Impact of Data Sparsity on Machine Learning for Fault Detection in Power System Protection
Open accessThe DOI matches its Crossref record; 16 of the 17 references it cites were found in a registry or an index; 2 of the 4 sources its claims cite were checked for support.
Abstract
ML has emerged as a powerful tool for power system protection, particularly for fault detection and fault line identification in transmission grids. However, ML model reliability depends on data quality and availability; data sparsity poses a challenge.
Overview
CoChat Summary
TL;DR
This paper proposes a framework to assess how data sparsity affects ML-based fault detection (FD) and fault line identification (FLI) in power system protection, using simulated “Double Line” grid data and a Random Forest model. FD remains robust under most sparsity scenarios, while FLI is highly sensitive to missing voltage measurements, Bus 2 failures, and long communication losses.
Key findings
- FD was largely robust: baseline F1 was 0.998 ± 0.001; missing voltage changed performance by +0.02%, missing current by -0.16%, and reduced sampling to 400 Hz (50× reduction) had negligible effect. The abstract reports FD maintaining an F1-score of 0.999 ± 0.000 after 50× data reduction, but a 45 ms communication loss dropped FD F1 by 32.8% to 0.672.
- FLI was more sensitive: missing voltage reduced F1 by 55.61% to 0.443 ± 0.008; Bus 2 failure reduced it by 9.73% to 0.900 ± 0.003; and a 45 ms communication loss reduced it by 68.6% to 0.314. Missing current (+0.04%) and reduced sampling had negligible impact.
- Component failures affected FLI unevenly: Bus 3 failure caused a -2.85% drop and Bus 1 failure -0.28%, while FD was unaffected. Phase-specific data loss had negligible effect for both tasks.
- The study ran 270 experiment combinations across five window lengths and multiple data sparsity scenarios; FD and FLI cannot be directly compared due to differing numbers of available window samples and task types.
Methods
- Simulated “Double Line” topology in DIgSILENT PowerFactory: 3 buses, 4 transmission lines, 8 protection relays, 48 measurements per time step (three-phase current and voltage), 4,000 samples, 1 s at 20 kHz, focused on three-phase short circuits with domain randomization.
- Preprocessing trimmed each sample to ±80 ms around fault start, slid time series with a 5 ms step, and evaluated window lengths of 10, 20, 30, 40, and 50 ms. FD was binary classification, FLI was four-class classification; a Random Forest classifier was used with 5-fold cross-validation, F1-score, and scikit-learn.
- Sparsity scenarios included missing voltage/current, reduced sampling (10 kHz, 4 kHz, 2 kHz, 800 Hz, 400 Hz), component failures (Buses 1–3, PRs 1–8), phase-specific loss (A/B/C), and communication loss (5–45 ms in 5 ms steps).
Limitations
- Stated: this is a proof of concept; it focuses only on three-phase short circuits in a single grid topology. Future work should extend the framework to various ML approaches, different grid topologies, additional fault types (e.g., two-phase, ground faults), load conditions, multiple fault scenarios, and noisy data.
- Evident from the text: results rely on simulated PowerFactory data rather than real grid measurements; only one ML model (Random Forest) is evaluated; FD and FLI are not directly comparable due to differing window samples and task types; communication loss scenarios were only considered when the loss period was shorter than the window length; and detailed reduced temporal resolution results were omitted due to space constraints.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Figures


Verification
Claims the paper makes
2 Valid · 0 Not valid · 2 Not checked · 40 Own results and interpretations
The cited sources support only part of this claim — read each source’s verdict below.
In the paper
“The Random Forest (RF) classifier is selected based on our comparative study [8], which demonstrated its favorable trade-off between performance and runtime.”
