Stress–Strain State and Strength of Fiber-Reinforced Concrete Beams with Basalt, Steel, and Polypropylene Fibers
Open accessAbstract
Fiber-reinforced concrete has proved to be viable in improving the mechanical characteristics of structural elements to the flexural and shear stresses. The concrete cubes, prisms, and cylinders were standardized, cast and cured after 28 days to assess the baseline mechanical characteristics. Beam specimens were made of different types of fibers, lengths, and different volumetric contents and then subjected to controlled shear tests in which the crack initiation, propagation, and deformation were accurately measured. The experimental data proved that the addition of fibers was highly beneficial in terms of the mechanical performance of concrete. Basalt fibers enhanced compressive strength by up to 20.8 percent and tensile strength by 30.8 percent, whereas steel fibers had the best flexural strength with a maximum compressive and bending strength of 47.2 MPa and 6.56 MPa, respectively, at optimum dosage. Polypropylene fibers also improved performance, but in a lesser manner. The fiber addition served well to reduce the width of cracks and retard crack propagation, thus enhancing load-bearing capacity. These results show that dispersed fiber reinforcement that uses steel and basalt fibers is a practical solution to improving the dispersion of concrete in terms of durability and load-bearing capacity. The research will help guide the selection of fiber and the content in the reinforced concrete work to offer more robust and sustainable solutions to building.
AI snapshot
Written from the paper’s full text.
TL;DR
This experimental study compares shear behavior and mechanical properties of reinforced concrete beams with basalt, polypropylene, or steel fibers under a unified test program. Steel fibers gave the largest gains in strength and crack control, followed by basalt, then polypropylene.
Key findings
- Basalt fibers increased compressive strength by up to 20.8% (41.8 MPa vs. 34.6 MPa control) and tensile strength by 30.8% (2.89 MPa vs. 2.21 MPa); flexural strength rose from 4.41 MPa to 5.49–5.81 MPa, a 25–32% increase.
- Steel fibers performed best: compressive strength reached 47.2 MPa at 2% fiber content, tensile strength 3.48–3.54 MPa, flexural strength 6.33–6.56 MPa, and elastic modulus 35.6–36.8 GPa vs. 30.91 GPa for the control. Load-bearing capacity increased by 27.3–39.5% for steel, 12.0–20.6% for basalt, and 9.4–14.9% for polypropylene.
- Crack control improved with fibers: at 50–60% of ultimate load, control beams had crack widths of about 0.37 mm, basalt/polypropylene beams about 0.20 mm, and steel-fiber beams about 0.15 mm (Table 4 reports steel values of 0.10–0.15 mm).
- Initial oblique cracking loads were 32.23 kN for the control, 38.92–42.12 kN for basalt, 38.05–41.14 kN for polypropylene, and 48.62–54.59 kN for steel fiber-reinforced beams.
Methods
- Four beam series were cast: control (3 specimens), basalt fiber (18 specimens; 10 mm and 30 mm lengths at 0.1%, 0.2%, 0.3%), polypropylene fiber (18 specimens; same lengths and contents), and steel fiber (9 specimens; 30 mm length at 1%, 2%, 3% per the text, though Table 1 lists 0.1%, 0.2%, 0.3%).
- Beams measured 100 × 200 × 1200 mm, with two 12 mm A-III longitudinal bars (1.33% reinforcement ratio) and 5 mm B-I stirrups spaced at 60 mm near supports and 90 mm at midspan.
- Concrete cubes, prisms, and cylinders were tested at 28 days using a hydraulic press SYE-2000; beam shear tests applied load in stages, measured crack initiation/propagation and deformations with dial gauges/deflectometer to 0.001 mm tolerance.
Limitations
- The paper does not state a limitations section.
- Evident from the text: it is a non-peer-reviewed preprint (Preprints.org, posted 30 December 2025), and there are internal inconsistencies, including steel fiber contents listed as 0.1–0.3% in Table 1 versus 1–3% in the methods/results, Table 4 placing BS30-0.3 under the polypropylene series, repeated “BB10-0.1” labels in the conclusions, and control crack width reported as 0.37 mm in results/Table 4 but 0.30 mm in the conclusions.
- Evident from the text: only three specimens per fiber combination are described, with no statistical analysis reported, and the study is limited to one beam geometry, one concrete mixture, and 28-day testing.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Claims the paper makes
0 of 30 cited sources checked · 0 supported · 0 flagged
- Findingown data
Steel fiber-reinforced concrete beams had elastic modulus increased from 30.91 GPa to 35.6-36.8 GPa.
“Flexural strengths were at 6.33-6.56Mpa and the increase in elastic modulus was as 30.91 Gpa to 35.6-36.8Gpa.”
Quote in the paperSubstantial claim - Findingown data
All tested beams failed in the shear section.
“The shear section failed in all the beams that were tested.”
Quote in the paperNot a substantial claim - Findingown data
The BS30-3.0 sample with 3% steel fiber showed the lowest creep values in almost all stages.
“The BS30-3.0 sample with 3% steel fiber showed the lowest creep values in almost all stages.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingown data
When adding 30 mm long basalt fibers to concrete in an amount of 0.1%, the relative deformations of concrete in the oblique section reached ɛfb=(1.25÷3.0)•10−4 when the breaking force in the oblique section reached 60÷70 kN.
“When adding 30 mm long basalt fibers to the concrete in an amount of 0.1%, the relative deformations of concrete in the oblique section reached the values ɛfb=(1.25÷3.0)•10-4when the breaking force in the oblique section reached 60÷70 kN in the dispersed reinforced fiber-reinforced concrete beams (Figure 13).”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingown data
The relative deformation of the BS30-1.0 sample under a load of 60÷70 kN was ɛfb=(0.85÷1.05)•10−4.
“For example, the relative deformation of the BS30-1.0sample under a load of 60÷70 kN was ɛfb=(0.85÷1.05)•10⁻⁴.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingown data
When the load reached 60÷70 kN, the relative deformation of the BO-1 (plain concrete) sample reached ɛfb=(2÷7)•10−4.
“When the load reached 60÷70 kN, the relative deformation of the BO-1 (plain concrete) sample reached ɛfb=(2÷7)•10⁻⁴.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingreasoning
Basalt fibers had an effective effect on increasing the crack resistance of concrete.
“Basalt fibers also had an effective effect on increasing the crack resistance of concrete.”
Quote in the paperSubstantial claim - Findingreasoning
The transverse failure of beams with dispersed fiber reinforcement was significantly different from that of classical reinforced concrete beams.
“The transverse failure of beams with dispersed fiber reinforcement was significantly different from that of classical reinforced concrete beams.”
Quote in the paperSubstantial claim- Rests on an assumption: The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.
- Findingown data
The volume and length of basalt fibers significantly affected the relative deformations of concrete in the stages of loading in the oblique section.
“The results of the experiment on fiber-reinforced concrete beams dispersedly reinforced with basalt fibers showed that the volume and length of the fibers significantly affected the relative deformations of concrete in the stages of loading in the oblique section.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingnone given
In reinforced concrete beams made of ordinary concrete, when the breaking force reached 80÷90% (130÷140 kN), the deflection value was 10÷12 mm.
“In reinforced concrete beams made of ordinary concrete, when the value of the breaking force reached 80÷90%, that is, (130÷140 kN), the deflection value was 10÷12 mm.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingreasoning
Fibers increased the strength of concrete in the initial crack formation even after cracks formed.
“even after the formation of cracks, that is, they increased the strength of concrete in the initial crack formation.”
Quote in the paperSubstantial claim - Findingown data
In the BS30-1.0, BS30-2.0 and BS30-3.0 sample beams (steel fiber-reinforced concrete), the deformations remained relatively low.
“In the BS30-1.0,BS30-2.0 and BS30-3.0sample beams, that is, fiber-reinforced concrete samples with the addition of steel fibers, the deformations remained relatively low.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingreasoning
The overall crack resistance of the fiber-reinforced concrete beam was ensured.
“The overall crack resistance of the fiber-reinforced concrete beam was ensured.”
Quote in the paperSubstantial claim - Findingown data
Steel fiber-reinforced concrete beams had tensile strengths of 3.48-3.54 MPa.
“Compressive strengths of 1, 2 and 3 percent steel fiber beam were 45.1, 47.2 and 44.3 Mpa respectively and tensile strengths rose to 3.48-3.54Mpa.”
Quote in the paperSubstantial claim - Findingown data
At stages with a breaking load of up to 60 kN in the transverse section, the creep in the BP30-0.3 and BS30-0.2 samples showed a greater resistance by a difference of 0.2÷0.3 mm compared to the creep of reinforced concrete beam samples made of ordinary concrete BO-0.
