odd harmonics up to the 25th order, and the experimental AHF failed at higher orders; passive filters may introduce resonance risks if system impedance varies or capacitor banks interact with upstream network inductance, although no resonance was observed in the studied cases. It also notes that supraharmonics remain unregulated and that common standards cover only up to the 50th harmonic (IEC/IEEE) or 25th harmonic (EN 50160).
- The text makes evident additional limitations: the industrial workshop AHF was not tested due to the SOLV limitation; the heat pump AHF experiment was limited to the 25th harmonic while the simulation was not, contributing to the simulation/experiment discrepancy; and supraharmonic assessment was bounded by the SOLV upper limit of 4.15 kHz and the measurement bandwidth of 30 kHz.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
0 Valid · 2 Not valid · 26 Not checked · 85 Own results and interpretations
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Overall, the simulation model shows slightly better harmonic mitigation performance, which can be attributed to natural differences between the simulation environment and real-world practice.”
§ Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond > D. ACTIVE HARMONIC FILTER SOLUTION
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Rests on an assumption not shown here.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Also, the total THD I values at the individual connections equipped with the AUHF-HP have improved.”
§ Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond > D. USING BROADBAND FILTERS
plainstates a causeSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Rests on an assumption not shown here.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Table 3 suggests that with this combined arrangement, the power system of the industrial workshop is fully compliant with the harmonic requirements of IEC 61000-3-12.”
§ Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond > D. USING BROADBAND FILTERS
hedgedstates a causeSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Rests on an assumption not shown here.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The transformer load factor has been reduced to 0.91.”
§ Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond > C. USING 18-PULSE DRIVES
plainstates a causeSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Rests on an assumption not shown here.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The voltage and current waveforms at the PCC 1 are very non-sinusoidal, as demonstrated in Fig. 3.”
§ Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond > B. BASE CASE
boostedSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Rests on an assumption not shown here.
42 more claims
Create a free account to see all 113 claims and to verify the 27 references still open.
- It may state two separate claims as one. 53
- The quote only partly states this claim. 1
- Probably not a substantial claim. 19
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond > II. HARMONIC ASSESSMENT AND LIMITS
“To account for the effects of higher-order harmonics on transformer performance, the IEEE 57.110-2018 standard recommends applying a derating factor.”
§ Harmonic Mitigation Solutions for Industrial Connections With Variable Frequency Drives: Meeting the Standards and Beyond > References
“Establishing Liquid-Filled Dry-Type Power Distribution Transformer Capability When Supplying Nonsinusoidal Load Currents, Standard C57.110-2008. Pract Ieee Recommended, 2008IEEE Power and Energy Society”
Citations
Cites
Emerging Power Quality Challenges Due to Integration of Renewable Energy Sources
Liang, X. (2017) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2016.2626253 · Cited by 935
Liang, X., & Andalib -Bin- Karim, C. (2018) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2018.2823680 · Cited by 249 · cited 2×
“In the majority of the cases, THD V are below 5%, whereas THD I values can be anywhere between 1% and 35% [11].”
Harmonic Sources Modeling and Characterization in Modern Power Systems: A Comprehensive Overview
Hu, Z. F., Han, Y., Zalhaf, A. S., Zhou, S., Zhao, E., & Yang, P. (2023) · Electric Power Systems Research · doi:10.1016/j.epsr.2023.109234 · Cited by 131 · cited 1×
“In commercial buildings, harmonic distortions can appear due to nonlinear switch-mode power supplies, which are used in computers, servers, printers, photocopiers, telecommunication systems, broadcasting equipment, banking machines, and many other electronic devices [1].”
Supraharmonics in Power Grid: Identification, Standards, and Measurement Techniques
Alfalahi, S. T. Y., Alkahtani, A. A., Al-Shetwi, A. Q., Al-Ogaili, A. S., Abbood, A. A., Mansor, M., & Fazea, Y. (2021) · IEEE Access · doi:10.1109/access.2021.3099013 · Cited by 99 · cited 2×
“C damping stages at the AHF output [16].”