§ Impact of Data Sparsity on Machine Learning for Fault Detection in Power System Protection > C. Machine Learning Models for Fault Detection and Line Identification
What the sources say
- Partly supportedcites [8] J. Oelhaf et al., "A Systematic Evaluation of Machine Learning Methods for Fault Detection and Line Identification in Electrical Power Grids," in ICASSP 2025 -2025 IEEE International Conference on Acoustics, Speech and Signal Processing (ICASSP), 2025, pp. 1-5. sourceExperimental — accuracy not yet measured
The Experiments and Results section compares RF with other classifiers and lists it among the best performers. The Discussion also reports that RF is among the top-performing models, but identifies MLP, GB, and Stacking—not RF—as combining the highest scores with competitive runtimes. The paper therefore supports using the study to assess RF, but does not establish the claimed favorable performance–runtime trade-off for RF specifically. No page numbers are available in our copy. (LLM, conf=0.84)
boostedstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Partly supported
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“A 5 ms loss in the 10 ms window had less impact than a 25 ms loss in the 50 ms window, despite both being 50% of data loss.”
§ Impact of Data Sparsity on Machine Learning for Fault Detection in Power System Protection > IV. DISCUSSION
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“In contrast, for the FLI task, the model experienced a significant performance drop when V measurements were missing (-55.61%), while the removal of I measurements had a negligible impact (+0.04%).”
§ Impact of Data Sparsity on Machine Learning for Fault Detection in Power System Protection > Missing Voltage or Current Data:
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“However, Bus 1 failure caused a slight reduction of only -0.28% (see Tab. III).”
§ Impact of Data Sparsity on Machine Learning for Fault Detection in Power System Protection > Missing Voltage or Current Data:
plainstates a causeSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The largest change occurred in the FLI task at 400 Hz, reaching an F1-score of 0.998 (+0.09%).”
§ Impact of Data Sparsity on Machine Learning for Fault Detection in Power System Protection > Missing Voltage or Current Data:
plainstates an association- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
20 more claims
Create a free account to see all 44 claims and every source verdict.
- It may state two separate claims as one. 15
- The quote only partly states this claim. 1
- Probably not a substantial claim. 6
Citations
Cites
Scikit-learn: Machine Learning in Python
Pedregosa, F., Varoquaux, G., Gramfort, A., Michel, V., Thirion, B., Grisel, O., Blondel, M., Müller, A., Nothman, J., Louppe, G., et al. (2012) · arXiv · doi:10.48550/arxiv.1201.0490 · Cited by 71,016 · cited 1×
“Model implementation, training, cross-validation, and evaluation are carried out using scikit-learn [19].”
Scikit-learn: Machine Learning in Python
(2011) · Journal of Machine Learning Research · doi:10.5555/1953048.2078195 · Cited by 8,539
Sustainable Energy Transition for Renewable and Low Carbon Grid Electricity Generation and Supply
Kabeyi, M. J. B., & Olanrewaju, O. A. (2022) · Frontiers in Energy Research · doi:10.3389/fenrg.2021.743114 · Cited by 1,177 · cited 1×
“The growth of wind, solar, and hydroelec-tric generation, along with the increase in energy efficiency and demand-side management, presents new challenges for ensuring a secure, stable, and affordable electricity supply [1].”
Central Power Research Institute, Telukunta, V., Pradhan, J., Central Power Research Institute, Agrawal, A., Central Power Research Institute, Singh, M., Central Power Research Institute, Srivani, S. G., & R V College of Engineering (2017) · CSEE Journal of Power and Energy Systems · doi:10.17775/cseejpes.2017.00030 · Cited by 544 · cited 1×
“Traditional grid control mechanisms, designed for centralized generation, are increasingly insufficient to manage the variability and distributed nature of renewable energy sources [3].”
Electric Power Distribution Engineering
Gonen, T. (2015) · doi:10.1201/b16455 · Cited by 287
IEC 61850 based substation automation system: A survey
Aftab, M. A., Hussain, S. M. S., Ali, I., & Ustun, T. S. (2020) · International Journal of Electrical Power & Energy Systems · doi:10.1016/j.ijepes.2020.106008 · Cited by 206 · cited 1×
“These data streams originate from protection relays (PRs) and other monitoring systems, which transfer real-time information to centralized control centers for analysis and decision-making [4].”