“The creep characteristics of concrete samples with the addition of polypropylene fibers (BP30-0.3,BS30-0.2,BS30-0.1)show that at stages with a breaking load of up to 60 kN in the transverse section, the creep in the BP30-0.3 and BS30-0.2samples showed a greater resistance by a difference of 0.2÷0.3mm compared to the creep of reinforced concrete beam samples made of ordinary concrete BO-0.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingown data
Steel fiber-reinforced concrete beams had flexural strengths of 6.33-6.56 MPa.
“Flexural strengths were at 6.33-6.56Mpa and the increase in elastic modulus was as 30.91 Gpa to 35.6-36.8Gpa.”
Quote in the paperSubstantial claim - Findingown data
In the steel fiber reinforced concrete samples, the deformations at the stage of breaking force 140÷150 kN were relatively small.
“In the steel fiber reinforced concrete samples, the deformations at this stage were relatively small.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingnone given
As the load increased, especially when the breaking force in the oblique section reached 140÷150 kN, the relative deformations in the samples became much larger.
“As the load increased, especially when the breaking force in the oblique section reached 140÷150 kN, the relative deformations in the samples became much larger.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingown data
Steel fiber-reinforced concrete beams with 1%, 2%, and 3% steel fibers had compressive strengths of 45.1, 47.2, and 44.3 MPa, respectively.
“Compressive strengths of 1, 2 and 3 percent steel fiber beam were 45.1, 47.2 and 44.3 Mpa respectively and tensile strengths rose to 3.48-3.54Mpa.”
Quote in the paperSubstantial claim - Findingown data
The beam reinforced with 2.0% steel fiber recorded the highest moment and force.
“In particular, the beam reinforced with 2.0% steel fiber recorded the highest moment and force.”
Quote in the paperSubstantial claim - Findingown data
Control concrete (BO) had a compressive strength of 34.6 MPa.
“In compressive strength, control specimen (BO) had a compressive strength of 34.6 Mpa with the basalt fiber reinforced specifications of 39.8-41.8Mpa with the greatest strength of 41.8 Mpa which is a 20.8 percentage improvement.”
Quote in the paperSubstantial claim - Findingown data
In ordinary concrete (BO-1 sample), the deformations at the stage of breaking force 140÷150 kN increased to ɛfb=(75÷80)•10−4.
“In ordinary concrete, that is, in the BO-1 sample, the deformations at this stage increased to ɛfb=(75÷80)•10⁻⁴.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingreasoning
Among all the experimented specimens, steel fiber-reinforced concrete had the greatest improvements.
“Among all the experimented specimens, steel fiber-reinforced concrete had the greatest improvements.”
Quote in the paperSubstantial claim- Rests on an assumption: Steel fibers are the most effective reinforcement in enhancing shear resistance and ductility in reinforced concrete beams.
- Findingown data
The initial crack in the oblique section occurred at Qcrc=32.23 kN in the reinforced concrete beam made of ordinary concrete.
“The initial crack in the oblique section occurred at Qcrc=32.23 kN in the reinforced concrete beam made of ordinary concrete”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingown data
When the breaking load reached 50÷60%, the crack width in ordinary reinforced concrete beams was 0.30 mm.
“When the breaking load reached 50÷60%, the crack width in ordinary reinforced concrete beams was 0.30 mm.”
Quote in the paperSubstantial claim - Findingown data
In specimens reinforced with 30 mm long steel fibers added to concrete in the range of 1.0÷3.0%, the initial cracks in the oblique section occurred at Qcrc=48.62÷54.59 kN.
“In specimens reinforced with 30 mm long steel fibers added to concrete in the range of 1.0÷3.0%, the initial cracks in the oblique section occurred at Qcrc=48.62÷54.59kN.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingreasoning
The failure in fiber-reinforced beams along the oblique section is not brittle but continuous plastic failure.
“This is manifested not by brittle failure in the beam along the oblique section but by continuous plastic failure.”
Quote in the paperSubstantial claim- Rests on an assumption: The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.
- Findingreasoning
Basalt and polypropylene fibers contribute not to the process of failure occurring in the oblique section but to the reduction of the initial internal defects-cracks that can create the basis for this failure.
“It was observed that they contribute not to the process of failure occurring in the oblique section but to the reduction of the initial internal defects-cracks that can create the basis for this failure.”
Quote in the paperSubstantial claim - Findingown data
In samples reinforced with polypropylene fibers with a length of 10 and 30 mm added to the concrete in the range of 0.1÷0.3%, the initial crack in the oblique section occurred at Qcrc=38.05÷41.14 kN.
“In the samples reinforced with polypropylene fibers with a length of 10 and 30 mm added to the concrete in the range of 0.1÷0.3%, the initial crack in the oblique section occurred at Qcrc=38.05÷41.14kN.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Findingown data
The load-bearing capacity of fiber-reinforced concrete beams dispersedly reinforced with basalt fibers increased by 12.0÷20.6% compared to the load-bearing capacity of ordinary beams.
“According to the results of laboratory tests, it was found that the load-bearing capacity of fiber-reinforced concrete beams dispersedly reinforced with basalt fibers increased by 12.0÷20.6%compared to the load-bearing capacity of ordinary beams.”
Quote in the paperSubstantial claim - Findingreasoning
After the cracks formed, the beam continued to carry the load for a certain period of time without losing its full strength.
“After the cracks formed, the beam continued to carry the load for a certain period of time without losing its full strength.”
Quote in the paperSubstantial claim - Findingown data
In samples reinforced with basalt fibers with a length of 30 mm added to the concrete in the range of 0.1÷0.3%, the initial crack in the oblique section occurred at Qcrc=38.92÷40.69 kN.
“In the samples reinforced with basalt fibers with a length of 30 mm added to the concrete in the range of 0.1÷0.3%, the initial crack in the oblique section occurred at Qcrc=38.92÷40.69kN.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
- Interpretationown data
The addition of fibers was highly beneficial in terms of the mechanical performance of concrete.
“The experimental data proved that the addition of fibers was highly beneficial in terms of the mechanical performance of concrete.”
Quote in the paperSubstantial claim - Premisecitation
Fibers can transmit tensile forces across cracks through interfacial bonding, friction, and mechanical anchorage.
“The principle of dispersed reinforcement is anchored on the fact that fibers can transmit tensile forces across cracks using interfacial bonding, friction and mechanical anchorage [13].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [13] Silva, 2024, Mechanical and chemical properties of cementitious composites with rice husk after natural polymer degradation at high temperatures, J. Build. Eng. source
- Interpretationown data
Dispersed fiber reinforcement using steel and basalt fibers is a practical solution to improving the dispersion of concrete in terms of durability and load-bearing capacity.
“These results show that dispersed fiber reinforcement that uses steel and basalt fibers is a practical solution to improving the dispersion of concrete in terms of durability and loadbearing capacity.”
Quote in the paperSubstantial claim- Rests on an assumption: The behavior observed in the 100×200×1200 mm beam specimens under the described shear test is representative of reinforced concrete beams in building applications.
- Premisecitation
Basalt fiber performance is highly dependent on fiber length, volume fraction, and bonding with the cementitious matrix.
“But their performance is highly bound on the length of fibers, volume fraction and the bonding with cementitious matrix [27].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [27] Yan, 2023, Mechanical performance study of basalt-polyethylene fiber reinforced concrete under dynamic compressive loading, Constr. Build. Mater. source
- Premisecitation
Direct comparisons of different fiber types tend to be inconclusive.
“Therefore, direct comparisons of the various types of fibers tend to be inconclusive [29].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [29] Islam, 2024, An experimental study on mechanical and fracture characteristics of hybrid fibre reinforced concrete, Structures source
- Premisecitation
Short discrete fibers incorporated into the concrete matrix provide an added crack-bridging mechanism.
“Improvement of the material behavior involves the use of the short, discrete fibers into the concrete matrix to provide an added crack-bridging mechanism [11].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [11] Ralegaonkar, 2018, Application of chopped basalt fibers in reinforced mortar: A review, Constr. Build. Mater. source
- Premisecitation
These problems are acute under high service loads, dynamic or cyclic loading, and harsh environmental conditions.
“These problems are acute in case of high loads of services, dynamic or cyclic loading, and in harsh environmental conditions [9].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [9] Vedhasakthi, 2023, Strength attributes and microstructural characterization of basalt fibre incorporated self-compacting concrete, J. Build. Eng. source
- Premisecitation
The overall assessment of the stress-strain state of reinforced concrete beams reinforced with dispersely reinforced steel, polypropylene, and basalt fibers under the same experimental conditions is under-researched.