Diagnosis of supraharmonics-related problems based on the effects on electrical equipment
Espín-Delgado, Á., Rönnberg, S. K., Letha, S. S., & Bollen, M. (2021) · Electric Power Systems Research · doi:10.1016/j.epsr.2021.107179 · Cited by 85 · cited 1×
“The article [17] proposes guidelines and formulas for evaluating the negative impact of supraharmonics based on interference morphology, such as light flicker, tripping of residential current devices, noise, and cable termination failures.”
Thermal analysis and derating of a power transformer with harmonic loads
Mikhak‐Beyranvand, M., Faiz, J., & Rezaeealam, B. (2020) · IET Generation, Transmission & Distribution · doi:10.1049/iet-gtd.2019.0703 · Cited by 39 · cited 1×
“To prevent a preliminary failure of a transformer supplying nonlinear loads, its rated power can be reduced, which is commonly known as derating [22].”
Modeling and Analysis of Supraharmonic Propagation for Stochastic Studies
Espín-Delgado, Á., & Rönnberg, S. K. (2022) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2022.3162712 · Cited by 35 · cited 1×
“The paper [18] introduces a stochastic method to analyze supraharmonic propagation, highlighting how the impact of low-voltage load impedance can be quantified to help grid operators mitigate upstream propagation and preserve power quality.”
Active Harmonic Mitigation: What the Manufacturers Don't Tell You
Hoevenaars, A., Farbis, M., & McGraw, M. (2020) · IEEE Industry Applications Magazine · doi:10.1109/mias.2020.2982484 · Cited by 29 · cited 3×
“…use of fast-switching components in equipment such as converters (including inverters) connected directly to the utility grid, harmonics in the 2–150 kHz range, known as supraharmonics, have become increasingly common and problematic, causing voltage distortion and additional harmonic losses [9].”
InfluentialIs Transformer kVA Derating Always Required Under Harmonics? A Manufacturer's Perspective
Das, B. P., & Radakovic, Z. (2018) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2018.2815901 · Cited by 26 · cited 1×
“The paper [25] demonstrates that, depending on the load profile, type of oil, and the ambient temperature, a derating might not be required or may be required only for a particular duration.”
Contemporary electric energy meters testing under simulated nonsinusoidal field conditions
Diahovchenko, I. M., Dolník, B., Kanálik, M., & Kurimský, J. (2021) · Electrical Engineering · doi:10.1007/s00202-021-01365-8 · Cited by 24
Self-citationDiahovchenko, I., Chuprun, A., & Čonka, Z. (2023) · Electric Power Systems Research · doi:10.1016/j.epsr.2023.109455 · Cited by 19 · cited 1×
“Moreover, harmonic currents injected by nonlinear loads substantially increase the copper and eddy current losses in distribution transformers, resulting in overheating, accelerating insulation degradation, and ultimately reducing the transformer’s lifetime [21].”
Self-citationВолохін, В. В., & Diahovchenko, I. M. (2016) · IEEE International Conference Nanomaterials: Applications & Properties (NAP) · doi:10.1109/nap.2016.7757298 · Cited by 15 · cited 1×
“Moreover, distortions in voltage and current waveforms can compromise the work of relay protection, reduce the accuracy of current transformers [6], and influence the readings of electric energy meters [7].”
Self-citationVolokhin, V., Diahovchenko, I., Kurochkina, V., & Kanálik, M. (2017) · Energetika · doi:10.6001/energetika.v63i1.3503 · Cited by 13 · cited 2×
“The apparent power can be assessed with the formula [27]: Limits for harmonics are specified in several national and international standards.”
Self-citationThermal effects due to harmonics on dry-type transformers: Impact of filters and phase angles
Costa, M. C., Fortes, M. Z., Sotelo, G. G., & França, B. W. (2025) · Measurement Energy · doi:10.1016/j.meaene.2025.100045 · Cited by 11
Hoevenaars, A. H., McGraw, M., & Alexander, J. (2017) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2016.2603143 · Cited by 7
Telephone Interference From Solar PV Switching
Singh, G., Cooke, T., Johns, J., Vega, L., Valdez, A., & Bull, G. (2023) · IEEE Open Access Journal of Power and Energy · doi:10.1109/oajpe.2023.3239854 · Cited by 5
Hu, Y., Wang, L., Li, J., Weng, H., Zheng, Z., Wen, G., & Zhang, F. (2025) · Energies · doi:10.3390/en18174707 · Cited by 4 · cited 2×
“An industrial-scale air-to-water heat pump of 400 kW capacity is installed at a university campus and connected to the MV grid via a delta-star transformer with a rated power of 630 kVA, with the parameters as per [32].”
