Design and Optimization of a 200-kW Medium-Frequency Transformer for Medium-Voltage SiC PV Inverters
Open accessAbstract
This article presents a design and optimization methodology for a 200-kW medium-frequency transformer (MFT) based on low-loss magnetic core (FINEMET FT-3TL). The proposed optimal design methodology consists of predesign, preliminary design, and optimal design. In the preliminary design, the parallel-concentric winding structure is selected to increase the current carrying capability and reduce the leakage inductance. Based on the parallel-concentric winding concept, a novel cooing and insulation structure with 3-D printed bobbins are proposed. The optimal designed MFT prototype achieves a power density higher than 19.23 kW/L. The electrical insulation system is tested at 12 kV ac peak voltage. In addition, the partial discharge (PD) test is conducted at 7.5 kV ac peak voltage to ensure the PD-free design. The high-frequency bipolar pulsewidth modulation voltage insulation (PD) test is the first time applied in MFT design and test process. Finally, the transformer is applied in a dual-active-bridge (DAB) converter with 200 kW rated power. The peak efficiency of the DAB converter is 99.53%, and the efficiency at 200 kW is 98.85%. The peak efficiency of MFT is 99.844%, and the efficiency at 200 kW is 99.842%.
Overview
CoChat Summary
TL;DR
This paper presents a three-stage optimal design methodology for a 200-kW, 15-kHz medium-frequency transformer (MFT) using FINEMET® FT-3TL nanocrystalline cores and a parallel-concentric winding structure. The prototype achieves >19.23 kW/L power density, PD-free operation up to 5.3 kV RMS/7.5 kV peak, and 99.842% MFT efficiency at 200 kW in a 200-kW DAB converter.
Key findings
- The parallel-concentric winding structure gave the lowest measured leakage inductance among compared structures: 2.6 µH and a leakage-to-magnetizing inductance ratio of 0.023%; the final prototype reported 5.36 µH / 21.67 mH (0.0247%).
- The optimized MFT prototype achieved a power density higher than 19.23 kW/L, with insulation tested at 12 kV AC peak and partial discharge (PD) testing at 7.5 kV AC peak; measured PDIV was about 5.3 kV RMS/7.5 kV peak, with PD smaller than 50 pC and PD rate much less than 1 pulse/cycle.
- In the 200-kW DAB converter, the peak DAB efficiency was 99.53% at 50 kW and 98.85% at 200 kW; the MFT peak efficiency was 99.844% at around 180 kW and 99.842% at 200 kW.
- At 200 kW, measured maximum core surface temperature rise was about 25 °C and winding temperature rise was 23 °C; the paper states MFT core temperature rise at 200 kW is lower than 30 °C.
Methods
- Design and optimization methodology with three stages: predesign, preliminary design, and optimal design; it selects magnetic core material/dimensions, Litz wire, insulation materials, and winding structure, then sweeps free parameters such as switching frequency, turns number, and bobbin dimensions.
- Core loss evaluation compared OSE, MSE, GSE, and IGSE models, with IGSE selected; winding loss used Dowell’s model and FFT-based harmonic summation; thermal design used a detailed steady-state thermal network and fluid/thermal simulation.
- Experimental verification used a 200-kW DAB converter with 1700-V SiC MOSFET modules, 1300-V input, and 15-kHz operation; PD testing was based on IEC 60270, and DAB efficiency was measured with a HIOKI PW6001 power analyzer, while MFT efficiency was calculated from experimental core and winding loss information.
Limitations
- The paper does not include an explicit limitations section.
- Evident from the text: although high-frequency bipolar PWM insulation/PD testing is claimed as first applied in MFT design and test, the developed MFT’s PD detection was performed with a 60-Hz sine wave because no well-established standard method exists for reliable PD measurement under PWM excitations.
- Evident from the text: MFT efficiency is reported as calculation efficiency based on experimental core and winding losses, rather than as a directly measured transformer efficiency.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
1 Valid · 7 Not valid · 11 Not checked · 79 Own results and interpretations
The cited sources support only part of this claim — read each source’s verdict below.
In the paper
“The selected working frequency of the MFT is 15kHz which is based on the efficiency and dimension optimization of the whole DAB converter system[20-21].”
