The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications
Open accessAbstract
The medium-frequency (MF) transformer in a phase-shift modulated dc solid state transformer (SST) is prone to partial discharge (PD) that impacts the system reliability and lifetime. Tightly packed MF transformer windings carrying pulsewidth modulation (PWM) voltages create favorable conditions for PD inception due to proximity between adjacent winding conductors and electric field enhancement because of spiral geometry. A peak potential condition is created between the adjacent posterior conductors of the primary and secondary windings as a result of phase-shifted modulation. This along with fast alternating electric fields incepts PD at lower than expected operating voltages. Early inception of PD leads to premature transformer failure leading to unanticipated dc SST down-time. The effects of PWM voltages containing highdv/dtswitching transients on PD and lifetime characteristics of MF transformer in a dc SST are not yet understood, which is investigated in this article. A nonintrusive PD detection strategy for MF PWM ac voltage is presented using high-speed optical sensors. PD characterization is performed on Kapton polyimide insulated copper foil windings for a foil-type MF transformer. Winding samples are stress tested with steady state PWM voltages up to 2 kV and frequencies up to 50 kHz with highdv/dtup to 60 V/ns generated by a half-bridge inverter using 3.3 kV SiC devices while maintaining the transformer's geometric profile. Accelerated dielectric lifetime characterization is also performed and novel lifetime prediction models are derived based on the acquired results containing both frequency anddv/dtdependent variables.
Overview
CoChat Summary
TL;DR
The paper characterizes partial discharge (PD) and dielectric lifetime of Kapton-insulated copper foil medium-frequency transformer windings under high-*dv/dt* PWM for MV solid-state transformer applications. It finds PD inception/extinction depends on PWM frequency below about 1 kHz but not on the tested *dv/dt*, while insulation lifetime decreases with both switching frequency and *dv/dt*, yielding lifetime models.
Key findings
- PDIV and PDEV were about 18% higher for PWM frequencies less than 1 kHz; at 10 kHz and above, PDIV was 25% lower than at 100 Hz and showed negligible dependence on PWM frequency beyond 10 kHz. PDEV can be up to 35% below PDIV.
- PD characteristics were independent of the two tested *dv/dt* cases, 30 V/ns and 60 V/ns; no variation in measured PDIV/PDEV was observed between them.
- Dielectric breakdown time was inversely proportional to PWM frequency, and faster switching speeds negatively impacted lifetime. The frequency-model exponent was *k* = 1.25 for 30 V/ns and *k* = 1.4 for 60 V/ns; the extended lifetime model was within 17% of experimental data, with highest deviation at 30 kHz.
- FEA showed 4×–5× electric field enhancement along the lateral winding edges and about 2× field enhancement between copper, adhesive, and Kapton, creating favorable PD conditions.
Methods
- Experimental study on foil-type MF transformer winding samples: one primary and one secondary layer of 2 mil copper foil insulated with 3M 1093 Kapton (about 1 mil polyimide plus 1 mil silicone adhesive), held in a custom G-10 setup maintaining transformer geometry.
- A half-bridge inverter using 3.3 kV SiC MOSFETs generated unipolar PWM up to 2 kV dc-link, frequencies from 10 Hz to 50 kHz, and *dv/dt* of 30 or 60 V/ns. PD was detected nonintrusively with a photomultiplier tube inside a Faraday cage, validated against a coupling-capacitor PD detector at 60 Hz.
- PDIV/PDEV were measured across frequency and *dv/dt* test cases; accelerated dielectric breakdown tests were then performed at 2 kV PWM until breakdown, and lifetime models were derived by curve fitting.
Limitations
- The paper states that the effect of peak PWM voltage was not considered because experimental results could not be obtained above 2 kV dc-link due to the 3.3 kV device used in the PWM source.
- The paper states that PDIV and PDEV were measured without considering voltage ringing, although ringing can be limited by design; future work is targeted at including voltage stress, ambient conditions, and winding-to-core insulation.
