The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications

Open access
Agarwal, Rachit, Li, Hui, Guo, Zhehui, Cheetham, Peter · 2023 · IEEE Transactions on Industrial Electronics

Abstract

The medium-frequency (MF) transformer in a phase-shift modulated dc solid state transformer (SST) is prone to partial discharge (PD) that impacts the system reliability and lifetime. Tightly packed MF transformer windings carrying pulsewidth modulation (PWM) voltages create favorable conditions for PD inception due to proximity between adjacent winding conductors and electric field enhancement because of spiral geometry. A peak potential condition is created between the adjacent posterior conductors of the primary and secondary windings as a result of phase-shifted modulation. This along with fast alternating electric fields incepts PD at lower than expected operating voltages. Early inception of PD leads to premature transformer failure leading to unanticipated dc SST down-time. The effects of PWM voltages containing highdv/dtswitching transients on PD and lifetime characteristics of MF transformer in a dc SST are not yet understood, which is investigated in this article. A nonintrusive PD detection strategy for MF PWM ac voltage is presented using high-speed optical sensors. PD characterization is performed on Kapton polyimide insulated copper foil windings for a foil-type MF transformer. Winding samples are stress tested with steady state PWM voltages up to 2 kV and frequencies up to 50 kHz with highdv/dtup to 60 V/ns generated by a half-bridge inverter using 3.3 kV SiC devices while maintaining the transformer's geometric profile. Accelerated dielectric lifetime characterization is also performed and novel lifetime prediction models are derived based on the acquired results containing both frequency anddv/dtdependent variables.

Overview

CoChat Summary

TL;DR

The paper characterizes partial discharge (PD) and dielectric lifetime of Kapton-insulated copper foil medium-frequency transformer windings under high-*dv/dt* PWM for MV solid-state transformer applications. It finds PD inception/extinction depends on PWM frequency below about 1 kHz but not on the tested *dv/dt*, while insulation lifetime decreases with both switching frequency and *dv/dt*, yielding lifetime models.

Key findings

  • PDIV and PDEV were about 18% higher for PWM frequencies less than 1 kHz; at 10 kHz and above, PDIV was 25% lower than at 100 Hz and showed negligible dependence on PWM frequency beyond 10 kHz. PDEV can be up to 35% below PDIV.
  • PD characteristics were independent of the two tested *dv/dt* cases, 30 V/ns and 60 V/ns; no variation in measured PDIV/PDEV was observed between them.
  • Dielectric breakdown time was inversely proportional to PWM frequency, and faster switching speeds negatively impacted lifetime. The frequency-model exponent was *k* = 1.25 for 30 V/ns and *k* = 1.4 for 60 V/ns; the extended lifetime model was within 17% of experimental data, with highest deviation at 30 kHz.
  • FEA showed 4×–5× electric field enhancement along the lateral winding edges and about 2× field enhancement between copper, adhesive, and Kapton, creating favorable PD conditions.

Methods

  • Experimental study on foil-type MF transformer winding samples: one primary and one secondary layer of 2 mil copper foil insulated with 3M 1093 Kapton (about 1 mil polyimide plus 1 mil silicone adhesive), held in a custom G-10 setup maintaining transformer geometry.
  • A half-bridge inverter using 3.3 kV SiC MOSFETs generated unipolar PWM up to 2 kV dc-link, frequencies from 10 Hz to 50 kHz, and *dv/dt* of 30 or 60 V/ns. PD was detected nonintrusively with a photomultiplier tube inside a Faraday cage, validated against a coupling-capacitor PD detector at 60 Hz.
  • PDIV/PDEV were measured across frequency and *dv/dt* test cases; accelerated dielectric breakdown tests were then performed at 2 kV PWM until breakdown, and lifetime models were derived by curve fitting.

Limitations

  • The paper states that the effect of peak PWM voltage was not considered because experimental results could not be obtained above 2 kV dc-link due to the 3.3 kV device used in the PWM source.
  • The paper states that PDIV and PDEV were measured without considering voltage ringing, although ringing can be limited by design; future work is targeted at including voltage stress, ambient conditions, and winding-to-core insulation.
  • Evident from the text: the study is limited to one insulation material/geometry (Kapton-insulated copper foil, separate winding structure), two *dv/dt* cases, and hand-made samples; the paper notes that breakdown energy would increase when the transformer winding is loaded with current.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

Crossref · 10.1109/tie.2022.3174243

Cites

21 of 21 references verified0 citation errors · 0 not checkable

Statistics

Nothing to recompute.

