Design and Implementation of a Modular Multilevel Converter With Hierarchical Redundancy Ability for Electric Ship MVDC System
The DOI matches its Crossref record; 35 of the 35 references it cites were found in a registry or an index.
Abstract
Modular multilevel converter (MMC) can be considered as a promising candidate for modern electric ship medium-voltage direct current (MVDC) power system due to its high-voltage quality, low switching loss, good expansibility, and good redundancy. As the voltage level in MVDC is much lower than that in high-voltage direct current case, the number of submodules (SMs) of MMC in MVDC system is also much less. Therefore, the SM failure will have more significant effect on the safety operation. Since uninterrupted operation is one of the most important requirements in electric ship application, the special redundancy design for MMC is required. This paper thus proposes an MMC system with hierarchical redundancy ability, aiming to guarantee the ride-through operation under SM failure. The “hot-reserved” and “cold-reserved” SMs are prepared in the MMC by compromising the faulty SM number, voltage and current stress of SMs, SM power loss, and so on, and the hierarchical redundancy strategy is divided into several progressive layers to ride through the SM failure in different cases. The pretreatment units are designed to realize the proposed hierarchical redundant strategy smoothly, and without changing the existent modulation and sort-and-selection strategies designed for normal condition. The proposed design is explained in this paper, and verified by a three-phase MMC simulation and a single-phase MMC prototype.
Overview
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
Citations
Cites
Multicarrier PWM strategies for multilevel inverters
McGrath, B. P., & Holmes, D. G. (2002) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2002.801073 · Cited by 1,232 · cited 1×
“on the method [35], aiming to generate the proper SM number signal nL that needs to be driven by “1”; however, its rule has been extended to adapt to the redundancy purpose.”
MethodFault Detection for Modular Multilevel Converters Based on Sliding Mode Observer
Shao, S., Wheeler, P. W., Clare, J. C., & Watson, A. J. (2013) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2013.2242093 · Cited by 361 · cited 1×
“battery [4], [16], [17], the MMC can obtain the energy storage ability; and if the active power filter is added to”
BackgroundLi, B., Shi, S., Wang, B., Wang, G., Wang, W., & Xu, D. (2016) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2015.2454534 · Cited by 329 · cited 1×
“In [18] and [19], SM fault is detected by sliding mode observer.”
BackgroundSon, G. T., Lee, H.-J., Nam, T. S., Chung, Y.-H., Lee, U.-H., Baek, S.-T., Hur, K., & Park, J.-W. (2012) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2012.2190530 · Cited by 290 · cited 3×
“In [23]–[26], the “hot-reserved” and “cold-reserved” SMs were prepared.”
BackgroundOperation of a Medium-Voltage Drive Under Faulty Conditions
Rodriguez, J., Hammond, P. W., Pontt, J., Musalem, R., Lezana, P., & Escobar, M. J. (2005) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2005.851645 · Cited by 282
Fault Detection and Localization Method for Modular Multilevel Converters
Deng, F., Chen, Z., Khan, M. R., & Zhu, R. (2015) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2014.2348194 · Cited by 266 · cited 1×
“battery [4], [16], [17], the MMC can obtain the energy storage ability; and if the active power filter is added to”
BackgroundModular multilevel inverter: pulse width modulation and capacitor balancing technique
Adam, G. P., Anaya-Lara, O., Burt, G. M., Telford, D., Williams, B. W., & McDonald, J. R. (2010) · IET Power Electronics · doi:10.1049/iet-pel.2009.0184 · Cited by 248
Shao, S., Watson, A. J., Clare, J. C., & Wheeler, P. W. (2016) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2015.2462717 · Cited by 182 · cited 1×
“Reference [20] employed a Kalman filter to detect the fault.”
MethodEnhancing the reliability of modular medium-voltage drives
Hammond, P. W. (2002) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2002.803172 · Cited by 176 · cited 1×
“In [23]–[26], the “hot-reserved” and “cold-reserved” SMs were prepared.”
Energy-balancing Control Strategy for Modular Multilevel Converters Under Submodule Fault Conditions
Hu, P., Jiang, D., Zhou, Y., Liang, Y., Guo, J., & Lin, Z. (2014) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2013.2284919 · Cited by 148 · cited 1×
“Besides, the output port of the SM is associated with a mechanical switch Q [23], [30], [31], and it can be turned ON or OFF for redundancy purpose.”
