Continuous measurements of air change rates in an occupied house for 1 year: The effect of temperature, wind, fans, and windows
The DOI matches its Crossref record; 19 of the 19 references it cites were found in a registry or an index.
Abstract
A year-long investigation of air change rates in an occupied house was undertaken to establish the effects of temperature, wind velocity, use of exhaust fans, and window-opening behavior. Air change rates were calculated by periodically injecting a tracer gas (SF(6)) into the return air duct and measuring the concentration in 10 indoor locations sequentially every minute by a gas chromatograph equipped with an electron capture detector. Temperatures were also measured outdoors and in the 10 indoor locations. Relative humidity (RH) was measured outdoors and in five indoor locations every 5 min. Wind speed and direction in the horizontal plane were measured using a portable meteorological station mounted on the rooftop. Use of the thermostat-controlled attic fan was recorded automatically. Indoor temperatures increased from 21 degrees C in winter to 27 degrees C in summer. Indoor RH increased from 20% to 70% in the same time period. Windows were open only a few percent of the time in winter but more than half the time in summer. About 4600 hour-long average air change rates were calculated from the measured tracer gas decay rates. The mean (SD) rate was 0.65 (0.56) h(-1). Tracer gas decay rates in different rooms were very similar, ranging only from 0.62 to 0.67 h(-1), suggesting that conditions were well mixed throughout the year. The strongest influence on air change rates was opening windows, which could increase the rate to as much as 2 h(-1) for extended periods, and up to…
Overview
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
In the citing paper
“which are irritants to the eyes, mucous membranes and upper respiratory tract [60, 80, 81].”
From Occupational exposure and health risks of volatile organic compounds of hotel housekeepers: Field measurements of exposure and health risks (2021) · cites this paper as [80]
Citations
Cites
Building ventilation: theory and measurement
(1997) · Choice Reviews Online · doi:10.5860/choice.35-2135 · Cited by 734 · cited 1×
“Instead, the observed slope will have a positive bias with respect to the air change rate, the magnitude of the bias being dependent on the amount of Journal of Exposure Analysis and Environmental Epidemiology (2002) 12(4) 301 interzonal flow (Etheridge and Sandberg, 1996).”
BackgroundMurray, D. M., & Burmaster, D. E. (1995) · Risk Analysis · doi:10.1111/j.1539-6924.1995.tb00338.x · Cited by 250 · cited 2×
“Air change rates have been measured in several thousand homes in the US (Murray and Burmaster, 1995), but most of these were one- time measurements made over short periods of 12 h to several weeks, making it impossible to determine the effects on air change rates of weather conditions and homeowner behavior such as wi…”
BackgroundThe Effect of Opening Windows on Air Change Rates in Two Homes
Howard-Reed, C., Wallace, L. A., & Ott, W. R. (2002) · Journal of the Air & Waste Management Association · doi:10.1080/10473289.2002.10470775 · Cited by 218 · cited 5×
“One recent study has provided quantitative information on the effect in two homes of opening windows to measured widths (Howard-Reed et al., 2002), but may have lacked sufficient measurements to derive a robust relationship with temperature and wind.”
BackgroundResultInfluentialSelf-citationRadon transport into a detached one-story house with a basement
Nazaroff, W. W., Feustel, H. E., Nero, A. V., Revzan, K. L., Grimsrud, D. T., Essling, M. A., & Toohey, R. E. (1985) · Atmospheric Environment (1967) · doi:10.1016/0004-6981(85)90134-9 · Cited by 111 · cited 2×
“A positive intercept of similar magnitude (0.13–0.16 h 1) for a multiple regression including wind speed and either pressure or temperature difference was also noted in the study of Nazaroff et al. (1985) (our calculations based on their Table 2) .”
BackgroundResultInfluentialVentilation Research in Occupied Houses.
Dick, J. B., & Thomas, D. (1951) · Cited by 56
Measured Air Leakage of Buildings
Trechsel, H., & Lagus, P. L. (1986) · doi:10.1520/stp904-eb · Cited by 38 · cited 1×
“Two ASTM publications (Hunt et al., 1980; Trechsel and Lagus, 1986) provide convenient collections of papers on air leakage measurements.”
BackgroundThe Fundamentals of Natural Ventilation of Houses.
Dick, J. B. (1950) · Cited by 30
Field studies of dependence of air infiltration on outside temperature and wind
Malik, N. (1978) · Energy and Buildings · doi:10.1016/0378-7788(78)90008-7 · Cited by 27 · cited 2×
“Many find no effect of wind direction, but others (Malik, 1978) find that direction is important.”
BackgroundField measurements of air infiltration in ten elec-trically-heated houses.