- Evident from the text: the study is limited to one insulation material/geometry (Kapton-insulated copper foil, separate winding structure), two *dv/dt* cases, and hand-made samples; the paper notes that breakdown energy would increase when the transformer winding is loaded with current.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Figures













Verification
Claims the paper makes
3 Valid · 3 Not valid · 14 Not checked · 82 Own results and interpretations
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The test results for 30 V/ns show slightly better dielectric BD endurance than the faster 60 V/ns case.”
plainstates an association- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“PDIV and PDEVvalues were about 18% higher for PWM frequencies less than 1 kHz.”
plainstates an association- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The BD time is significantly shorter for 50 kHz ac frequency as compared to 10 kHz ac.”
boostedstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The simulation also demonstrates the edge effect predominantly enhancing the electric field at the filleted edge of the winding.”
boostedstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The zoom-in simulation results in Fig. 3 show 4 × -5 × electric field enhancements along the entire lateral edge of the primary and secondary windings.”
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
37 more claims
Create a free account to see all 102 claims and to verify the 2 references still open.
- It may state two separate claims as one. 42
- Probably not a substantial claim. 36
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ III. TRANSFORMER PD CHARACTERIZATION WITH VARIABLE SWITCHING FREQUENCY AND HIGH DV/DT · p. 5
“Faraday cage is equipped with dedicated climate control equipment that maintains consistent ambient conditions of 22 °C and 28% relative humidity.”
§ III. TRANSFORMER PD CHARACTERIZATION WITH VARIABLE SWITCHING FREQUENCY AND HIGH DV/DT · p. 6
“All the tests were performed in climate controlled lab area with ambient temperature averaging to 25 ◦ C and at normal atmospheric pressure.”
Citations
Cites
Dispersion and Absorption in Dielectrics I. Alternating Current Characteristics
Cole, K. S., & Cole, R. H. (1941) · The Journal of Chemical Physics · doi:10.1063/1.1750906 · Cited by 10,152 · cited 1×
“This can be explained by Cole-Cole model [21] that describes the inverse relationship of dielectric permittivity with frequency.”
MethodKüchler, A. (2018) · doi:10.1007/978-3-642-11993-4 · Cited by 231
High-Frequency Transformer Design for Modular Power Conversion From Medium-Voltage AC to 400 VDC
Zhao, S., Li, Q., Lee, F. C., & Li, B. (2018) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2017.2774440 · Cited by 231 · cited 1×
“in [3] have designed a 500 kHz transformer with PTFE polymer based insulation that has been characterized up to 30 kV with short impulse voltage testing.”
MethodEffect of rise time on PD pulse features under repetitive square wave voltages
Wang, P. W., Cavallini, A., Montanari, G. C., et al. (2013) · IEEE Transactions on Dielectrics and Electrical Insulation · doi:10.1109/tdei.2013.6451364 · Cited by 150 · cited 1×
“On the other hand, the non-intrusive methods include optical detection using Photo Multiplier Tube (PMT) [8], electromagnetic detection using ultra high frequency (UHF) antenna [18] as well as acoustic & electrochemical detection using ultrasound and ozone sensors.”
MethodOkubo, H., Hayakawa, N., & Montanari, G. C. (2007) · IEEE Transactions on Dielectrics and Electrical Insulation · doi:10.1109/tdei.2007.4401236 · Cited by 116 · cited 1×
“The partial discharges research for motor windings under actual PWM excitation at greater than 60 Hz frequency has been reported in [6]–[9].”
BackgroundDesign and Optimization of a 200-kW Medium-Frequency Transformer for Medium-Voltage SiC PV Inverters
Guo, Z., Yu, R., Xu, W., Feng, X., & Huang, A. Q. (2021) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2021.3059879 · Cited by 115
Self-citationLusuardi, L., Rumi, A., Cavallini, A., et al. (2021) · IEEE Access · doi:10.1109/access.2021.3058089 · Cited by 99
Fabiani, D., Montanari, G. C., & Contin, A. (2002) · ICSD'01. Proceedings of the 20001 IEEE 7th International Conference on Solid Dielectrics (Cat. No.01CH37117) · doi:10.1109/icsd.2001.955625 · Cited by 98 · cited 2×
“Survey of literature suggests that degradation of dielectric material is affected by PD activity and the life expectancy is substantially reduced in the presence of PD [10].”