“Specifically, the overall assessment of the stress-strain state of reinforced concrete beams reinforced with dispersely reinforced steel, polypropylene, and basalt fibers under the same experimental conditions is under-researched [30,31].”
Quote in the paperSubstantial claim0 of 2 sources checked- cites [30] Cai, 2024, Study on fracture characteristics of steel fiber reinforced manufactured sand concrete using DIC technique, Case Stud. Constr. Mater. source
- cites [31] Xiong, 2024, Fracture properties and mechanisms of steel fiber and glass fiber reinforced rubberized concrete, J. Build. Eng. source
- Interpretationown data
Steel fibers have the greatest resistance to crack propagation in the shear zone.
“These findings indicate that steel fibers have the greatest resistance to crack propagation in the shear zone.”
Quote in the paperSubstantial claim - Premisecitation
There is a relative paucity of studies that analyze strain distribution, stiffness degradation, post-yield behavior, and failure mechanisms in fiber-reinforced concrete beams.
“Numerous investigations focus on ultimate load capacity or cracking patterns, and there is a relative paucity of studies that analyze the distribution of strains, degradation of stiffness, post-yield behavior, and mechanisms of failure [32,33].”
Quote in the paperSubstantial claim0 of 2 sources checked- cites [32] Khalid, 2023, Fresh, mechanical, and durability properties of basalt fiber-reinforced concrete (BFRC): A review, Dev. Built Environ. source
- cites [33] Yousefi, 2022, Flexural behavior of reinforced concrete beams made of normal and polypropylene fiber-reinforced concrete containing date palm leaf ash, Structures source
- Interpretationreasoning
This ensured that the structure retained a certain load-bearing capacity even in the event of damage.
“This ensured that the structure retained a certain load-bearing capacity even in the event of damage.”
Quote in the paperSubstantial claim - Interpretationreasoning
The small decrease in performance with increased fiber contents indicates that there is an optimum level of dose beyond which the fiber clustering and lower workability can have a negative impact on performance.
“The small decrease in performance with increased fiber contents indicates that there is an optimum level of dose beyond which the fiber clustering and lower workability can have a negative impact on performance.”
Quote in the paperSubstantial claim- Rests on an assumption: Moderate levels of fiber work better compared to higher amounts because of their better workability and fiber dispersion.
- Interpretationreasoning
Basalt and polypropylene fibers are important in preventing microcracks that appear in the plastic state of concrete (before solidification).
“However, they are important in preventing microcracks that appear in the plastic state of concrete (before solidification).”
Quote in the paperSubstantial claim - Interpretationreasoning
Dispersed reinforcement (fibers distributed in volume) affected the failure processes in fiber-reinforced concrete beams under the influence of transverse forces.
“Dispersed reinforcement-that is, the addition of fibers distributed not in a single direction but in volume to the concrete mass-affected the failure processes in fiber-reinforced concrete beams under the influence of transverse forces.”
Quote in the paperSubstantial claim- Rests on an assumption: The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.
- Interpretationreasoning
The shrinking of the diagonal cracking at half the maximum shear load proves the purpose of polypropylene fibers in facilitating serviceability action instead of maximum strength.
“The shrinking of the diagonal cracking at half the maximum shear load proves the purpose of polypropylene fibers in facilitating serviceability action instead of maximum strength.”
Quote in the paperSubstantial claim - Interpretationreasoning
Steel fibers act as a 'bridge' between diagonal cracks, maintaining the load-bearing capacity of the beam for a certain period of time.
“In particular, since steel fibers have high elasticity and tensile strength, they act as a”
Quote in the paperSubstantial claim- Rests on an assumption: The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.
- May combine two claims. 65
- Classified as probably not a substantial claim. 8
- The quote only partly states this claim. 1
May combine two claims.
Findingown dataAt loads around 20÷70 kN, the creep indicators in steel fiber concrete were lower than in concrete without fibers, increasing the internal resistance of the structure.
“It was found that at loads around 20÷70 kN, the creep indicators in steel fiber concrete were lower than in concrete without fibers, increasing the internal resistance of the structure.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
May combine two claims.
Findingown dataAt 60 kN, the creep in BO-0 was 2.1 mm, in BS30-0.1 it was 1.4 mm, in BP30-0.3 it was 1.9 mm, and in BS30-0.2 it was 1.7 mm.
“For example, at 60 kN, the creep in BO-0 was 2.1 mm, while in BS30-0.1 it was 1.4 mm, in BP30-0.3 it was 1.9 mm, and in BS30-0.2 it was 1.7 mm (Figure 15).”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
May combine two claims.
Findingown dataBasalt fiber-reinforced concrete specimens had tensile strengths of 2.66-2.89 MPa compared to 2.21 MPa in plain concrete, and the improvement in BB10-0.2 was 30.8%.
“The tensile strength had risen to 2.66-2.89Mpa in basalt fiber specimens as compared to 2.21 Mpa in plain concrete and the improvement in BB10-0.2 was 30.8%.”
- Also stated in: § Abstract · plain
“Basalt fibers enhanced compressive strength by up to 20.8 percent and tensile strength by 30.8 percent, whereas steel fibers had the best flexural strength with a maximum compressive and bending strength of 47.2 MPa and 6.56 MPa, respectively, at optimum dosage.”
Quote in the paperSubstantial claim- Also stated in: § Abstract · plain
May combine two claims.
Findingown dataIn BP10-0.3, the normal cracking moment was 3.92 kN m and the transverse force causing oblique cracking was 38.28 kN.
“In the BP10-0.3sample, the moment causing normal cracks was 3.92 kN•m, and the transverse force causing oblique cracks was 38.28 kN.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown dataThe deformations of the concrete along the inclined section did not have large values at the initial stages of loading, and their change increased almost linearly.
“The deformations of the concrete along the inclined section did not have large values at the initial stages of loading, and their change increased almost linearly.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
May combine two claims.
Findingown dataBasalt fiber-reinforced concrete specimens had flexural strengths of 5.49-5.81 MPa compared to 4.41 MPa in control, an increment of 25-32%.
“It also enhanced flexural strength, which was 4.41 Mpa in the control and 5.49-5.81Mpa in the basalt fiber specimen, which is an increment of 25 to 32 percent.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn BP10-0.2, the normal cracking moment was 3.99 kN m and the transverse force causing oblique cracking was 41.14 kN, 48% higher in moment and 28% higher in shear force than the BO beam.
“In the BP10-0.2beam, the moment causing normal cracking was 3.99 kN m and the transverse force causing oblique cracking was 41.14 kN, which means that it is 48% higher in moment and 28% higher in shear force than the BO beam.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn BP30-0.1, the normal cracking moment was 4.01 kN m and the transverse force causing oblique cracks was 40.49 kN, increases of 49% and 25% compared to the plain beam.
“In the BP30-0.1 sample, the normal cracking moment was 4.01 kN m, and the transverse force causing oblique cracks was 40.49kN.These results show an increase of 49% and 25%, respectively, compared to the plain beam.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataControl reinforced concrete beams without fibers formed diagonal cracks mainly around supports at a 45° angle and collapsed abruptly in a brittle fashion at maximum load with little post-cracking strength.
“The diagonal cracks that formed in the control reinforced concrete beam with no fibers were mainly formed in the areas surrounding the supports and extended at a 45 ° angle.At the point of the maximum load, these beams collapsed abruptly in a brittle fashion, which meant that they had very little post-cracking strength.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn BS30-1.0, the normal cracking moment was 4.60 kN m and the transverse force causing oblique cracks was 52.59 kN, increases of approximately 71% and 63% compared to the normal beam.
“In the steel fiber reinforced beams, i.e., in the BS30-1.0sample, the normal cracking moment was 4.60 kN m, and the transverse force causing oblique cracks was 52.59 kN.These results show an increase of approximately 71% and 63%, respectively, compared to the normal beam.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataFiber-reinforced beams with basalt, polypropylene, or steel fibers limited crack initiation and propagation, reduced crack width and spacing, slowed failure, and retained load-bearing capacity after diagonal cracks developed.
“The inclusion of fibers was key in limiting the crack initiation and propagation by limiting the widening of cracks, decreasing the separation between the cracks and slowing down the general failure.This made fiber-reinforced beams retain some amount of load bearing capacity despite development of diagonal cracks.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataResidual tensile strength of basalt fiber specimens was 1.16-1.29 MPa for 10 mm fibers and 1.19-1.32 MPa for 30 mm fibers.