Coblentz, C. W., & Achenbach, P. (1963) · Cited by 26
Measurement and simulation of the IAQ impact of particle air cleaners in a single-zone building
Emmerich, S. J., & Nabinger, S. J. (2000) · doi:10.6028/nist.ir.6461 · Cited by 24
Self-citation
Research works printed but not linked: 3
- Bahnfleth DR Moseley TT Harris WS Measurement of infiltration in two residences: Part I. Technique and measured infiltration, ASHRAE Trans (1957) 63: 453–476
- Lagus PL Air leakage measurements by the tracer dilution method In: Hunt C.M., King J.C., and Trechsel H.R. (Eds.) Building Air Change Rate and Infiltration Measurements, STP 719. American Society for Testing and Materials, Philadelphia, PA 1980 pp 16–49
- Laschober RR Healy JH Statistical analyses of air leakage in split-level residences, ASHRAE Trans (1964) 70: 364–374
Cited by
Identifying airborne transmission as the dominant route for the spread of COVID-19
Zhang, R., Li, Y., Zhang, A. L., Wang, Y., & Molina, M. J. (2020) · Proceedings of the National Academy of Sciences · doi:10.1073/pnas.2009637117 · Cited by 1,236
Fabi, V., Andersen, R. V., Corgnati, S., & Olesen, B. W. (2012) · Building and Environment · doi:10.1016/j.buildenv.2012.07.009 · Cited by 659
“[74] measured air change rates in a house in Virginia during a year, they found that the window opening behaviour had the largest effect on air change rates, causing increases ranging from a few tenths of an air change per hour to approximately two air changes per hour.”
BackgroundNguyen, J. L., Schwartz, J., & Dockery, D. W. (2014) · Indoor Air · doi:10.1111/ina.12052 · Cited by 410
“N IH -PA Author M anuscript N IH -PA Author M anuscript N IH -PA Author M anuscript example, windows are more likely to be opened for extended periods of time when the outside temperature is moderate (Wallace et al., 2002).”
BackgroundMethodInfluentialLaidlaw, M. A. S., & Filippelli, G. M. (2008) · Applied Geochemistry · doi:10.1016/j.apgeochem.2008.05.009 · Cited by 325
Window opening behaviour modelled from measurements in Danish dwellings
Andersen, R., Fabi, V., Toftum, J., Corgnati, S. P., & Olesen, B. W. (2013) · Building and Environment · doi:10.1016/j.buildenv.2013.07.005 · Cited by 300
Metadata
- Authors
- WALLACE, L. A., EMMERICH, S. J., & HOWARD-REED, C.
- Affiliations
- Environmental Protection Agency (US)
- National Institute of Standards and Technology (US)
- Corresponding author
- WALLACE, L A
- Venue
- Journal of Exposure Science & Environmental Epidemiology
- Published
- 2002-06-28
- Volume
- 12
- Issue
- 4
- Pages
- 296-306
- ISSN
- 1559-0631 (ISSN-L)
- 1559-064X
- OpenAlex
- W2067182986
- Semantic Scholar
- babd7df8b55b7dc377cad9f36becf006b33b8122
- Cited by
- 260
- References
- 19
- Citations by year
- 2026: 4 · 2025: 12 · 2024: 8 · 2023: 9 · 2022: 19 · 2021: 18 · 2020: 18 · 2019: 23 · 2018: 20 · 2017: 14 · 2016: 8 · 2015: 18 · 2014: 19 · 2013: 14 · 2012: 10
- FWCI
- 3.32
- Type
- journal article
- Language
- en
- Open access
- closed
- Licence
- www.springer.com/tdm (tdm)
- www.springer.com/tdm (vor)
- Locations
- Journal of Exposure Science & Environmental Epidemiology (publishedVersion)
- PubMed (publishedVersion)
- Topics
- Physical Sciences › Environmental Science › Health, Toxicology and Mutagenesis › Indoor Air Quality and Microbial Exposure
- Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
- Physical Sciences › Environmental Science › Environmental Engineering › Wind and Air Flow Studies
- Keywords
- occupied houses, window openings, exhaust fan, indoor-outdoor temperature difference, wind speed, indoor humidity, sulfur hexafluoride, indoor air mixing
- MeSH terms
- Air Movements, Environmental Exposure, Environmental Monitoring, Gases, Housing, Humans, Humidity, Reference Values, Temperature, Ventilation, Wind, Air Pollution, Indoor
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: Continuous measurements of air change rates in an occupied house for 1 year: The effect of temperature, wind, fans, and windows. https://app.cochat.ai/papers/10.1038/sj.jea.7500229
- The paper
- WALLACE, L. A., EMMERICH, S. J., & HOWARD-REED, C. (2002). Continuous measurements of air change rates in an occupied house for 1 year: The effect of temperature, wind, fans, and windows. Journal of Exposure Science & Environmental Epidemiology. https://doi.org/10.1038/sj.jea.7500229
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.