The DOI matches its Crossref record; 31 of the 31 references it cites were found in a registry or an index; none of the 15 sources its claims cite is checked for support yet.
Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network
Open accessAbstract
Electrification of the transportation sector can play a vital role in reshaping smart cities. With an increasing number of electric vehicles (EVs) on the road, deployment of well-planned and efficient charging infrastructure is highly desirable. Unlike level 1 and level 2 charging stations, level 3 chargers are super-fast in charging EVs. However, their installation at every possible site is not techno-economically justifiable because level 3 chargers may cause violation of critical system parameters due to their high power consumption. In this paper, we demonstrate an optimized combination of all three types of EV chargers for efficiently managing the EV load while minimizing installation cost, losses, and distribution transformer loading. Effects of photovoltaic (PV) generation are also incorporated in the analysis. Due to the uncertain nature of vehicle users, EV load is modeled as a stochastic process. Particle swarm optimization (PSO) is used to solve the constrained nonlinear stochastic problem. MATLAB and OpenDSS are used to simulate the model. The proposed idea is validated on the real distribution system of the National University of Sciences and Technology (NUST) Pakistan. Results show that an optimized combination of chargers placed at judicious locations can greatly reduce cost from $3.55 million to $1.99 million, daily losses from 787kWh to 286kWh and distribution transformer congestion from 58% to 22% when compared to scenario of optimized placement of level 3 chargers for 20% penetration level in commercial feeders. In residential feeder, these statistics are improved from $2.52 to $0.81 million, from 2167kWh to 398kWh and from 106% to 14%, respectively. It is also realized that the integration of PV improves voltage profile and reduces the negative impact of EV load. Our optimization model can work for commercial areas such as offices, university campuses, and industries as well as residential colonies.
Overview
CoChat Summary
TL;DR
This paper optimizes the placement and mix of Level 1, Level 2, and Level 3 EV chargers in an active distribution network using particle swarm optimization, stochastic EV load modeling, and PV generation. Tested on the NUST Pakistan distribution system, the optimized mix reduces cost, daily losses, and transformer congestion compared with optimized Level 3-only placement.
Key findings
- In commercial feeders at 20% EV penetration, the optimized charger mix reduced cost from $3.55 million to $1.99 million, daily losses from 787 kWh to 286 kWh, and distribution transformer congestion from 58% to 22% compared with optimized Level 3-only placement.
- In the residential feeder, the same comparison improved cost from $2.52 million to $0.81 million, daily losses from 2167 kWh to 398 kWh, and transformer utilization from 106% to 14%.
- Loss reductions for the proposed solution versus Level 3 chargers were 37% (45%) at 5% penetration in commercial (residential) feeders, 54% (63%) at 10% (20%) in commercial feeders, and 61% (82%) at 10% (20%) in the residential feeder.
- PV integration improved voltage profile: at peak load, voltage improvement was 0.001 per unit at node 20 and 0.005 per unit at node 24; node 41 dropped to 0.93 per unit without PV. The proposed solution maintained commercial feeder voltage above 0.94 per unit for all studied penetration levels and residential voltage at 0.99 per unit, while Level 3 chargers caused residential voltage to drop below 0.975 per unit at peak for 20% penetration.
Methods
- EV load was modeled stochastically from a 300-sample survey of arrival time, departure time, and traveled distance; probability distributions were fitted in MATLAB, and initial state of charge was related to traveled distance. PV generation was modeled using real insolation and temperature data.
- The optimization objective minimized charger installation cost, parking-availability penalty, and power-loss cost at $0.092/kWh, subject to voltage limits (±10%), thermal limits, charging capacity, charger-number limits, integer charger counts, and a customer-satisfaction constraint requiring charge above 80% within available time. PSO was implemented in MATLAB and coupled with OpenDSS for unbalanced distribution power flow.
- The test system was the real 11/0.4 kV radial distribution network of NUST, Islamabad, Pakistan, with three feeders (Feeders 1 and 2 commercial, Feeder 3 residential). The EV modeled was a Nissan Altra with a 29.07 kWh Li-ion battery and about 80-mile range; PV included 200 kW at node 19 of Feeder 1 and 1 MW at node 24 of Feeder 2.
Limitations
- The paper states that PSO is a heuristic technique and can get stuck in local optima; to mitigate this, PSO was run multiple times and results analyzed statistically, which increases computational burden.
- The paper states that vehicle-to-grid (V2G) is not considered, and the maximum number of chargers per node is based on an assumed physical limit of 3 allowable parking slots per location.