“Remaining tensile strength of 10 mm specimens with basalt fibers (basalt fibers) was between 1.16 and 1.29 Mpa and 1.19 and 1.32 Mpa in 30 mm fiber specimens.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown dataAt the loading stage of 130÷140 kN, the deflection in BS30-3.0 was 8.8 mm, in BS30-2.0 it was 7.5 mm, and in BS30-1.0 it was 8.8 mm.
“At this loading stage, the deflection in BS30-3.0 was 8.8 mm, in BS30-2.0 it was 7.5 mm, and in BS30-1.0 it was 8.8 mm.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
May combine two claims.
Findingown dataBasalt fiber-reinforced concrete specimens had compressive strengths of 39.8-41.8 MPa, with the greatest strength 41.8 MPa, a 20.8% improvement over control.
“In compressive strength, control specimen (BO) had a compressive strength of 34.6 Mpa with the basalt fiber reinforced specifications of 39.8-41.8Mpa with the greatest strength of 41.8 Mpa which is a 20.8 percentage improvement.”
- Also stated in: § Abstract · plain
“Basalt fibers enhanced compressive strength by up to 20.8 percent and tensile strength by 30.8 percent, whereas steel fibers had the best flexural strength with a maximum compressive and bending strength of 47.2 MPa and 6.56 MPa, respectively, at optimum dosage.”
Quote in the paperSubstantial claim- Also stated in: § Abstract · plain
May combine two claims.
Findingown dataIn BP30-0.2, the normal cracking moment was 3.87 kN m and the transverse force causing oblique cracks was 39.10 kN.
“In the BP30-0.2,these figures were 3.87 kN m and 39.10 kN, while in the BP30-0.3they were 3.81 kN m and 38.56 kN.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown dataPolypropylene fiber-reinforced concrete BP10-0.1 and BP10-0.2 had compressive strengths of 38.6 and 39.9 MPa, respectively.
“Compressive, tensile, and flexural strengths of BP10-0.1 and BP10-0.2 were 38.6 and 39.9 Mpa, 2.71 and 2.76 Mpa and 1.12-1.25 times greater than plain concrete respectively.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataAt breaking force 140÷150 kN, the relative deformations in steel fiber reinforced concrete samples were: BS30-1.0: ɛfb=(50÷60)•10−4, BS30-2.0: ɛfb=(35÷50)•10−4, BS30-3.0: ɛfb=(65÷70)•10−4.
“In the BS30-1.0series sample, the relative deformation reached ɛfb=(50÷60)•10⁻⁴, in the BS30-2.0series sample, the relative deformation reached ɛfb=(35÷50)•10⁻⁴, and in the BS30-3.0series sample, the relative deformation reached ɛfb=(65÷70)•10⁻⁴.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
May combine two claims.
Findingown dataThe highest compressive, tensile, and flexural performances were found among steel fiber-reinforced specimens, then basalt fiber and polypropylene fiber specimens.
“All in all, the highest results of compressive, tensile, and flexural performances were found among steel fiber-reinforced specimens, then basalt fiber and polypropylene fiber specimens.”
- Also stated in: § Abstract · plain
“Basalt fibers enhanced compressive strength by up to 20.8 percent and tensile strength by 30.8 percent, whereas steel fibers had the best flexural strength with a maximum compressive and bending strength of 47.2 MPa and 6.56 MPa, respectively, at optimum dosage.Polypropylene fibers also improved performance, but in a lesser manner.”
Quote in the paperSubstantial claim- Also stated in: § Abstract · plain
May combine two claims.
Findingnone givenPolypropylene fibers limited the width of the cracks and reduced the number and size of cracks on the surface of the beam.
“Polypropylene fibers limited the width of the cracks and reduced the number and size of cracks on the surface of the beam.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn BS30-3.0, the normal cracking moment was 4.71 kN m and the transverse force causing oblique cracks was 48.62 kN; the high efficiency achieved at 2.0% fiber content was slightly reduced at 3.0%.
“In the BS30-3.0beam, the normal cracking moment was 4.71 kN m, and the transverse force causing oblique cracks was 48.62 kN, i.e., the high efficiency achieved with a fiber content increased to 2.0% was slightly reduced at 3.0%.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn BS30-2.0, the normal cracking moment was 5.0 kN m and the transverse force causing oblique cracks was 54.42 kN, increases of 86% in normal cracking moment and 69% in shear force compared to the BO beam.
“In the BS30-2.0beam, the normal cracking moment increased further to 5.0 kN m, and the transverse force causing oblique cracks was 54.42 kN.These figures show an increase of 86% in normal cracking moment and 69% in shear force compared to the BO beam.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataWhen the breaking force reached 60 kN, the deflection in the BS30-3.0 sample reached 1.8 mm, in BS30-2.0 it was 1.5 mm, in BS30-1.0 it was 1.5 mm, and in BO-0 it was 2.1 mm.
“When the value of the breaking force reached 60 kN, the deflection in the BS30-3.0sample reached 1.8 mm, while in BS30-2.0 it was 1.5 mm, in BS30-1.0 it was 1.5 mm, and in BO-0 it was 2.1 mm.”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
May combine two claims.
Findingown dataIn BP10-0.1, the normal cracking moment was 3.80 kN m and the transverse force causing oblique cracking was 38.05 kN, increases of 41% and 18% compared to the ordinary beam.
“In the BP10-0.1 sample, the moment causing normal cracking was 3.80 kN m, and the transverse force causing oblique cracking was 38.05 kN.These indicators indicate an increase of 41% and 18%, respectively, compared to the ordinary beam.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataAt 25 kN, the deflection in the BS30-3.0 sample was 0.470 mm, in BS30-2.0 it was 0.418 mm, in BS30-1.0 it was 0.38 mm, and in BO-0 it was 0.3 mm.
“For example, at 25 kN, the deflection in the BS30-3.0sample was 0.470 mm, while in the BS30-2.0 it was 0.418 mm, in the BS30-1.0 it was 0.38 mm, and in the BO-0 it was 0.3 mm (Figure 14).”
Quote in the paperNot a substantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
May combine two claims.
Findingown dataPolypropylene fiber-reinforced concrete BP10-0.1 and BP10-0.2 had tensile strengths of 2.71 and 2.76 MPa, respectively.
“Compressive, tensile, and flexural strengths of BP10-0.1 and BP10-0.2 were 38.6 and 39.9 Mpa, 2.71 and 2.76 Mpa and 1.12-1.25 times greater than plain concrete respectively.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn BP30-0.3, the normal cracking moment was 3.81 kN m and the transverse force causing oblique cracks was 38.56 kN.
“In the BP30-0.2,these figures were 3.87 kN m and 39.10 kN, while in the BP30-0.3they were 3.81 kN m and 38.56 kN.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown dataAt a load of nearly 50-60% of the final load, control beam crack width was approximately 0.37 mm; polypropylene and basalt fiber-reinforced beams had crack widths about 0.20 mm; steel fiber-reinforced beams had the lowest crack widths about 0.15 mm.
“At a load of nearly 50÷60 percent of the final load, the width of the cracks in the control beams was approximately 0.37 mm.Comparatively, both polypropylene and basalt fiber reinforced beam types recorded low crack widths of about 0.20 mm and steel fiber-reinforced beam types had the lowest crack widths of about 0.15 mm.”
Quote in the paperSubstantial claimMay combine two claims.
FindingreasoningThe reinforced concrete of basalt fiber was tested to reveal the significant growth of compressive and tensile strength, and the best indicators were recorded at 0.2 percent of fiber content and 10 mm length.
“The reinforced concrete of basalt fiber was tested to reveal the significant growth of compressive and tensile strength, and the best indicators were recorded at 0.2 percent of fiber content and 10 mm length.”
Quote in the paperSubstantial claimMay combine two claims.
FindingreasoningIn fiber-reinforced concrete beams with the addition of fibers, cracks along the oblique section developed at a small angle, their width became smaller, and they spread in the form of several diagonal lines.
“In fiber-reinforced concrete beams with the addition of fibers, cracks along the oblique section developed at a small angle, their width became smaller, and they spread in the form of several diagonal lines.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn beams reinforced with polypropylene fibers, the load-bearing capacity increased by 9.4÷14.9%, and in beams reinforced with steel fibers by 27.3÷39.5%.
“In beams reinforced with polypropylene fibers, this indicator increased by 9.4÷14.9%,and in beams reinforced with steel fibers -by 27.3÷39.5%.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataAll of fiber-reinforced concrete specimens had better compressive, tensile and flexural strengths, better crack control and post-cracking properties when compared to the control beams.