Figures

Fig. 1 SST architecture with two-level PWM voltage.
Fig. 1 SST architecture with two-level PWM voltage.From the PDF
Fig. 2 Foil-type MF transformer construction.
Fig. 2 Foil-type MF transformer construction.From the PDF
Fig. 3 FEA simulation results of the anterior winding edge with one layer of Kapton insulation.
Fig. 3 FEA simulation results of the anterior winding edge with one layer of Kapton insulation.From the PDF
Fig. 4 (a) Schematic of the developed system to characterize PDs and lifetime of foil-type MF transformer. (b) PWM source containing SiC half-bridge, input dc-link capacitor, and optically coupled gate drivers. (c) Transformer winding test setup built with fiberglass G-10 material. (d) Photograph of PD characterization test setup inside Faraday cage.
Fig. 4 (a) Schematic of the developed system to characterize PDs and lifetime of foil-type MF transformer. (b) PWM source containing SiC half-bridge, input dc-link capacitor, and optically coupled gate drivers. (c) Transformer winding test setup built with fiberglass G-10 material. (d) Photograph of PD characterization test setup inside Faraday cage.From the PDF
Fig. 5 PDIV measurement results with dv/dt = 30 V/ns at: (a) 10 kHz PWM frequency and (b) 50 kHz PWM frequency.
Fig. 5 PDIV measurement results with dv/dt = 30 V/ns at: (a) 10 kHz PWM frequency and (b) 50 kHz PWM frequency.From the PDF
Fig. 6 PDIV and PDEV as a function of PWM frequency with dv/dt = 30 V/ns.
Fig. 6 PDIV and PDEV as a function of PWM frequency with dv/dt = 30 V/ns.From the PDF
Fig. 7 Dielectric BD test waveforms with dv/dt = 60 V/ns. (a) 10 kHz PWM frequency. (b) 50 kHz PWM frequency.
Fig. 7 Dielectric BD test waveforms with dv/dt = 60 V/ns. (a) 10 kHz PWM frequency. (b) 50 kHz PWM frequency.From the PDF
Fig. 8 BD test results for varying PWM frequency and dv/dt .
Fig. 8 BD test results for varying PWM frequency and dv/dt .From the PDF
Fig. 9 Experimental lifetime test results at dv/dt = 30 V/ns (magenta bars); experimental lifetime test results at dv/dt = 60 V/ns (blue bars); extrapolated lifetime test at dv/dt = 30 V/ns from model (dotted red); extrapolated lifetime test at dv/dt = 60 V/ns from model (dotted green).
Fig. 9 Experimental lifetime test results at dv/dt = 30 V/ns (magenta bars); experimental lifetime test results at dv/dt = 60 V/ns (blue bars); extrapolated lifetime test at dv/dt = 30 V/ns from model (dotted red); extrapolated lifetime test at dv/dt = 60 V/ns from model (dotted green).From the PDF
Image 10
From the PDF
Image 11
From the PDF
Image 12
From the PDF
Image 13
From the PDF

Verification

Claims the paper makes

3 Valid · 3 Not valid · 14 Not checked · 82 Own results and interpretations

37 more claims

Create a free account to see all 102 claims and to verify the 2 references still open.

See all claims — free account
  • It may state two separate claims as one. 42
  • Probably not a substantial claim. 36

Create a free account to see these claims.

Self-check

Percentages, sums and reported differences re-computed from the paper’s own numbers.

Each contradiction between two passages listed here was confirmed by an independent check.

1 of 1

Citations

Cites

Show all 20 references

Research works printed but not linked: 1

  1. 2015, Amendment 1—High-Voltage Test Techniques—Partial Discharge Measurements

Cited by

See all 79

Metadata

Authors
Agarwal, R., Li, H., Guo, Z., & Cheetham, P.
Affiliations
Florida State University (US)
Venue
IEEE Transactions on Industrial Electronics
Published
2023-04
Volume
70
Issue
4
Pages
3857-3866
ISSN
  • 0278-0046 (ISSN-L)
  • 1557-9948
OpenAlex
W4285298339
Cited by
79
References
20
Citations by year
2026: 24 · 2025: 25 · 2024: 20 · 2023: 10
FWCI
3.75
Type
journal article
Language
en
Open access
Locations
IEEE Transactions on Industrial Electronics (publishedVersion, cc-by)
Topics
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › High voltage insulation and dielectric phenomena
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Advanced DC-DC Converters
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Power Transformer Diagnostics and Insulation
Keywords
partial discharge, medium frequency transformer, solid-state transformer, pulse width modulation, optical sensors, phase-shift modulation, dielectric aging, electric field enhancement

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

The claim verdicts this report counts are experimental: their accuracy is not yet measured.

A language model drew the claims from the paper on 2026-10-10, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).

A second model labelled each claim on 2026-10-10 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

How to cite

Cite CoChat for the checks on this page, and the paper for its own findings.

This page
CoChat. (2026). Citation check: The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications. https://app.cochat.ai/papers/10.1109/tie.2022.3174243
The paper
Agarwal, R., Li, H., Guo, Z., & Cheetham, P. (2023). The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications. IEEE Transactions on Industrial Electronics. https://doi.org/10.1109/tie.2022.3174243

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.