Renewable and cooling aware workload management for sustainable data centers
The DOI matches its Crossref record; 26 of the 26 references it cites were found in a registry or an index.
Abstract
Recently, the demand for data center computing has surged, increasing the total energy footprint of data centers worldwide. Data centers typically comprise three subsystems: IT equipment provides services to customers; power infrastructure supports the IT and cooling equipment; and the cooling infrastructure removes heat generated by these subsystems. This work presents a novel approach to model the energy flows in a data center and optimize its operation. Traditionally, supply-side constraints such as energy or cooling availability were treated independently from IT workload management. This work reduces electricity cost and environmental impact using a holistic approach that integrates renewable supply, dynamic pricing, and cooling supply including chiller and outside air cooling, with IT workload planning to improve the overall sustainability of data center operations. Specifically, we first predict renewable energy as well as IT demand. Then we use these predictions to generate an IT workload management plan that schedules IT workload and allocates IT resources within a data center according to time varying power supply and cooling efficiency. We have implemented and evaluated our approach using traces from real data centers and production systems. The results demonstrate that our approach can reduce both the recurring power costs and the use of non-renewable energy by as much as 60% compared to existing techniques, while still meeting the Service Level Agreements.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Bertsekas, D. P. (1997) · Journal of the Operational Research Society · doi:10.1038/sj.jors.2600425 · Cited by 11,726
Holman, J. P. (1976) · Cited by 9,157
(2011) · SpringerReference · doi:10.1007/springerreference_57547 · Cited by 3,190
Weik, M. H. (2000) · Computer Science and Communications Dictionary · doi:10.1007/1-4020-0613-6_12436 · Cited by 2,570
Power provisioning for a warehouse-sized computer
Fan, X., Weber, W.-D., & Barroso, L. A. (2007) · Proceedings of the 34th annual international symposium on Computer architecture · doi:10.1145/1250662.1250665 · Cited by 1,797
Power management in energy harvesting sensor networks
Kansal, A., Hsu, J., Zahedi, S., & Srivastava, M. B. (2007) · ACM Transactions on Embedded Computing Systems · doi:10.1145/1274858.1274870 · Cited by 1,533
Vazirani, V. V. (2003) · Springer eBooks · doi:10.1007/978-3-662-04565-7 · Cited by 716
Making scheduling cool: temperature-aware workload placement in data centers
Moore, J., Chase, J., Ranganathan, P., & Sharma, R. K. (2005) · USENIX Annual Technical Conference · Cited by 651
No "power" struggles: coordinated multi-level power management for the data center
Raghavendra, R., Ranganathan, P., Talwar, V., Wang, Z., & Zhu, X. (2008) · Proceedings of the 13th international conference on Architectural support for programming languages and operating systems · doi:10.1145/1346281.1346289 · Cited by 619
Self-citationRao, L., Liu, X., Xie, L., & Liu, W. (2010) · 2010 Proceedings IEEE INFOCOM · doi:10.1109/infcom.2010.5461933 · Cited by 526
Predicting solar generation from weather forecasts using machine learning
Sharma, N., Sharma, P., Irwin, D., & Shenoy, P. (2011) · 2011 IEEE International Conference on Smart Grid Communications (SmartGridComm) · doi:10.1109/smartgridcomm.2011.6102379 · Cited by 467
Greening geographical load balancing
Liu, Z., Lin, M., Wierman, A., Low, S. H., & Andrew, L. L. H. (2011) · Proceedings of the ACM SIGMETRICS joint international conference on Measurement and modeling of computer systems · doi:10.1145/1993744.1993767 · Cited by 467
Self-citationOptimal power cost management using stored energy in data centers
Urgaonkar, R., Urgaonkar, B., Neely, M. J., & Sivasubramaniam, A. (2011) · ACM SIGMETRICS International Conference on Measurement and Modeling of Computer Systems (SIGMETRICS) · doi:10.1145/1993744.1993766 · Cited by 461
Optimal power allocation in server farms