“All of fiber-reinforced concrete specimens had better compressive, tensile and flexural strengths, better crack control and post-cracking properties when compared to the control beams.”
Quote in the paperSubstantial claim- Rests on an assumption: Fibers are crack-bridging fibers that inhibit crack generation and propagation, and increase the overall structure performance of members made of concrete.
May combine two claims.
FindingreasoningAccording to the results of scientific research, transverse failure in beams with dispersed reinforcement with steel, basalt, and polypropylene fibers occurs later, and the cracks develop at a smaller angle and more slowly.
“According to the results of scientific research, transverse failure in beams with dispersed reinforcement with steel, basalt, and polypropylene fibers occurs later, and the cracks develop at a smaller angle and more slowly.”
Quote in the paperSubstantial claim- Rests on an assumption: The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.
May combine two claims.
FindingreasoningPolypropylene fibers add to better mechanical properties and crack management but at a slightly lower extent than basalt and steel fibers.
“Polypropylene fibers were also known to add to better mechanical properties and crack management but at a slightly lower extent than basalt and steel fibers.”
Quote in the paperSubstantial claim- Rests on an assumption: Fibers are crack-bridging fibers that inhibit crack generation and propagation, and increase the overall structure performance of members made of concrete.
May combine two claims.
Findingown dataIn samples with the addition of polypropylene and basalt fibers, the crack width at 50÷60% breaking load was 0.2 mm, and in samples reinforced with steel fibers it was 0.15 mm.
“For comparison, in samples with the addition of polypropylene and basalt fibers, this indicator was 0.2 mm, and in samples reinforced with steel fibers -0.15 mm.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataThe addition of steel, basalt and glass fibers to ordinary reinforced concrete beams effectively resisted the propagation of diagonal and normal cracks in the samples, increased the number of cracks and reduced the distance between the cracks.
“It was found that the addition of steel, basalt and glass fibers to ordinary reinforced concrete beams effectively resisted the propagation of diagonal and normal cracks in the samples, increased the number of cracks and reduced the distance between the cracks.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataIn the BB10-0.1 sample, the initial crack in the oblique section occurred at Qcrc=41.97 kN; in the BB10-0.1 sample at Qcrc=42.12 kN; and in the BB10-0.1 sample at Qcrc=39.06 kN.
“while in the BB10-0.1 sample it occurred at Qcrc=41.97 kN, in the BB10-0.1 sample it occurred at Qcrc=42.12 kN and in the BB10-0.1 sample it occurred at Qcrc=39.06 kN.”
Quote in the paperSubstantial claim- Rests on an assumption: The measuring device installed along the inclined section accurately measures relative deformations of concrete.
Probably not a substantial claim: may not pass S3 (load-bearing).
PremisecitationSteel fibers can corrode in harsh conditions, affecting long-term durability unless proper protection is provided.
“But steel fibers can be easily corroded in harsh conditions and as such, long life durability can be affected unless proper protection is provided [19].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [19] Liu, 2025, Performance of red mud concrete reinforced with single and hybrid Polyvinyl alcohol and Basalt fibers, J. Build. Eng. source
Probably not a substantial claim: may not pass S3 (load-bearing). The quote only partly states this claim.
Study design and conductown dataThree beam specimens were cast for each fiber length and dosage combination in the basalt and polypropylene series.
“For each fiber length and dosage, three beam specimens were cast, resulting in a total of 18 basalt fiber-reinforced concrete beams.”
- Also stated in: § 2.1. Construction of the Testing Samples · plain
“Similarly, three beam specimens were prepared for each combination, yielding a total of 18 polypropylene fiber-reinforced concrete beams.”
Quote in the paperNot a substantial claim- Also stated in: § 2.1. Construction of the Testing Samples · plain
May combine two claims.
PremisecitationFibers change the tensile characteristics of concrete, crack spacing, and width, and influence the stress transfer process between concrete and steel reinforcement.
“The fibers change the tensile characteristics of concrete, crack spacing, and width, as well as influence the stress transfer process between concrete and steel reinforcement [34].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [34] Azandariani, 2023, Mechanical properties of polyolefin and polypropylene fibers-reinforced concrete–An experimental study, Compos. Part C Open Access source
May combine two claims.
PremisecitationThe majority of current studies are either on a single type of fiber or examine fibers under different environmental conditions, concrete compositions, reinforcement configurations, or loading configurations.
“Although there has been an extensive amount of literature on fiber-reinforced concrete, the majority of current studies are either on a single type of fiber or examine fibers under different environmental conditions, including the different concrete compositions, reinforcement configurations, or loading configurations [28].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [28] He, 2025, Flexural performance of steel fiber reinforced MPCC beams: Experimental study and theoretical analysis, Eng. Struct. source
May combine two claims.
InterpretationreasoningBasalt fibers ensured that the stresses during bending did not accumulate at one point, reducing the formation of microcracks.
“Basalt fibers ensured that the stresses during bending did not accumulate at one point, reducing the formation of microcracks.”
Quote in the paperSubstantial claimClassified as probably not a substantial claim.
Study design and conductcitationConcrete specimens were cast with the same batch of concrete used on the experimental beams.
“According to the demands of [36], physical and mechanical properties of the concrete were carried out based on standard cube, prism and cylinder specimens casted with the same batch of concrete used on the experimental beams.”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [36] (2017). Fiber Reinforced Concrete Structures and Precast Products with Non-Steel Fibers. Design Rules (Standard No. DR297.1325800.2017).
Not checked in the free run.
Probably not a substantial claim: may not pass S3 (load-bearing).
Study design and conductown dataThree beam specimens were prepared for each steel fiber content.
“For each fiber content, three beam specimens were prepared, resulting in a total of 9 steel fiber-reinforced concrete beams.”
Quote in the paperNot a substantial claimMay combine two claims.
PremisecitationBasalt fibers have high tensile strength, relatively high elastic modulus, high thermal stability, and high resistance to chemical attack and corrosion.
“Basalt fibers have great tensile strength, comparatively high elastic modulus, high thermal stability, and high resistance to chemical attack and corrosion [24].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [24] Mashayekhi, 2025, Shear performance of fibre-reinforced seawater sea-sand concrete–fibre hybridization and synergy effects, Constr. Build. Mater. source
Classified as probably not a substantial claim. May combine two claims.
Study design and conductnone givenBeam specimens were constructed with the exact geometry, the same reinforcement plan, the same concrete mixture, and the same curing conditions to ensure effective direct comparison.
“The beam specimens are constructed with the exact geometry, the same reinforcement plan, the same concrete mixture, and the same curing conditions to make sure that the direct comparison is effective.”
Quote in the paperSubstantial claimMay combine two claims.
PremisecitationDispersed fibers are randomly placed throughout the concrete volume and interact with micro- and macrocracks at various loading stages.
“In contrast to the traditional reinforcement bars that work at the macro-scale only, the dispersed fibers are in place at random all through the concrete volume and the interaction with micro-and macrocracks at various loading stages takes place [12].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [12] Shyamala, 2022, Impact of reinforcement and geometry of deep beam–Research perspective, Mater. Today Proc. source
Probably not a substantial claim: may not pass S3 (load-bearing). May combine two claims.
PremisecitationPolypropylene fibers are chemically inert and corrosion resistant, making them appealing for durability and long-term performance.
“The polypropylene fibers are especially appealing to use where durability and long-term performance become a major concern owing to their chemical inertness and resistance to corrosion [23].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [23] Yang, 2024, Shear behavior of regular oriented steel fiber-reinforced concrete beams reinforced with glass fiber polymer (GFRP) bars, Structures source
May combine two claims.
Interpretationown dataBasalt and polypropylene fibers were effective in restricting crack growth, but their efficiency to control cracks was slightly lower than steel fibers.
“The basalt and polypropylene fibers also were effective in restrictions of crack growth, but the efficiency of the polypropylene and basalt fibers to control crack was a little lower than the steel fibers.”
Quote in the paperSubstantial claimMay combine two claims.
PremisecitationConventional reinforced concrete beams have shortcomings under bending moments, including premature tensile cracking, high crack growth rate, low post-cracking stiffness, and relatively brittle failure after tensile reinforcement yields.
“Although they are widely used, conventional reinforced concrete beams have a number of shortcomings inherent to them at the time when they are under bending moments [2].These shortcomings consist of premature tensile cracking, high rate of crack growth, low post tensile cracking hardness and comparatively brittle failure behavior after tensile reinforcement yields [3].”