What the sources say
- Partly supportedcites [20] [20] W. Xu et al., "Hardware Design and Demonstration of a 100kW, 99% Efficiency Dual Active Half Bridge Converter Based on 1700V SiC Power MOSFET," 2020 IEEE Applied Power Electronics Conference and Exposition (APEC), New Orleans, LA, USA, 2020, pp. 1367-1373, doi: 10.1109/APEC39645.2020.9124401. - sourceExperimental — accuracy not yet measured
Table IV lists 15–50 kHz as the converter’s switching-frequency range, so 15 kHz is included. But the paper describes a variable-frequency converter (Conclusions) and does not say that 15 kHz was selected through an efficiency-and-dimension optimization of the whole system. (LLM, conf=0.85)
- Partly supportedcites [21] [21] W. Xu, R. y. Yu, Z. Guo and A. Q. Huang, "Design of 1500V/200kW 99.6% Efficiency Dual Active Bridge Converters Based on 1700V SiC Power MOSFET Module," 2020 IEEE Energy Conversion Congress and Exposition (ECCE), Detroit, MI, USA, 2020, pp. 6000-6007, doi: 10.1109/ECCE44975.2020.9235903. - sourceExperimental — accuracy not yet measured
The Experiment Results section (page not available in our copy) states that the DAB converter’s switching frequency was fixed at 15 kHz. It does not say that 15 kHz was selected through efficiency-and-dimension optimization of the whole converter, or explicitly identify it as an optimized MFT frequency. (LLM, conf=0.87)
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Partly supported
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The MFT efficiency is 99.842%, and the temperature rise is lower than 30 °C at 200 kW.”
plainSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“For the parallel-concentric winding structure, the inner layer winding always has higher temperature because the inner layer is surrounded by outer layer winding as an external heat source.”
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The optimal designed MFT prototype achieves a power density higher than 19.23 kW/L.”
- Also stated in: § I. INTRODUCTION · p. 2 · plain
“At this power level, the calculated power density is 19.23 kW/L.”
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Also stated in: § I. INTRODUCTION · p. 2 · plain
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“Besides, the parallel-concentric winding structure also improves the window area utilization factor.”
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
46 more claims
Create a free account to see all 98 claims and every source verdict.
- Probably not a substantial claim. 26
- It may state two separate claims as one. 30
- The quote only partly states this claim. 1
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
The source backs part of the claim, not all of it — or backs it for a different population, condition or comparison.
In the citing paper
“Separate winding structure may suffer from higher leakage inductance due to lower magnetic coupling as compared to concentric or interleaved winding structures [4]; the separate structure however exhibits the best interwinding insulation due to natural separation between the primary and secondary sides, often aided by a small air gap.”
From The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications (2023) · cites this paper as [4]
Experimental — accuracy not yet measuredThe cited source says what the claim attributes to it.
In the citing paper
“Guo et al. developed a 200-kW, 15-kHz dual active bridge SST MF transformer in [4] with PD characterization up to 7.5 kV peak.”
The cited source says what the claim attributes to it.
In the citing paper
“The PD test is performed at 60 Hz sine ac voltage bearing different properties compared to PWM voltage.”
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ I. INTRODUCTION · p. 1
“These designs have power rating exceeding 50 kW”
§ I. INTRODUCTION · p. 2
“| CUT 2016 [11] | 50 | 5”
Citations
Cites
Effects of eddy currents in transformer windings
Dowell, P. L. (1966) · Proceedings of the Institution of Electrical Engineers · doi:10.1049/piee.1966.0236 · Cited by 1,438
Transformer and Inductor Design Handbook
McLyman, C. W. T. (2004) · CRC Press eBooks · doi:10.1201/9780203913598 · Cited by 1,369
Venkatachalam, K., Sullivan, C. R., Abdallah, T., & Tacca, H. (2003) · 2002 IEEE Workshop on Computers in Power Electronics, 2002. Proceedings. · doi:10.1109/cipe.2002.1196712 · Cited by 1,145
Calculation of losses in ferro- and ferrimagnetic materials based on the modified Steinmetz equation
Reinert, J., Brockmeyer, A., & De Doncker, R. W. A. A. (2001) · IEEE Transactions on Industry Applications · doi:10.1109/28.936396 · Cited by 704
Voltage and Power Balance Control for a Cascaded H-Bridge Converter-Based Solid-State Transformer
Zhao, T., Wang, G., Bhattacharya, S., & Huang, A. Q. (2013) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2012.2216549 · Cited by 642
Self-citationImproved calculation of core loss with nonsinusoidal waveforms