InfluentialHarmonic Mitigation Solutions for Industrial Connections with Variable Frequency Drives
Diahovchenko, I. M., & Serhiienko, S. (2024) · AEIT International Annual Conference · doi:10.23919/aeit63317.2024.10736817 · Cited by 2 · cited 2×
“It further enhances the results presented in [14] by: (a) integrating compliance assessment of the recognized international standards with supraharmonic analysis, (b) including an experimental case study on a campus-scale system, (c) discussing the recommended practices for transformer derating and…”
Self-citationNajafi, E., Keane, A., Etemad, A., Hashmi, K., & Zakariazadeh, A. (2024) · IEEE PES Innovative Smart Grid Technologies Europe · doi:10.1109/isgteurope62998.2024.10863386 · Cited by 2 · cited 3×
“While the individual power ratings of domestic inverters and chargers are much lower than those of industrial loads, their large numbers and prolonged simultaneous operation make them significant contributors to harmonic distortion [4].”
InfluentialSelf-citationDiahovchenko, I. M., Keane, A., Petrovskyi, M. V., Лебединський, І. Л., & Petrichenko, R. (2025) · Lecture notes in electrical engineering · doi:10.1007/978-3-031-97333-8_5 · Cited by 2
Self-citationCost-Weight Analysis of Transformers with Different K-Factor Values: A Comparative Study
Dawood, K., Çakir, M. A., & Tursun, S. (2024) · 2024 15th National Conference with International Participation (ELECTRONICA) · doi:10.1109/electronica63645.2024.11146149 · Cited by 1
Electrical Distribution Fundamentals Design Guide
(2024)
UnresolvedHarmonic mitigation strategies in variable frequency drive applications
Wallace (2021) · ASHRAE Trans.
UnresolvedGuide To Harmonics With AC Drives
(2017)
UnresolvedHarmonic solutions explained
Carnovale (2021)
UnresolvedPower quality
Sankaran (2001) · Cashier Technique Schneider Electric
UnresolvedUntitled work
(2022) · IEEE Std. 519-2022. Standard for Harmonic Control in Electric Power Systems
UnresolvedHarmonic detection and filtering
(2008)
UnresolvedElectrical Power Systems Quality
Dugan (2012)
UnresolvedUntitled work
Kusko (2007) · Power quality in electrical systems
UnresolvedLineator: Advanced Universal Harmonic Filter
(2022)
UnresolvedSOLV Harmonic Analysis Software
(2025)
UnresolvedMultifunction Active Filters AFQm
(2026)
Unresolved
Cited by
Diahovchenko, I. M., Keane, A., & Zahorodnia, T. (2026) · IEEE Access · doi:10.1109/access.2026.3710418
Self-citationA practical study on the impact of a large heat pump on harmonic distortion
Najafi, E., Diahovchenko, I. M., & O'Sullivan, R. (2026) · International Conference on Harmonics and Quality of Power · doi:10.1109/ichqp67927.2026.11756895
Self-citation
Metadata
- Authors
- Diahovchenko, I., Najafi, E., & O'Donnell, T.
- Affiliations
- University College Dublin (IE)
- 1Energy Institute, University College Dublin, 4
- Venue
- IEEE Access
- Published
- 2026
- Volume
- 14
- Pages
- 55788-55801
- ISSN
- 2169-3536 (ISSN-L)
- OpenAlex
- W7152643369
- Cited by
- 0
- References
- 34
- FWCI
- 0.00
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Locations
- IEEE Access (publishedVersion, cc-by)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
- Funders
- Next Generation Energy Systems (NexSys) project (SFI/21/SPP/3756)
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Power Quality and Harmonics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Electromagnetic Compatibility and Noise Suppression
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Multilevel Inverters and Converters
- Keywords
- harmonic compensation, variable frequency drive, supraharmonics, active power filter, voltage distortion, transformer overheating, cable overheating, heat pumps, industrial power quality, power quality standards
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
A language model drew the claims from the paper on 2026-11-23, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-11-23 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.