Quote in the paperSubstantial claim0 of 2 sources checked- cites [2] Hassan, 2025, Effect of basalt macro fiber on shear strength of high-strength concrete beams with web openings: A finite element parametric study, Case Stud. Constr. Mater.
Not checked in the free run.
- cites [3] Liu, 2022, Experimental study on the mechanical behaviour of short chopped basalt fibre reinforced concrete beams, Structures source
Probably not a substantial claim: may not pass S3 (load-bearing).
PremisecitationBasalt fibers have less environmental impact in production than synthetic fibers.
“In addition, they have less environmental effects in their production as opposed to synthetic fibers and are therefore environmentally friendly [25].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [25] Mirzaaghabeik, 2025, Impact of geometrical dimensions on the shear behaviour of UHPC deep beams reinforced with steel and synthetic fibres, Structures source
May combine two claims.
PremisecitationPolypropylene fibers improve deformation capacity and post-cracking performance in flexural members, although their ultimate strength is usually small.
“The benefit of PP fibers is that in flexural members, the deformation capacity and post-cracking performance are improved, although their ultimate strength is usually small [22].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [22] Esakki, A.K.D.K., Dev, S.K.A., Gomathy, T., and Chella Gifta, C. (Mater. Today Proc., 2023). Influence of adding steel–glass–polypropylene fibers on the strength and flexural behaviour of hybrid fiber reinforced concrete, Mater. Today Proc., in press. source
May combine two claims.
PremisecitationSteel fibers offer good crack-bridging behavior, increasing post-cracking stiffness and residual strength.
“They offer good crack-bridging behavior, and consequently, increase in stiffness during post-cracking stage and great increase in residual strength [18].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [18] Zhou, 2025, Experimental and modelling investigation of stress-strain behavior of basalt fiber-reinforced coral aggregate concrete under uniaxial and triaxial compression, Constr. Build. Mater. source
May combine two claims.
PremisecitationBasalt fiber has shown potential in reinforced concrete beams for better crack control, flexural behavior, and post-cracking behavior.
“Basalt fiber has shown potential in reinforced concrete beam as a promising tool on better control of cracks, better flexural behaviors and post cracking behaviors [26].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [26] Yu, 2022, Experimental study on shear performance of basalt fiber concrete beams without web reinforcement, Case Stud. Constr. Mater. source
Checked before — its earlier verdict is held back until a new check runs.
May combine two claims.
PremisecitationThe tensile strength of concrete is very low, making the tensile zone of a reinforced concrete beam especially susceptible to flexural loading.
“The tensile strength of concrete is very low and therefore the tensile zone of a reinforced concrete beam is especially susceptible to flexural loading [5].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [5] Zheng, 2022, A review of the mechanical properties and durability of basalt fiber-reinforced concrete, Constr. Build. Mater. source
Probably not a substantial claim: may not pass S3 (load-bearing). May combine two claims.
Study design and conductnone givenThe concrete specimens were tested at 28 days both prior to testing the experimental beams and by the time all beam tests were completed.
“The tests to be measured on the concrete specimens were performed at the age of 28 days-both prior to testing of the experimental beams and by the time of all beam tests being completed.”
Quote in the paperNot a substantial claimMay combine two claims.
PremisecitationSteel fibers have high tensile strength and great elastic modulus, making them effective especially in flexural strength and load bearing.
“Steel fibers are commonly described in terms of high tensile strength and great elastic modulus that makes them effective especially in flexural strength as well as load bearing [16,17].”
Quote in the paperSubstantial claim0 of 2 sources checked- cites [16] Shabani, 2025, Flexural and serviceability behaviour of macro-synthetic fibre-reinforced concrete beams reinforced with GFRP bars, Constr. Build. Mater. source
- cites [17] Lang, 2025, Flexural performance of basalt fiber reinforced recycled aggregate concrete subjected to sulfate corrosion, Case Stud. Constr. Mater. source
May combine two claims.
InterpretationreasoningFibers continued to carry loads even after crack formation, increasing concrete strength in initial crack formation.
“The fibers continued to carry loads even after the formation of cracks, that is, they increased the strength of concrete in the initial crack formation.”
Quote in the paperSubstantial claimMay combine two claims.
InterpretationreasoningSteel fibers act as bridges on crack surfaces and effectively resist crack expansion because they have high modulus of elasticity and tensile strength.
“Since steel fibers have a high modulus of elasticity and tensile strength, they act as bridges on the surface of cracks and effectively resist the expansion of cracks.”
Quote in the paperSubstantial claimMay combine two claims.
PremisecitationTraditional RC beams have a sharp transition between elastic and cracked phases, limited energy dissipation capacity, and can collapse abruptly.
“In addition, its stress-strain behavior of the traditional RC beams is that the transition between elastic and cracked phases is sharp and the beam has limited energy dissipation capacity and collapses abruptly in some situations [8].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [8] Jiang, 2014, Experimental study on the mechanical properties and microstructure of chopped basalt fibre reinforced concrete, Mater. Des. source
May combine two claims.
Interpretationown dataFiber addition reduced the width of cracks and retarded crack propagation, thus enhancing load-bearing capacity.
“The fiber addition served well to reduce the width of cracks and retard crack propagation, thus enhancing load-bearing capacity.”
Quote in the paperSubstantial claimMay combine two claims.
PremisecitationFRC beams are more ductile, toughened, and damage-tolerant than traditional RC beams.
“FRC beam is therefore more ductile, toughened and damage-tolerant than the traditional RC beam.”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [14] Shi, 2025, Flexural behavior of steel fiber-reinforced recycled aggregate concrete beam reinforced with hybrid steel and FRP bars, Structures source
May combine two claims.
PremisecitationFibers inhibit micro-crack widening and bridge macrocracks, providing residual tensile capacity and increasing post-cracking stiffness.
“As the micro-cracks commence in the concrete matrix, the fibers which cross the micro-cracks inhibit their cracking and retard the speed at which they widen.As the loading is increased and the cracks evolved to macrocracks, the fibers will continue to bridge the surfaces of the cracks to give the remaining tensile capacity and increase the post-cracking stiffness.”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [14] Shi, 2025, Flexural behavior of steel fiber-reinforced recycled aggregate concrete beam reinforced with hybrid steel and FRP bars, Structures source
May combine two claims.
PremisecitationPolypropylene fibers have relatively low tensile strength and elastic modulus compared to steel fibers.
“Polypropylene fibers on the other hand have relatively low tensile strength and elastic modulus in comparison to steel fibers [20].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [20] Wei, 2023, Behaviour of hybrid polypropylene and steel fibre reinforced ultra-high performance concrete beams against single and repeated impact loading, Structures source
May combine two claims.
InterpretationreasoningBasalt fibers were distributed in the concrete before the formation of microcracks and participated in the distribution of forces.
“They were distributed in the concrete before the formation of microcracks and participated in the distribution of forces.”
Quote in the paperSubstantial claimMay combine two claims.
PremisecitationAfter tensile stress reaches the cracking threshold, discrete cracks develop and propagate very fast, causing stress concentration and loss in stiffness.
“After the tensile stress reaches the cracking threshold, discrete cracks develop and propagate very fast resulting in stress concentration and loss in stiffness [6].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [6] Vairagade, 2023, Hybrid fibre reinforced concrete–A state of the art review, Hybrid Adv. source
May combine two claims.
InterpretationreasoningShort basalt fibers are uniformly spread in the cement matrix, thereby increasing the stress transfer across microcracks.
“This is explained by the fact that short basalt fibers are uniformly spread in the cement matrix, thereby increasing the stress transfer across microcracks.”
Quote in the paperSubstantial claim- Rests on an assumption: Short basalt fibers are uniformly spread in the cement matrix.
May combine two claims.
InterpretationreasoningThe fibers partially absorb the shear forces and disperse local stresses in the transverse section of concrete.
“This can be explained by the fact that the fibers partially absorb the shear forces and disperse local stresses in the transverse section of concrete.”
Quote in the paperSubstantial claim- Rests on an assumption: The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.
May combine two claims.
InterpretationreasoningPolypropylene fibers have a lower modulus of elasticity and thus the contribution to the load-bearing capacity is minimal but still with a positive outcome such as in managing early age cracking and the narrowing of the crack.
“This is in line with the fact that polypropylene fibers have a lower modulus of elasticity and thus the contribution to the load-bearing capacity is minimal but still with a positive outcome such as in managing early age cracking and the narrowing of the crack.”
Quote in the paperSubstantial claimMay combine two claims.