BackgroundResultBaek, S., Wang, G., & Bhattacharya, S. (2010) · Annual Conference of the IEEE Industrial Electronics Society (IECON) · doi:10.1109/iecon.2010.5674991 · Cited by 76 · cited 1×
“Researches in [1], [2] have designed MF frequency transformers for inductor tank based MV dc SST with PWM frequency from 3 kHz to 20 kHz.”
BackgroundHigh frequency transformer design for modular power conversion from medium voltage AC to 400V DC
Zhao, S., Li, Q., & Lee, F. C. (2017) · Conference proceedings/Conference proceedings - IEEE Applied Power Electronics Conference and Exposition · doi:10.1109/apec.2017.7931108 · Cited by 61
Research works printed but not linked: 1
- 2015, Amendment 1—High-Voltage Test Techniques—Partial Discharge Measurements
Cited by
Li, Z., Hsieh, E., Li, Q., & Lee, F. C. (2023) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2023.3279030 · Cited by 111
“The dry-type transformer potted with epoxy is the mainstream solution for SST applications to handle MV [24], [25], [26], [27], [28], [29], [30], [31], [32], [33], [34].”
BackgroundMethodReview of Various Sensor Technologies in Monitoring the Condition of Power Transformers
Asl, M. B., Fofana, I., & Meghnefi, F. (2024) · Energies · doi:10.3390/en17143533 · Cited by 50
Hygrothermal aging mechanism of epoxy composites used for medium-frequency transformers
Luo, Z., Wang, L., Zhao, B., et al. (2024) · Polymer Degradation and Stability · doi:10.1016/j.polymdegradstab.2024.110913 · Cited by 27
Self-citationMotor Winding Insulation Degradation Under Repetitive Voltage Pulses
Yang, M., & Phung, B. T. (2024) · IEEE Access · doi:10.1109/access.2024.3406490 · Cited by 28
“How the switching frequency will impact the PDIV and PDEV of transformer windings is studied in [39].”
BackgroundWang, H., Xiao, G., Wang, L., Dong, X., & Ma, Z. (2025) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2024.3523746 · Cited by 18
“WhenthephenomenonofPDoccurs,itisaccompanied by electrical signals [8], [9], optical signals [7], mechanical vibration [10], and thermal radiation.”
Metadata
- Authors
- Agarwal, R., Li, H., Guo, Z., & Cheetham, P.
- Affiliations
- Florida State University (US)
- Venue
- IEEE Transactions on Industrial Electronics
- Published
- 2023-04
- Volume
- 70
- Issue
- 4
- Pages
- 3857-3866
- ISSN
- 0278-0046 (ISSN-L)
- 1557-9948
- OpenAlex
- W4285298339
- Semantic Scholar
- 33f47aa245ed1d2077566c46afca1b5079a8dea6
- Cited by
- 79
- References
- 20
- Citations by year
- 2026: 24 · 2025: 25 · 2024: 20 · 2023: 10
- FWCI
- 3.75
- Type
- journal article
- Language
- en
- Open access
- hybrid
- doi.org
- Locations
- IEEE Transactions on Industrial Electronics (publishedVersion, cc-by)
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › High voltage insulation and dielectric phenomena
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Advanced DC-DC Converters
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Power Transformer Diagnostics and Insulation
- Keywords
- partial discharge, medium frequency transformer, solid-state transformer, pulse width modulation, optical sensors, phase-shift modulation, dielectric aging, electric field enhancement
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
The claim verdicts this report counts are experimental: their accuracy is not yet measured.
A language model drew the claims from the paper on 2026-10-10, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-10 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications. https://app.cochat.ai/papers/10.1109/tie.2022.3174243
- The paper
- Agarwal, R., Li, H., Guo, Z., & Cheetham, P. (2023). The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications. IEEE Transactions on Industrial Electronics. https://doi.org/10.1109/tie.2022.3174243
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.