Impact of Data Sparsity on Machine Learning for Fault Detection in Power System Protection

Open access
Oelhaf, Julian, Kordowich, Georg, Kim, Changhun, Pérez-Toro, Paula Andrea, Maier, Andreas, Jäger, Johann, Bayer, Siming · 2025 · 2025 33rd European Signal Processing Conference (EUSIPCO)

The DOI matches its Crossref record; 16 of the 17 references it cites were found in a registry or an index; 2 of the 4 sources its claims cite were checked for support.

Abstract

ML has emerged as a powerful tool for power system protection, particularly for fault detection and fault line identification in transmission grids. However, ML model reliability depends on data quality and availability; data sparsity poses a challenge.

Overview

CoChat Summary

TL;DR

This paper proposes a framework to assess how data sparsity affects ML-based fault detection (FD) and fault line identification (FLI) in power system protection, using simulated “Double Line” grid data and a Random Forest model. FD remains robust under most sparsity scenarios, while FLI is highly sensitive to missing voltage measurements, Bus 2 failures, and long communication losses.

Key findings

  • FD was largely robust: baseline F1 was 0.998 ± 0.001; missing voltage changed performance by +0.02%, missing current by -0.16%, and reduced sampling to 400 Hz (50× reduction) had negligible effect. The abstract reports FD maintaining an F1-score of 0.999 ± 0.000 after 50× data reduction, but a 45 ms communication loss dropped FD F1 by 32.8% to 0.672.
  • FLI was more sensitive: missing voltage reduced F1 by 55.61% to 0.443 ± 0.008; Bus 2 failure reduced it by 9.73% to 0.900 ± 0.003; and a 45 ms communication loss reduced it by 68.6% to 0.314. Missing current (+0.04%) and reduced sampling had negligible impact.
  • Component failures affected FLI unevenly: Bus 3 failure caused a -2.85% drop and Bus 1 failure -0.28%, while FD was unaffected. Phase-specific data loss had negligible effect for both tasks.
  • The study ran 270 experiment combinations across five window lengths and multiple data sparsity scenarios; FD and FLI cannot be directly compared due to differing numbers of available window samples and task types.

Methods

  • Simulated “Double Line” topology in DIgSILENT PowerFactory: 3 buses, 4 transmission lines, 8 protection relays, 48 measurements per time step (three-phase current and voltage), 4,000 samples, 1 s at 20 kHz, focused on three-phase short circuits with domain randomization.
  • Preprocessing trimmed each sample to ±80 ms around fault start, slid time series with a 5 ms step, and evaluated window lengths of 10, 20, 30, 40, and 50 ms. FD was binary classification, FLI was four-class classification; a Random Forest classifier was used with 5-fold cross-validation, F1-score, and scikit-learn.
  • Sparsity scenarios included missing voltage/current, reduced sampling (10 kHz, 4 kHz, 2 kHz, 800 Hz, 400 Hz), component failures (Buses 1–3, PRs 1–8), phase-specific loss (A/B/C), and communication loss (5–45 ms in 5 ms steps).

Limitations

  • Stated: this is a proof of concept; it focuses only on three-phase short circuits in a single grid topology. Future work should extend the framework to various ML approaches, different grid topologies, additional fault types (e.g., two-phase, ground faults), load conditions, multiple fault scenarios, and noisy data.
  • Evident from the text: results rely on simulated PowerFactory data rather than real grid measurements; only one ML model (Random Forest) is evaluated; FD and FLI are not directly comparable due to differing window samples and task types; communication loss scenarios were only considered when the loss period was shorter than the window length; and detailed reduced temporal resolution results were omitted due to space constraints.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

Crossref · 10.23919/eusipco63237.2025.11226584

Cites

16 of 17 references verified1 citation errors · 0 not checkable

Statistics

Nothing to recompute.

Figures

Fig. 1 Schematic of the 'Double Line' grid topology. The diagram illustrates the transmission lines, PRs, and communication devices. Measurements are recorded at the PRs and transmitted to the substations at each bus. From there, the data is relayed to the control center for FD and FLI.
Fig. 1 Schematic of the 'Double Line' grid topology. The diagram illustrates the transmission lines, PRs, and communication devices. Measurements are recorded at the PRs and transmitted to the substations at each bus. From there, the data is relayed to the control center for FD and FLI.CC-BY · From the PDF
Fig. 2 Heatmap of the Fault Line Identification task F1-scores under cases of temporal communication loss.
Fig. 2 Heatmap of the Fault Line Identification task F1-scores under cases of temporal communication loss.CC-BY · From the PDF

Verification

Claims the paper makes

2 Valid · 0 Not valid · 2 Not checked · 40 Own results and interpretations

20 more claims

Create a free account to see all 44 claims and every source verdict.

See all claims — free account
  • It may state two separate claims as one. 15
  • The quote only partly states this claim. 1
  • Probably not a substantial claim. 6

Create a free account to see these claims.

Citations

Cites

Research works printed but not linked: 4

  1. B. für Wirtschaft und Klimaschutz, "Aktueller Stand des Netzausbaus ( Übertragungsnetz)," https://www.bmwk.de/Redaktion/DE/Downloads/ M-O/netzausbau-schreitet-voran.pdf? blob=publicationFile&v=17, 2024, accessed: 2025-03-11.
  2. I. E. Commission, "IEC 61850:2024 SER | IEC," May 2024. [Online]. Available: https://webstore.iec.ch/en/publication/6028
  3. M. Wang et al., "A Generic Data Generation Framework for Short Circuit Detection Training of Neural Networks," in PESS + PELSS 2022; Power and Energy Student Summit. Kassel, Germany: VDE, Nov. 2022, pp. 49-54. [Online]. Available: https: //ieeexplore.ieee.org/document/10104226
  4. R. Roeper and Mitlehner, Friedrich, Kurzschlußströme in Drehstromnet- zen, 6th ed. Publicis Corporate Publishing, 1984.

Cited by

See all 10

Metadata

Authors
Oelhaf, J., Kordowich, G., Kim, C., Pérez-Toro, P. A., Maier, A., Jäger, J., & Bayer, S.
Affiliations
  • Friedrich-Alexander-Universität Erlangen-Nürnberg (DE)
  • Institute of Electrical Energy Systems, Friedrich-Alexander-University Erlangen-Nuremberg,Erlangen,Germany
Venue
2025 33rd European Signal Processing Conference (EUSIPCO)
Publisher
IEEE
Published
2025-09-08
Pages
1997-2001
OpenAlex
W4417053512
Cited by
0
References
15
FWCI
0.00
Type
conference paper
Language
en
Open access
Locations
  • European Signal Processing Conference (EUSIPCO) (publishedVersion)
  • arXiv (Cornell University) (submittedVersion, cc-by)
  • arXiv (Cornell University) (cc-by)
Funders
Deutsche Forschungsgemeinschaft (535389056)
Topics
  • Physical Sciences › Engineering › Control and Systems Engineering › Power Systems Fault Detection
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Power System Optimization and Stability
  • Physical Sciences › Engineering › Electrical and Electronic Engineering › Electrical Fault Detection and Protection
Keywords
data sparsity, fault detection, fault line identification, power system protection, transmission networks, missing sensor data, communication breakdown, renewable energy integration, machine learning robustness, data quality, voltage measurement

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

The claim verdicts this report counts are experimental: their accuracy is not yet measured.

A language model drew the claims from the paper on 2026-10-12, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).

A second model labelled each claim on 2026-10-12 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Cited sources are checked with a language model’s help (gpt-6-sol).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.