Interpretationown dataDispersed reinforcement increases the strength of beams in the oblique section, reduces the risk of brittle failure, and ensures the reliability of the structure.
“Dispersed reinforcement increases the strength of beams in the oblique section, reduces the risk of brittle failure, and ensures the reliability of the structure.”
Quote in the paperSubstantial claimMay combine two claims.
Interpretationown dataThe high increase in shear cracking load, ultimate load, and stiffness and the lowest crack widths show the excellent ability of steel fibers to break cracks and their strength under tension.
“The high increase in shear cracking load, ultimate load, and stiffness and the lowest crack widths show the excellent ability of steel fibers to break cracks and their strength under tension.”
Quote in the paperSubstantial claim- Rests on an assumption: Steel fibers are the most effective reinforcement in enhancing shear resistance and ductility in reinforced concrete beams.
The paper relies on this without support.
The behavior observed in the 100×200×1200 mm beam specimens under the described shear test is representative of reinforced concrete beams in building applications.
“These results show that dispersed fiber reinforcement that uses steel and basalt fibers is a practical solution to improving the dispersion of concrete in terms of durability and loadbearing capacity.”
The paper relies on this without support.
The measuring device installed along the inclined section accurately measures relative deformations of concrete.
“The relative deformations of the concrete in front of the support of fiber-reinforced concrete and reinforced concrete beams were measured using a measuring device installed along the inclined section.”
The paper relies on this without support.
Short basalt fibers are uniformly spread in the cement matrix.
“short basalt fibers are uniformly spread in the cement matrix”
The paper relies on this without support.
The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.
“The transverse failure occurs mainly due to the formation and development of diagonal cracks in the internal structure of concrete as a result of increased transverse forces or large moments in the beam.”
The paper relies on this without support.
Fibers are crack-bridging fibers that inhibit crack generation and propagation, and increase the overall structure performance of members made of concrete.
“These results closely coincide with those of the past studies, which had indicated that fibers are crack-bridging fibers that inhibit crack generation and propagation, and increase the overall structure performance of members made of concrete.”
The paper relies on this without support.
Moderate levels of fiber work better compared to higher amounts because of their better workability and fiber dispersion.
“More or less the same has been observed in previous studies where moderate levels of fiber were reported to work better compared to higher amounts because of their better workability and fiber dispersion.”
The paper relies on this without support.
Steel fibers are the most effective reinforcement in enhancing shear resistance and ductility in reinforced concrete beams.
“These findings are in line with many other studies that have been carried out in the past and found steel fibers to be the most effective reinforcement in enhancing shear resistance and ductility in reinforced concrete beams.”
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Claim that steel-fiber values are lower than control fails at 25 kN
MajorThe paper says steel-fiber creep indicators were lower than the control's around 20-70 kN. Its 25 kN example gives all three steel-fiber beams greater deflection than the control.
“It was found that at loads around 20÷70 kN, the creep indicators in steel fiber concrete were lower than in concrete without fibers, increasing the internal resistance of the structure.”
“For example, at 25 kN, the deflection in the BS30-3.0sample was 0.470 mm, while in the BS30-2.0 it was 0.418 mm, in the BS30-1.0 it was 0.38 mm, and in the BO-0 it was 0.3 mm (Figure 14).”
Steel-fiber dosages differ by a factor of ten
MinorThe methods describe steel-fiber volume fractions of 1%, 2%, and 3%, but Table 1 lists 0.1%, 0.2%, and 0.3% for the same specimens. This changes which dosages the reported results represent.
“Steel fibers with a length of 30 mm were added to the concrete mixture at volume fractions of 1%, 2%, and 3%.”
“| 14 | S4 | BS30-1.0 | Steel | 30 | 0.1 | 3 | | 15 | | BS30-2.0 | Steel | 30 | 0.2 | 3 | | 16 | | BS30-3.0 | Steel | 30 | 0.3 | 3 |”
Control crack width changes in the conclusions
MinorFor a load of 50-60% of the final or breaking load, the results give the control-beam crack width as approximately 0.37 mm, while the conclusions give 0.30 mm.
“When the breaking load reached 50÷60%, the crack width in ordinary reinforced concrete beams was 0.30 mm.”
“At a load of nearly 50÷60 percent of the final load, the width of the cracks in the control beams was approximately 0.37 mm.”
Fiber tensile-strength comparison reverses Table 2
MinorThe text says basalt and polypropylene fibers have lower tensile strengths than steel fibers. Table 2 instead lists 3500 MPa for basalt and 500 MPa for polypropylene, both above steel's 250 MPa.
“The tensile strength and elastic modulus of basalt and polypropylene fibers are lower than these indicators of steel fibers.”
“| Basalt | 2650 | 3500 | 110 | 10, 30 | 0.017 | | Polypropylene | 910 | 500 | 35 | 10, 30 | 0.018 | | Steel | 7850 | 250 | 200 | 30 | 0.3 |”
Three different cracking loads receive the same specimen ID
MinorConclusion 1 assigns 41.97, 42.12, and 39.06 kN to BB10-0.1. Table 4 assigns those values to BB10-0.1, BB10-0.2, and BB10-0.3, respectively.
“while in the BB10-0.1 sample it occurred at Qcrc=41.97 kN, in the BB10-0.1 sample it occurred at Qcrc=42.12 kN and in the BB10-0.1 sample it occurred at Qcrc=39.06 kN.”
“| S2 | BB10-0.1 | 4.37 | 41.97 | 0.21 | | | BB10-0.2 | 4.46 | 42.12 | 0.19 | | | BB10-0.3 | 4.02 | 39.06 | 0.22 |”
BP30-0.3 is labeled as a steel specimen in Table 4
MinorTable 1 identifies the 30 mm, 0.3% polypropylene specimen as BP30-0.3, but its corresponding row in Table 4 is labeled BS30-0.3.
“| | BS30-0.3 | 3.81 | 38.56 | 0.20 |”
“| 13 | | BP30-0.3 | Polypropylene | 30 | 0.3 | 3 |”
Basalt tensile-strength units conflict
MinorThe materials description gives the basalt-fiber tensile strength as 3500 GPa, while Table 2 gives 3500 MPa.
“Basalt fibers were 2650 kg/m 3 in density, 3500 Gpa in tensile strength, 110 Gpa in elastic modulus, 17 mm in fiber diameter, and 30 mm in length.”
“| Basalt | 2650 | 3500 | 110 | 10, 30 | 0.017 |”
Maximum steel-fiber oblique-cracking load differs
MinorConclusion 1 gives the upper end of the steel-fiber cracking-load range as 54.59 kN. The reported BS30-2.0 value in both the results and Table 4 is 54.42 kN.
“In specimens reinforced with 30 mm long steel fibers added to concrete in the range of 1.0÷3.0%, the initial cracks in the oblique section occurred at Qcrc=48.62÷54.59kN.”
“| | BS30-2.0 | 5.00 | 54.42 | 0.10 |”
Claim of lowest BS30-3.0 creep conflicts with the given example
MinorThe text calls BS30-3.0 the lowest-creep sample in almost all stages, then illustrates the claim with a 25 kN deflection that is higher than every comparator listed.
“The BS30-3.0 sample with 3% steel fiber showed the lowest creep values in almost all stages.”
“For example, at 25 kN, the deflection in the BS30-3.0sample was 0.470 mm, while in the BS30-2.0 it was 0.418 mm, in the BS30-1.0 it was 0.38 mm, and in the BO-0 it was 0.3 mm (Figure 14).”