Gandhi, A., Harchol-Balter, M., Das, R., & Lefurgy, C. (2009) · Proceedings of the eleventh international joint conference on Measurement and modeling of computer systems · doi:10.1145/1555349.1555368 · Cited by 457
Dynamic Right-Sizing for Power-Proportional Data Centers
Lin, M., Wierman, A., Andrew, & Thereska, E. (2013) · IEEE/ACM Transactions on Networking · doi:10.1109/tnet.2012.2226216 · Cited by 446
Self-citationDynamic right-sizing for power-proportional data centers
Lin, M., Wierman, A., Andrew, L. L. H., & Thereska, E. (2011) · 2011 Proceedings IEEE INFOCOM · doi:10.1109/infcom.2011.5934885 · Cited by 437
Self-citationOnline algorithms for geographical load balancing
Lin, M., Liu, Z., Wierman, A., & Andrew, L. L. H. (2012) · 2012 International Green Computing Conference (IGCC) · doi:10.1109/igcc.2012.6322266 · Cited by 290
Self-citationPrediction by Exponentially Weighted Moving Averages and Related Methods
Cox, D. R. (1961) · Journal of the Royal Statistical Society Series B: Statistical Methodology · doi:10.1111/j.2517-6161.1961.tb00424.x · Cited by 263
Power-Aware Speed Scaling in Processor Sharing Systems
Wierman, A., Andrew, L. L. H., & Tang, A. (2009) · IEEE Conference on Computer Communications (INFOCOM) · doi:10.1109/infcom.2009.5062123 · Cited by 262
Self-citationGeographical load balancing with renewables
Liu, Z., Lin, M., Wierman, A., Low, S. H., & Andrew, L. L. H. (2011) · ACM SIGMETRICS Performance Evaluation Review · doi:10.1145/2160803.2160862 · Cited by 221
Self-citationMinimizing data center cooling and server power costs
Pakbaznia, E., & Pedram, M. (2009) · Proceedings of the 2009 ACM/IEEE international symposium on Low power electronics and design · doi:10.1145/1594233.1594268 · Cited by 218
Dynamic Thermal Management of Air Cooled Data Centers
Bash, C. E., Patel, C. D., & Sharma, R. K. (2006) · I-THERM :/I-THERM - Intersociety Conference on Thermal Phenomena in Electronic Systems · doi:10.1109/itherm.2006.1645377 · Cited by 182
Self-citationCapping the brown energy consumption of Internet services at low cost
Le, K., Bianchini, R., Nguyen, T. D., Bilgir, O., & Martonosi, M. (2010) · International Conference on Green Computing · doi:10.1109/greencomp.2010.5598305 · Cited by 173
Optimality, fairness, and robustness in speed scaling designs
Andrew, L. L. H., Lin, M., & Wierman, A. (2010) · ACM SIGMETRICS International Conference on Measurement and Modeling of Computer Systems (SIGMETRICS) · doi:10.1145/1811039.1811044 · Cited by 120
Self-citationProfiling Sustainability of Data Centers
Gmach, D., Chen, Y., Shah, A. J., Rolia, J., Bash, C. E., Christian, T., & Sharma, R. K. (2010) · IEEE International Symposium on Sustainable Systems and Technology · doi:10.1109/issst.2010.5507750 · Cited by 48
Self-citationSierra: a power-proportional, distributed storage system
Thereska, E., Donnelly, A., & Narayanan, D. (2009) · Cited by 48
Cited by
Data Center Energy Consumption Modeling: A Survey
Dayarathna, M., Wen, Y., & Fan, R. (2016) · IEEE Communications Surveys & Tutorials · doi:10.1109/comst.2015.2481183 · Cited by 1,165
Habibi Khalaj, A., & Halgamuge, S. K. (2017) · Applied Energy · doi:10.1016/j.apenergy.2017.08.037 · Cited by 707
Resource Management in Clouds: Survey and Research Challenges
Jennings, B., & Stadler, R. (2015) · Journal of Network and Systems Management · doi:10.1007/s10922-014-9307-7 · Cited by 548
Zeng, D., Gu, L., Guo, S., Cheng, Z., & Yu, S. (2016) · IEEE Transactions on Computers · doi:10.1109/tc.2016.2536019 · Cited by 426
Huang, P., Copertaro, B., Zhang, X., Shen, J., Löfgren, I., Rönnelid, M., Fahlen, J., Andersson, D., & Svanfeldt, M. (2020) · Applied Energy · doi:10.1016/j.apenergy.2019.114109 · Cited by 414
Metadata
- Authors
- Liu, Z., Chen, Y., Bash, C., Wierman, A., Gmach, D., Wang, Z., Marwah, M., & Hyser, C.
- Venue
- Proceedings of the 12th ACM SIGMETRICS/PERFORMANCE joint international conference on Measurement and Modeling of Computer Systems
- Publisher
- ACM
- Published
- 2012-06-11
- Pages
- 175-186
- OpenAlex
- W2107128713
- Cited by
- 413
- References
- 26
- FWCI
- 40.68
- Type
- conference paper
- Language
- en
- Open access
- closed
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.