Development and Integration of a Digital Twin Model for a Real Hydroelectric Power Plant

Open access
Ersan, Mustafa, Irmak, Erdal · 2024 · Sensors

The DOI matches its Crossref record; 62 of the 62 references it cites were found in a registry or an index; none of the 7 sources its claims cite is checked for support yet.

Abstract

In this study, a digital twin model of a hydroelectric power plant has been created. Models of the entire power plant have been created and malfunction situations of a sensor located after the inlet valve of the plant have been analyzed using a programmable logic controller (PLC). As a feature of the digital twin (DT), the error prediction and prevention function has been studied specifically for the pressure sensor. The accuracy and reliability of the data obtained from the sensor are compared with the data obtained from the DT model. The comparison results are evaluated and erroneous data are identified. In this way, it is determined whether the malfunction occurring in the system is a real malfunction or a malfunction caused by measurement or connection errors. In the case of sensor failure or measurement-related malfunction, this situation is determined through the digital twin-based control mechanism. In the case of actual failure, the system is stopped, but in the case of measurement or connection errors, since the data are calculated by the DT model, the value in the specified region is known and thus there is no need to stop the system. This prevents production loss in the hydroelectric power plant by ensuring the continuity of the system in case of errors.

Overview

CoChat Summary

TL;DR

The paper develops and integrates a digital twin model for a real hydroelectric power plant in Turkey, embedding DT calculations in PLCs to monitor and validate the Unit 1 outlet pressure sensor. It shows the DT can substitute calculated values when sensor data are erroneous, distinguishing measurement/connection errors from real faults and avoiding unnecessary shutdowns.

Key findings

  • The plant is a river-type hydroelectric facility with two units of 2 × 625 kW; pressure values are bounded by a lower limit of 24 bar and an upper limit of 28 bar, with values outside this range considered abnormal.
  • In normal operation, the sensor read 26.5 bar, within range and close to the dt0 value, so the real sensor value was used as output.
  • When sensor data decreased to 1 bar, the system selected the DT value (dt0) as output because the real value was inaccurate, continuing energy supply without output oscillation; other tests selected dt1 or dt2 when they had the lowest error.
  • When all dt values and the sensor value sequentially dropped to 0, the system treated it as a large-scale failure and isolated the plant from the main grid until resolved; after sensor repair, the system reverted to real sensor data.

Methods

  • Design: A DT model of a real hydroelectric power plant in Turkey was built with physical, operational, and functional dimensions; the full model combines sub-digital twins, but the paper details the Unit 1 outlet pressure sensor after the inlet valve as a case.
  • Data/infrastructure: The plant uses PLCs and SCADA; data are retrieved via Modbus TCP/IP, with OPC UA for SCADA integration. Three DT calculation methods (dt0, dt1, dt2) use different algorithms/data sources, including dam level, pre-inlet pressures, fluid density, and gravitational acceleration.
  • Analysis: Control algorithms filter and smooth dt values, compare errors against reference limits, select the dt value closest to zero error, and decide whether to output the real sensor value, manual value, or DT value; a Petri Net models fault detection and decision-making. Experimental tests covered normal operation, sensor faults, recovery, and plant-wide failure.

Limitations

  • Paper states: the DT scope primarily focuses on specific components and sensors; expanding to more components/systems would provide a more comprehensive view.
  • Paper states: the current implementation lacks comprehensive integration of historical and external data sources, and PLCs are not inherently designed for extensive data storage, making data management/analysis cumbersome; future work should add API/database integration.
  • Paper states: interoperability and cybersecurity are not fully robust; also, the study exhibits 3D and 4D DT characteristics but does not fully achieve 5D predictive–prescriptive analytics and autonomous control. Evident from text: the full DT model was too complex to explain entirely, so only one sub-digital twin is detailed.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

Crossref · 10.3390/s24134174

Cites

62 of 62 references verified0 citation errors · 0 not checkable

Statistics

Nothing to recompute.