Ultrafast Transmission Line Fault Detection Using a DWT-Based ANN
Abdullah, A. (2017) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2017.2774202 · Cited by 149
Najafzadeh, M., Pouladi, J., Daghigh, A., Beiza, J., & Abedinzadeh, T. (2024) · International Journal of Computational Intelligence Systems · doi:10.1007/s44196-024-00434-7 · Cited by 77 · cited 1×
“Many studies [11]–[13] on FD and FLI simulate data sampled at 20 kHz , which can often be unrealistic in practice.”
Elektrische Kraftwerke und Netze
Oeding, D., & Oswald, B. R. (2016) · Springer eBooks · doi:10.1007/978-3-662-52703-0 · Cited by 66
Faulted Line Identification and Localization in Power System using Machine Learning Techniques
(2019) · doi:10.1109/bigdata47090.2019.9006377 · Cited by 16 · cited 1×
“…this challenge, machine learning (ML) models have emerged as a promising solution for fault detection (FD) [6]–[8], fault line identification (FLI) [9], and protection coordination (PC) [10], enabling more accurate and adaptive fault management while efficiently handling large-scale grid data.”
Sustainable energy transition and optimization of grid electricity generation and supply
Kabeyi, M. J. B. (2024) · doi:10.51415/10321/5485 · Cited by 16
(2016) · doi:10.1016/j.pisc.2016.06.077 · Cited by 14 · cited 2×
“To address this challenge, machine learning (ML) models have emerged as a promising solution for fault detection (FD) [6]–[8], fault line identification (FLI) [9], and protection coordination (PC) [10], enabling more accurate and adaptive fault management while efficiently handling large-scale grid…”
Fault Detection and Classification in Smart Grid Using Machine Learning Approach
(2024) · doi:10.1109/areis62559.2024.10893627 · Cited by 13 · cited 1×
“Many studies [11]–[13] on FD and FLI simulate data sampled at 20 kHz , which can often be unrealistic in practice.”
Hybrid fuzzy evaluation algorithm for power system protection security assessment
Meyer, G. J., Lorz, T., Wehner, R., Jaeger, J., Dauer, M., & Krebs, R. (2020) · Electric Power Systems Research · doi:10.1016/j.epsr.2020.106555 · Cited by 13 · cited 1×
“To investigate the impact of data sparsity, we use a widely adopted topology in grid protection studies, as outlined in [14].”
Self-citationA hybrid Protection Scheme based on Deep Reinforcement Learning
(2022) · doi:10.1109/isgt-europe54678.2022.9960539 · Cited by 4 · cited 1×
“…this challenge, machine learning (ML) models have emerged as a promising solution for fault detection (FD) [6]–[8], fault line identification (FLI) [9], and protection coordination (PC) [10], enabling more accurate and adaptive fault management while efficiently handling large-scale grid data.”
Self-citationOelhaf, J., Kordowich, G., Pérez-Toro, P. A., Arias-Vergara, T., Maier, A., Jäger, J., & Bayer, S. (2025) · ICASSP 2025 - 2025 IEEE International Conference on Acoustics, Speech and Signal Processing (ICASSP) · doi:10.1109/icassp49660.2025.10890544 · Cited by 2 · cited 4×
“For further details on the parameter randomization process, refer to our previous study [8].”
InfluentialSelf-citation
Research works printed but not linked: 4
- B. für Wirtschaft und Klimaschutz, "Aktueller Stand des Netzausbaus ( Übertragungsnetz)," https://www.bmwk.de/Redaktion/DE/Downloads/ M-O/netzausbau-schreitet-voran.pdf? blob=publicationFile&v=17, 2024, accessed: 2025-03-11.