Background
Cited by
Items 101–113 of 113
Jang, D. H., Hwang, Y.-H., Yang, H.-W., Seo, C. W., Ji, T.-H., & Jung, S.-Y. (2023) · IEEE Energy Conversion Congress and Exposition (ECCE) · doi:10.1109/ecce53617.2023.10362731 · Cited by 1
Modified Sorting Algorithm for Fault- Tolerant Operation of Hybrid MMC With Hot Reserve Submodules
Hassanifar, M., Ventura, S., Langwasser, M., D’Amato, D., Monopoli, V. G., & Liserre, M. (2024) · IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG) · doi:10.1109/pedg61800.2024.10667398 · Cited by 1
“Cold reserve SMs are often recommended for MMCs used in high-voltage applications with a large number of SMs [12], [13].”
BackgroundMethodInfluentialReliability analysis and improvement of multilevel converters
Tu, P. (2019) · doi:10.32657/10220/48513 · Cited by 1
Improved Sampled Average Modulation Technique for the Modular Multilevel Converters
Colque, J. C., Filho, E. R., & Azcue-Puma, J. L. (2022) · Energies · doi:10.3390/en15134554
Coordinated Control of MVDC Shipboard Microgrids with Pulsed Power Loads
Xu, L. (2022) · VBN Forskningsportal (Aalborg Universitet) · doi:10.54337/aau499832422
Viatkin, A. (2023) · Springer theses · doi:10.1007/978-3-031-24712-5_1
Diode Clamped Shared Redundancy Topology for Middle Arm Reuse MMC
Liu, W., Chen, Y., Chen, G., Xu, B., & Wang, Y. (2025) · Journal of Physics Conference Series · doi:10.1088/1742-6596/3012/1/012075
“Ref [4] considers factors such as the number of faulty SMs, voltage/current stress, and power loss, and designs a preprocessing unit to implement a hierarchical redundancy strategy.”
Self-citationChen, P., Zhao, J., Zhao, L., Liu, K., Zhou, J., & Deng, F. (2025) · International Journal of Electrical Power & Energy Systems · doi:10.1016/j.ijepes.2025.110933
Erat, A., & Vural, A. M. (2025) · Tehnicki vjesnik - Technical Gazette · doi:10.17559/tv-20250207002344
Fault-Tolerant Control of Full-Bridge Mmc Operating in Boost Mode for Mvdc Applications
D’Amato, D., Bisht, N., & Liserre, M. (2025) · Energy Conversion Congress and Expo Europe (ECCE Europe) · doi:10.1109/ecce-europe62795.2025.11238776
“The redundant SMs can either be integrated during normal operation (hot reserve) [8] or initially bypassed and activated only after a fault occurs (cold reserve) [9].”
Isolated MVDC Power Converters Using Wide Bandgap Technology
Ashraf Gandomi, A. (2024) · eScholarship (California Digital Library)
Zhou, Z., Zhang, B., Lei, M., & Dai, N. (2026) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2026.3690768
Song, S.-W., Kim, H., Kim, J., Kim, S., & Jeon, H. (2026) · Journal of Marine Science and Engineering · doi:10.3390/jmse14171573
“These characteristics have led MMCs to be examined as a viable topology for medium-voltage, high-power drives [3], and they have attracted particular attention in applications that require medium-voltage, high-power variable-speed operation, such as electric ship propulsion [4,5].”
Metadata
- Authors
- Chen, Y., Li, Z., Zhao, S., Wei, X., & Kang, Y.
- Affiliations
- State Key Laboratory of Advanced Electromagnetic Engineering and Technology (CN)
- State Grid Corporation of China (China) (CN)
- Venue
- IEEE Journal of Emerging and Selected Topics in Power Electronics
- Published
- 2017-03
- Volume
- 5
- Issue
- 1
- Pages
- 189-202
- ISSN
- 2168-6777 (ISSN-L)
- 2168-6785
- OpenAlex
- W2550943922
- Cited by
- 111
- References
- 35
- Citations by year
- 2026: 3 · 2025: 8 · 2024: 12 · 2023: 9 · 2022: 16 · 2021: 12 · 2020: 15 · 2019: 13 · 2018: 15 · 2017: 8
- FWCI
- 5.54
- Type
- journal article
- Language
- en
- Open access
- closed
- Locations
- IEEE Journal of Emerging and Selected Topics in Power Electronics (publishedVersion)
- Funders
- Science and Technology Funds of State Grid Preliminary Research for High Voltage DC/DC Converters Suitable for DC Grids
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › HVDC Systems and Fault Protection
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Multilevel Inverters and Converters
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Silicon Carbide Semiconductor Technologies
- Keywords
- modular multilevel converter, electric ships, MVDC
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.