- Evident from the text: the EV load model relies on a 300-person survey and one real distribution system (NUST Pakistan), and simulations use one EV type (Nissan Altra), which may limit generalizability to other locations, populations, and vehicle fleets.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Figures



















Verification
Claims the paper makes
0 Valid · 6 Not valid · 14 Not checked · 62 Own results and interpretations
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“In residential feeder, these statistics are improved from $2.52 to $0.81 million, from 2167kWh to 398kWh and from 106% to 14%, respectively.”
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > Abstract
plainstates a causeSingle case- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“In case of residential feeder, the proposed solutions offer 61% (82%) less losses than level 3 chargers for 10% (20%) penetration.”
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > III. RESULTS
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“In addition, the losses are around 37% (45%) less than level 3 chargers in commercial (residential) feeder for 5% penetration level of EV, as shown in Figure 7.”
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > III. RESULTS
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“This is because residential feeders are low power feeders and level 3 chargers can increase its losses significantly and may overload certain transformers.”
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > III. RESULTS
plainstates a cause- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“To charge EVs using level 1 and level 2 chargers, the number of chargers needed is approximately equal to the number of vehicles to be charged daily.”
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > III. RESULTS
hedgedstates an association- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Rests on an assumption not shown here.
45 more claims
Create a free account to see all 82 claims and to verify the 2 references still open.
- The quote only partly states this claim. 3
- It may state two separate claims as one. 17
- Probably not a substantial claim. 14
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
The source backs part of the claim, not all of it — or backs it for a different population, condition or comparison.
In the citing paper
“As a result, fast charging in the EVCSs is viable for charging an EV's battery in 20-30 min Zeb et al. (2020).”
From Optimal location of electric vehicle charging station and its impact on distribution network: A review (2022) · cites this paper as Zeb et al., 2020
Experimental — accuracy not yet measuredThe cited source says what the claim attributes to it.
In the citing paper
“Therefore, most of the researchers have included power loss cost (Shukla et al., 2019;Zeb et al., 2020;Chen et al., 2021b;Moradi et al., 2015;Pal et al., 2021;Gampa et al., 2020;El-Zonkoly and Dos Santos Coelho, 2015;Battapothula et al., 2019a;Xiang et al., 2016) as the objective function in Eq. ( 7)”
From Optimal location of electric vehicle charging station and its impact on distribution network: A review (2022) · cites this paper as Zeb et al., 2020
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > III. RESULTS
“In addition, the losses are around 37% (45%) less than level 3 chargers in commercial (residential) feeder for 5% penetration level of EV, as shown in Figure 7.”
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > IV. CONCLUSION
“FIGURE 7. Cost of installation of charging stations for level 3 chargers and proposed solution.”
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > C. PROBLEM FORMULATION
“n 1,i + n 2,i + n 2,i ≤ n max,i ∀i ∈ N (7”
§ Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network > C. PROBLEM FORMULATION
“The limited charger number constraint ensures that total number of chargers at a node is less than the pre-determined feasible charging slots available for EV in a given location.”
Citations
Cites
Yilmaz, M., & Krein, P. T. (2013) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2012.2212917 · Cited by 3,118 · cited 1×
“However, level 2 chargers require protection upgrade if used inside a residential house [18].”
BackgroundModeling of Load Demand Due to EV Battery Charging in Distribution Systems
Qian, K., Zhou, C., Allan, M., & Yuan, Y. (2011) · IEEE Transactions on Power Systems · doi:10.1109/tpwrs.2010.2057456 · Cited by 1,268 · cited 1×
“When fully charged, its maximum range is around 80 miles [4].”
BackgroundCoordinated Charging of Plug-In Hybrid Electric Vehicles to Minimize Distribution System Losses
Sortomme, E., Hindi, M. M., MacPherson, S. D. J., & Venkata, S. S. (2011) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2010.2090913 · Cited by 1,155 · cited 2×
“A solution is proposed in [8] to lower distribution system losses by coordinated charging scheme.”
BackgroundOptimal Planning of Electric-Vehicle Charging Stations in Distribution Systems
Liu, Z., Wen, F., & Ledwich, G. (2013) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2012.2223489 · Cited by 672
The impact of plug-in hybrid electric vehicles on distribution networks: A review and outlook
Green, R. C., Wang, L., & Alam, M. (2011) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2010.08.015 · Cited by 640 · cited 1×
“ηch is charging efficiency (92%) [26], Cev is EV charging power which is determined by the type of charger, SOCinit is the initial state of charge which can be in the range of 0-1 and 1tch is available time of charging.”