Figures

Figure 1 Basic structure of the digital twin model used in this study.
Figure 1 Basic structure of the digital twin model used in this study.CC BY · PubMed Central
Figure 2 Process and instrumentation diagram of the plant.
Figure 2 Process and instrumentation diagram of the plant.CC BY · PubMed Central
Figure 3 Automation topology of the plant, showing the network of PLCs and SCADA system used for monitoring and controlling the operations.
Figure 3 Automation topology of the plant, showing the network of PLCs and SCADA system used for monitoring and controlling the operations.CC BY · PubMed Central
Figure 4 Automation infrastructure of the power plant.
Figure 4 Automation infrastructure of the power plant.CC BY · PubMed Central
Figure 5 Comprehensive DT model of the plant, showing the integration of the sub-models and their interrelationships.
Figure 5 Comprehensive DT model of the plant, showing the integration of the sub-models and their interrelationships.CC BY · PubMed Central
Figure 6 Data flow diagram for the DT model focusing on the outlet pressure sensor.
Figure 6 Data flow diagram for the DT model focusing on the outlet pressure sensor.CC BY · PubMed Central
Figure 7 Data flow diagram of the DT.
Figure 7 Data flow diagram of the DT.CC BY · PubMed Central
Figure 8 Checking algorithm for the DT variables.
Figure 8 Checking algorithm for the DT variables.CC BY · PubMed Central
Figure 9 Checking algorithm for the out variable.
Figure 9 Checking algorithm for the out variable.CC BY · PubMed Central
Figure 10 Diagram of the control and selection algorithm.
Figure 10 Diagram of the control and selection algorithm.CC BY · PubMed Central
Figure 11 Petri Net diagram of the selection algorithm.
Figure 11 Petri Net diagram of the selection algorithm.CC BY · PubMed Central
Figure 12 Normal operation of the system.
Figure 12 Normal operation of the system.CC BY · PubMed Central
Figure 13 Dt0 is selected as the output due to sensor inaccuracy.
Figure 13 Dt0 is selected as the output due to sensor inaccuracy.CC BY · PubMed Central
Figure 14 Real-time changes in the sensor and DT0 values when the sensor drops to 1 bar.
Figure 14 Real-time changes in the sensor and DT0 values when the sensor drops to 1 bar.CC BY · PubMed Central
Figure 15 Dynamic selection of Dt1 as the output due to its smallest error.
Figure 15 Dynamic selection of Dt1 as the output due to its smallest error.CC BY · PubMed Central
Figure 16 Values when Dt2 is used as the output.
Figure 16 Values when Dt2 is used as the output.CC BY · PubMed Central
Figure 17 System using Dt2 as the output despite the sensor value increase.
Figure 17 System using Dt2 as the output despite the sensor value increase.CC BY · PubMed Central
Figure 18 Incorrect sensor measurement (1.0 bar) causing the Dt0 output.
Figure 18 Incorrect sensor measurement (1.0 bar) causing the Dt0 output.CC BY · PubMed Central
Figure 19 System normalizes with the ‘Calc. Mod’ as the ‘Real Value’.
Figure 19 System normalizes with the ‘Calc. Mod’ as the ‘Real Value’.CC BY · PubMed Central
Figure 20 Variables during the transition to normal operation.
Figure 20 Variables during the transition to normal operation.CC BY · PubMed Central
Figure 21 Sequential reduction of all the DT values to 0, followed by the sensor value dropping to 0.
Figure 21 Sequential reduction of all the DT values to 0, followed by the sensor value dropping to 0.CC BY · PubMed Central
Figure 22 Sequential reduction of dt0, dt1, and dt2 to 0.
Figure 22 Sequential reduction of dt0, dt1, and dt2 to 0.CC BY · PubMed Central
Figure 23 An example of a real water leakage.
Figure 23 An example of a real water leakage.CC BY · PubMed Central
Figure 24 Application example of the turbine speed.
Figure 24 Application example of the turbine speed.CC BY · PubMed Central
Figure 25 Application example of the active power.
Figure 25 Application example of the active power.CC BY · PubMed Central
Figure 26 Application example of the Unit 1 generator current.
Figure 26 Application example of the Unit 1 generator current.CC BY · PubMed Central
Figure 27 Application example of the Unit 1 frequency.
Figure 27 Application example of the Unit 1 frequency.CC BY · PubMed Central

Verification

Claims the paper makes

0 Valid · 10 Not valid · 6 Not checked · 95 Own results and interpretations

40 more claims

Create a free account to see all 111 claims and to verify the 7 references still open.

See all claims — free account
  • Probably not a substantial claim. 37
  • It may state two separate claims as one. 36
  • The quote only partly states this claim. 2

Create a free account to see these claims.

Self-check

Percentages, sums and reported differences re-computed from the paper’s own numbers.

Each contradiction between two passages listed here was confirmed by an independent check.

3 of 3

Citations

Cites

Show all 62 references

Cited by

See all 48

Metadata

Authors
Ersan, M., & Irmak, E.
Affiliations
Gazi University (TR)
Corresponding author
Irmak, Erdal
Venue
Sensors
Publisher
MDPI AG
Published
2024-06-27
Volume
24
Issue
13
Pages
4174
ISSN
1424-8220 (ISSN-L)
OpenAlex
W4400093273
Cited by
48
References
60
Citations by year
2026: 30 · 2025: 16 · 2024: 2
FWCI
6.23
Type
journal article
Language
en
Open access
Locations
  • Sensors (publishedVersion, cc-by)
  • PubMed Central (publishedVersion, cc-by)
  • PubMed (publishedVersion)
  • DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion)
Topics
  • Physical Sciences › Engineering › Industrial and Manufacturing Engineering › Digital Transformation in Industry
  • Physical Sciences › Engineering › Control and Systems Engineering › Fault Detection and Control Systems
  • Physical Sciences › Engineering › Control and Systems Engineering › Industrial Automation and Control Systems
Keywords
digital twin, hydroelectric power plant, programmable logic controller, inlet valve, measurement error detection, fault diagnosis, power plant control

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

A language model drew the claims from the paper on 2026-11-29, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).

A second model labelled each claim on 2026-11-29 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.