Li, J., Abdallah, T., & Sullivan, C. R. (2002) · Conference Record of the 2001 IEEE Industry Applications Conference. 36th IAS Annual Meeting (Cat. No.01CH37248) · doi:10.1109/ias.2001.955931 · Cited by 531
Power Electronic Traction Transformer—Medium Voltage Prototype
Zhao, C., Dujic, D., Mester, A., Steinke, J. K., Weiss, M., Lewdeni-Schmid, S., Chaudhuri, T., & Stefanutti, P. (2014) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2013.2278960 · Cited by 478
Krismer, F., & Kolar, J. W. (2010) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2009.2025284 · Cited by 470
Calculation of losses in ferro- and ferrimagnetic materials based on the modified Steinmetz equation
Reinert, J., Brockmeyer, A., & De Doncker, R. W. (2003) · Conference Record of the 1999 IEEE Industry Applications Conference. Thirty-Forth IAS Annual Meeting (Cat. No.99CH36370) · doi:10.1109/ias.1999.806023 · Cited by 409
Optimizing the AC resistance of multilayer transformer windings with arbitrary current waveforms
Hurley, W. G., Gath, E., & Breslin, J. G. (2000) · IEEE Transactions on Power Electronics · doi:10.1109/63.838110 · Cited by 368
Research works printed but not linked: 5
- 10.1109/ICPE · doi:10.1109/icpe
- du, 0, High-voltage high frequency transformer design for a 7.2 kv to 120 v/240 v 20 kva solid state transformer, Proc 36th Annu Conf IEEE Ind Electron Soc, 493
- 10.1109/TPEL.2006.886608 · DOI · Paper page
- 2000, IEC 60270 International Standard
- 2015, General Requirements for Dry-Type Distribution and Power Transformers
Cited by
Li, Z., Hsieh, E., Li, Q., & Lee, F. C. (2023) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2023.3279030 · Cited by 111
“device loss, and thermal performance, are frequently employed to optimize the HFT and related converters [20], [21], [32], [33].”
BackgroundMethodInfluentialAgarwal, R., Li, H., Guo, Z., & Cheetham, P. (2023) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2022.3174243 · Cited by 79
Self-citationHardware Design of a 13.8-kV/3-MVA PV Plus Storage Solid-State Transformer (PVS-SST)
Xu, W., Guo, Z., Vetrivelan, A., Yu, R., & Huang, A. Q. (2021) · IEEE Journal of Emerging and Selected Topics in Power Electronics · doi:10.1109/jestpe.2021.3082033 · Cited by 78
Self-citationCharacterization of Partial Discharges in High-Frequency Transformer Under PWM Pulses
Guo, Z., Huang, A. Q., Hebner, R., Montanari, G. C., & Feng, X. (2022) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2022.3169747 · Cited by 76
Self-citationCzyż, P., Guillod, T., Zhang, D., Krismer, F., Huber, J., Färber, R., Franck, C. M., & Kolar, J. W. (2021) · IEEE Journal of Emerging and Selected Topics in Power Electronics · doi:10.1109/jestpe.2021.3123793 · Cited by 68
Metadata
- Authors
- Guo, Z., Yu, R., Xu, W., Feng, X., & Huang, A. Q.
- Affiliations
- The University of Texas at Austin (US)
- Venue
- IEEE Transactions on Power Electronics
- Published
- 2021-09
- Volume
- 36
- Issue
- 9
- Pages
- 10548-10560
- ISSN
- 0885-8993 (ISSN-L)
- 1941-0107
- OpenAlex
- W3131410230
- Cited by
- 115
- References
- 41
- Citations by year
- 2026: 20 · 2025: 21 · 2024: 23 · 2023: 22 · 2022: 20 · 2021: 9
- FWCI
- 5.43
- Type
- journal article
- Language
- en
- Open access
- green
- www.osti.gov
- Licence
- Locations
- IEEE Transactions on Power Electronics (publishedVersion)
- OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) (submittedVersion)
- Funders
- U.S. Department of Energy
- Office of Energy Efficiency and Renewable Energy
- Solar Energy Technologies Office (EE0008348)
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Advanced DC-DC Converters
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Multilevel Inverters and Converters
- Physical Sciences › Materials Science › Electronic, Optical and Magnetic Materials › Magnetic Properties and Applications
- Keywords
- medium frequency transformer, leakage inductance reduction, partial discharge testing, dual active bridge converter, transformer design optimization, power density
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
The claim verdicts this report counts are experimental: their accuracy is not yet measured.
A language model drew the claims from the paper on 2026-10-10, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-10 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Cited sources are checked with a language model’s help (gpt-6-sol).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: Design and Optimization of a 200-kW Medium-Frequency Transformer for Medium-Voltage SiC PV Inverters. https://app.cochat.ai/papers/10.1109/tpel.2021.3059879
- The paper
- Guo, Z., Yu, R., Xu, W., Feng, X., & Huang, A. Q. (2021). Design and Optimization of a 200-kW Medium-Frequency Transformer for Medium-Voltage SiC PV Inverters. IEEE Transactions on Power Electronics. https://doi.org/10.1109/tpel.2021.3059879
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.