- I. E. Commission, "IEC 61850:2024 SER | IEC," May 2024. [Online]. Available: https://webstore.iec.ch/en/publication/6028
- M. Wang et al., "A Generic Data Generation Framework for Short Circuit Detection Training of Neural Networks," in PESS + PELSS 2022; Power and Energy Student Summit. Kassel, Germany: VDE, Nov. 2022, pp. 49-54. [Online]. Available: https: //ieeexplore.ieee.org/document/10104226
- R. Roeper and Mitlehner, Friedrich, Kurzschlußströme in Drehstromnet- zen, 6th ed. Publicis Corporate Publishing, 1984.
Cited by
Oelhaf, J., Kordowich, G., Pashaei, M., Bergler, C., Maier, A., Jaeger, J., & Bayer, S. (2025) · International Journal of Electrical Power & Energy Systems · doi:10.1016/j.ijepes.2025.111257 · Cited by 63
“An example analysis is provided in our prior work [180].”
Self-citationPROTECT-90: A Fault Dataset for Power System Protection
Oelhaf, J., Kordowich, G., Bergler, C., et al. (2026) · arXiv.org · doi:10.48550/arxiv.2606.24298 · Cited by 8
“Randomized grid parameters (e.g., S ′′ k , V , ℓ , R ′ , X ′ ) allow controlled analysis of robustness and domain shift effects under varying operating conditions [15], [16].”
Self-citationOelhaf, J., Pashaei, M., Kordowich, G., Bergler, C., Maier, A., Jaeger, J., & Bayer, S. (2026) · IET conference proceedings. · doi:10.1049/icp.2026.1934 · Cited by 1
“Building on our previous framework for fault detection and line identification [8], this study extends the analysis to a unified robustness evaluation across both Fig.”
Self-citationOelhaf, J., Kordowich, G., Kim, C., Pérez-Toro, P. A., Bergler, C., Maier, A., Jaeger, J., & Bayer, S. (2025) · arXiv (Cornell University) · doi:10.48550/arxiv.2510.00831
“…results for fault detection and line identification [4], though their reliability remains limited by data quality, class imbalance, and limited interpretability in safety-critical settings [5], motivating consistent evaluation to distinguish genuine task limitations from dataset or model artefacts.”
Self-citationFeature Selection for Fault Prediction in Distribution Systems
Kordowich, G., Oelhaf, J., Bayer, S., et al. (2026) · Electric power systems research · doi:10.1016/j.epsr.2026.113498 · Cited by 2
“For FP, we use a random forest classifier (RF), which has demonstrated robust performance and resilience to noise for similar classification tasks [22], [28], [29].”
Self-citation
Metadata
- Authors
- Oelhaf, J., Kordowich, G., Kim, C., Pérez-Toro, P. A., Maier, A., Jäger, J., & Bayer, S.
- Affiliations
- Friedrich-Alexander-Universität Erlangen-Nürnberg (DE)
- Institute of Electrical Energy Systems, Friedrich-Alexander-University Erlangen-Nuremberg,Erlangen,Germany
- Venue
- 2025 33rd European Signal Processing Conference (EUSIPCO)
- Publisher
- IEEE
- Published
- 2025-09-08
- Pages
- 1997-2001
- OpenAlex
- W4417053512
- Cited by
- 0
- References
- 15
- FWCI
- 0.00
- Type
- conference paper
- Language
- en
- Open access
- green
- arxiv.org
- Locations
- European Signal Processing Conference (EUSIPCO) (publishedVersion)
- arXiv (Cornell University) (submittedVersion, cc-by)
- arXiv (Cornell University) (cc-by)
- Funders
- Deutsche Forschungsgemeinschaft (535389056)
- Topics
- Physical Sciences › Engineering › Control and Systems Engineering › Power Systems Fault Detection
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Power System Optimization and Stability
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Electrical Fault Detection and Protection
- Keywords
- data sparsity, fault detection, fault line identification, power system protection, transmission networks, missing sensor data, communication breakdown, renewable energy integration, machine learning robustness, data quality, voltage measurement
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
The claim verdicts this report counts are experimental: their accuracy is not yet measured.
A language model drew the claims from the paper on 2026-10-12, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-12 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Cited sources are checked with a language model’s help (gpt-6-sol).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.