Cites
Jiang, C., Fan, K., Wu, F., & Chen, D. (2014) · Materials & Design · doi:10.1016/j.matdes.2014.01.056 · Cited by 671 · see citing works
Application of chopped basalt fibers in reinforced mortar: A review
Ralegaonkar, R., Gavali, H., Aswath, P., & Abolmaali, S. (2018) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2017.12.245 · Cited by 197 · see citing works
A review of the mechanical properties and durability of basalt fiber-reinforced concrete
Zheng, Y., Zhang, Y., Zhuo, J., Zhang, Y., & Wan, C. (2022) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2022.129360 · Cited by 172 · see citing works
Fresh, mechanical, and durability properties of basalt fiber-reinforced concrete (BFRC): A review
Al-Rousan, E. T., Khalid, H. R., & Rahman, M. K. (2023) · Developments in the Built Environment · doi:10.1016/j.dibe.2023.100155 · Cited by 104 · see citing works
Chen, X.-F., Kou, S.-C., & Xing, F. (2021) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2021.123901 · Cited by 98 · see citing works
Hybrid fibre reinforced concrete–A state of the art review
Vairagade, V. S., & Dhale, S. A. (2023) · Hybrid Advances · doi:10.1016/j.hybadv.2023.100035 · Cited by 61 · see citing works
Yan, X., Wang, F., Luo, Y., Liu, X., Yang, Z., & Mao, H. (2023) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2023.133935 · Cited by 45 · see citing works
Yousefi, M., Khandestani, R., & Gharaei-Moghaddam, N. (2022) · Structures · doi:10.1016/j.istruc.2022.01.067 · Cited by 32 · see citing works
Gorji Azandariani, M., Vajdian, M., Asghari, K., & Mehrabi, S. (2023) · Composites Part C: Open Access · doi:10.1016/j.jcomc.2023.100410 · Cited by 31 · see citing works
Wei, J., Li, J., Liu, Z., Wu, C., & Liu, J. (2023) · Structures · doi:10.1016/j.istruc.2023.06.036 · Cited by 27 · see citing works
Performance of hybrid basalt-recycled polypropylene fibre reinforced concrete
Chia, E., Nguyen, H., Le, K. N., Bi, K., & Pham, T. M. (2025) · Structures · doi:10.1016/j.istruc.2025.108711 · Cited by 27 · see citing works
An experimental study on mechanical and fracture characteristics of hybrid fibre reinforced concrete
Islam, S. U., & Waseem, S. A. (2024) · Structures · doi:10.1016/j.istruc.2024.107053 · Cited by 24 · see citing works
Mousavi, S. S., & Dehestani, M. (2022) · Structures · doi:10.1016/j.istruc.2022.05.115 · Cited by 23 · see citing works
Liu, Y., Chen, B., Liu, X., Liu, X., Jijun, M., Weng, C., & Luo, Y. (2025) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2025.140944 · Cited by 21 · see citing works
Vedhasakthi, K., & Chithra, R. (2023) · Journal of Building Engineering · doi:10.1016/j.jobe.2023.107592 · Cited by 19 · see citing works
Fracture properties and mechanisms of steel fiber and glass fiber reinforced rubberized concrete
Xiong, Z., Li, H., Pan, Z., Li, X., Lu, L., He, M., Li, H., Liu, F., Feng, P., & Li, L. (2024) · Journal of Building Engineering · doi:10.1016/j.jobe.2024.108866 · Cited by 18 · see citing works
Liu, Q., Cai, L., & Guo, R. (2022) · Structures · doi:10.1016/j.istruc.2022.09.090 · Cited by 15 · see citing works
Mirzaaghabeik, H., Mashaan, N. S., & Shukla, S. K. (2025) · Structures · doi:10.1016/j.istruc.2025.109260 · Cited by 15 · see citing works
Yang, K., Wu, Z., Zheng, K., & Shi, J. (2024) · Structures · doi:10.1016/j.istruc.2024.106339 · Cited by 13 · see citing works
Shabani, H., Asadian, A., & Galal, K. (2025) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2025.143217 · Cited by 11 · see citing works
Zhou, Y., Xiao, J., Deng, Z., Yang, H., Mei, J., & Huang, J. (2025) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2025.143856 · Cited by 11 · see citing works
Silva, D. B., Pachla, E. C., Bolina, F. L., Graeff, Â. G., Lorenzi, L. S., & da Silva Filho, L. C. P. (2024) · Journal of Building Engineering · doi:10.1016/j.jobe.2024.108716 · Cited by 10 · see citing works
Sheikh, N. A., Katkhuda, H. N., & Shatarat, N. K. (2025) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2024.139842 · Cited by 10 · see citing works
Devi Keerthika Esakki, A. K., Karan Aakash Dev, S., Gomathy, T., & Chella Gifta, C. (2023) · Materials Today: Proceedings · doi:10.1016/j.matpr.2023.05.055 · Cited by 8 · see citing works
Shi, K., Gao, Z., & Kang, L. (2025) · Structures · doi:10.1016/j.istruc.2025.109665 · Cited by 8 · see citing works
Impact of reinforcement and geometry of deep beam–Research perspective
Shyamala, G. (2022) · Materials Today: Proceedings · doi:10.1016/j.matpr.2022.07.189 · Cited by 6 · see citing works
Cai, B., Chen, H., Xu, Y., Fan, C., Li, H., & Liu, D. (2024) · Case Studies in Construction Materials · doi:10.1016/j.cscm.2024.e03200 · Cited by 5 · see citing works
Wang, H., Zhou, M. K., Wei, B., Wu, C., Tang, Z., Zhang, S., & He, J. (2025) · Case Studies in Construction Materials · doi:10.1016/j.cscm.2025.e04372 · Cited by 5 · see citing works
Mashayekhi, A., Hassanli, R., Zhuge, Y., Ma, X., Chow, C. W. K., Bazli, M., & Manalo, A. (2025) · Construction and Building Materials · doi:10.1016/j.conbuildmat.2025.140955 · Cited by 5 · see citing works
Liu, Z., Kong, D., Wang, L., Liu, A., Xu, F., Fang, Z., & Wang, S. (2025) · Journal of Building Engineering · doi:10.1016/j.jobe.2025.113879 · Cited by 5 · see citing works
Experimental study on shear performance of basalt fiber concrete beams without web reinforcement
Jianbing, Y., Yufeng, X., Saijie, L., & Zhiqiang, X. (2022) · Case Studies in Construction Materials · doi:10.1016/j.cscm.2022.e01602 · Cited by 3 · see citing works
Muhammad, J. H. (2025) · Case Studies in Construction Materials · doi:10.1016/j.cscm.2025.e05088 · Cited by 3 · see citing works
He, L., Wu, F., Ma, Y., Li, Z., Chen, A., Zhao, B., & Cao, J. (2025) · Engineering Structures · doi:10.1016/j.engstruct.2025.121018 · Cited by 2 · see citing works
Ye, Y., Xie, T., Guo, T., Dong, B., Zhao, J., & Feng, J. (2025) · Journal of Building Engineering · doi:10.1016/j.jobe.2025.114924 · Cited by 2 · see citing works
Lang, W., Chen, W., Xie, Q., Wang, P., & Zhang, G. (2025) · Case Studies in Construction Materials · doi:10.1016/j.cscm.2025.e05156
Flagged first, then by citations
Cited by
Sorted by citations
Numerical modeling of fiber reinforced concrete beams using ANSYS
Kholmirzaev, S., Akhmedov, A. R., Jurayevich, R. S., Martazaev, A., & Juraeva, A. (2026) · Vibroengineering PROCEDIA · doi:10.21595/vp.2026.26364
Self-citationAkkaya, H. C., Şengün, K., Alacali, S., & NİĞDELİOĞLU, A. (2026) · Buildings · doi:10.3390/buildings16183749
Abedini, M., Zhang, C., Zhang, L., & Barmaki, M. (2026) · Innovative Infrastructure Solutions · doi:10.1007/s41062-026-03006-0
- Authors
- Martazaev, A., & Razzakov, S.
- Affiliations
- Namangan davlat texnika universiteti (UZ)
- Department of Construction of Buildings and Structures, Faculty of Construction, Namangan State Technical University, Namangan 160103, Uzbekistan
- Corresponding author
- Martazaev, Abdurasul
- ORCID
- Martazaev, Abdurasul
- Venue
- Construction Materials
- Publisher
- MDPI AG
- Published
- 2026-03-25
- Volume
- 6
- Issue
- 2
- Pages
- 19
- ISSN
- 2673-7108 (ISSN-L)
- OpenAlex
- W7140321195
- Semantic Scholar
- e19c6ae3ec6f82c4ad5d1f0cd3a4a040b076babf
- Cited by
- 3
- References
- 35
- Citations by year
- 2026: 3
- FWCI
- 6.13
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Licence
- Locations
- Construction Materials (publishedVersion, cc-by)
- Preprints.org (acceptedVersion, cc-by)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
- Topics
- Physical Sciences › Engineering › Civil and Structural Engineering › Innovative concrete reinforcement materials
- Physical Sciences › Engineering › Building and Construction › Structural Behavior of Reinforced Concrete
- Physical Sciences › Engineering › Civil and Structural Engineering › Fire effects on concrete materials
- Keywords
- fiber-reinforced concrete, basalt fiber, steel fibers, polypropylene fibers, concrete beams, shear behavior, flexural strength, compressive strength, tensile strength, crack propagation, crack width, fiber volume content, bearing capacity, durability
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Claims read by deepseek-v4.1-flash under definition version 3 (extract-v3) on 2026-11-06.
Classified by jev-1.13-20260917 (gold-guideline-v0.2) on 2026-11-06.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review