BackgroundOptimal fast charging station placing and sizing
Sadeghi-Barzani, P., Rajabi-Ghahnavieh, A., & Kazemi-Karegar, H. (2014) · Applied Energy · doi:10.1016/j.apenergy.2014.03.077 · Cited by 557 · cited 1×
“A comprehensive plan for optimally locating and sizing fast-charging stations on urban roads is presented in [21].”
BackgroundMasoum, A. S., Deilami, S., Moses, P. S., Masoum, M. A. S., & Abu-Siada, A. (2011) · IET Generation, Transmission & Distribution · doi:10.1049/iet-gtd.2010.0574 · Cited by 440 · cited 3×
“The maximum and minimum voltage limit constraint ensures voltage lies within permissible limits (±10%) [9].”
BackgroundA review on electric vehicles interacting with renewable energy in smart grid
Liu, L., Kong, F., Liu, X., Peng, Y., & Wang, Q. (2015) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2015.06.036 · Cited by 314 · cited 1×
“By 2022, the number of EVs is expected to surpass 35 million globally [2].”
BackgroundFazelpour, F., Vafaeipour, M., Rahbari, O., & Rosen, M. A. (2014) · Energy Conversion and Management · doi:10.1016/j.enconman.2013.09.006 · Cited by 257 · cited 1×
“Similarly, the ability of solar photovoltaic generation to improve voltage profile has been used to reduce negative impacts of EV parking in [17].”
BackgroundUnbalanced Model and Power-Flow Analysis of Microgrids and Active Distribution Systems
Kamh, M. Z., & Iravani, R. (2010) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2010.2042825 · Cited by 208 · cited 1×
“These include Forward/Backward sweep method and its variants [29], [30] and some novel techniques as presented in [27], [28], [31].”
Method
Research works printed but not linked: 3
- Atlas, 2020, Tier 1 Solar Measurement Site in NUST Islamabad Pakistan
- Company, 2019, Tariff Guide
- Dugan, 2017, OpenDSS Circuit Solution Technique
Cited by
Ahmad, F., Iqbal, A., Ashraf, I., Marzband, M., & khan, I. (2022) · Energy Reports · doi:10.1016/j.egyr.2022.01.180 · Cited by 533
“Therefore, active power loss cost [ 5, 10, 14, 15, 17, 20, 35, 36 ] , reactive power loss cost, voltage deviation cost [ 10, 14, 17, 26, 37, 38 ] , reliability cost [ 30, 38 ] and stability cost [ 39 ] of the distribution system are optimized to the placement of EVCSs under the DNO approach.”
InfluentialReview of Positive and Negative Impacts of Electric Vehicles Charging on Electric Power Systems
Nour, M., Chaves-Ávila, J. P., Magdy, G., & Sánchez-Miralles, Á. (2020) · Energies · doi:10.3390/en13184675 · Cited by 302
“The studies considered the optimal location and capacity of EV chargers [163].”
BackgroundYuvaraj, T., Devabalaji, K. R., Kumar, J. A., Thanikanti, S. B., & Nwulu, N. I. (2024) · IEEE Access · doi:10.1109/access.2023.3349274 · Cited by 249
Wang, J., Zhu, K., & Hossain, E. (2022) · IEEE Transactions on Green Communications and Networking · doi:10.1109/tgcn.2021.3127923 · Cited by 218
İnci, M., Savrun, M. M., & Çelik, Ö. (2022) · Journal of Energy Storage · doi:10.1016/j.est.2022.105579 · Cited by 207
Metadata
- Authors
- Zeb, M. Z., Imran, K., Khattak, A., Janjua, A. K., Pal, A., Nadeem, M., Zhang, J., & Khan, S.
- Affiliations
- National University of Sciences and Technology (PK)
- Arizona State University (US)
- Clemson University (US)
- AIT Austrian Institute of Technology GmbH (AT)
- ORCID
- Venue
- IEEE Access
- Published
- 2020
- Volume
- 8
- Pages
- 68124-68134
- ISSN
- 2169-3536 (ISSN-L)
- OpenAlex
- W3015098507
- Cited by
- 263
- References
- 28
- Citations by year
- 2026: 37 · 2025: 47 · 2024: 64 · 2023: 55 · 2022: 34 · 2021: 23 · 2020: 3
- FWCI
- 9.86
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Locations
- IEEE Access (publishedVersion, cc-by)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
- Funders
- Arizona State University
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Electric Vehicles and Infrastructure
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Optimal Power Flow Distribution
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Smart Grid Energy Management
- Keywords
- electric vehicle charging stations, charging station location, active distribution networks, photovoltaic integration, particle swarm optimization, distribution transformer loading, power losses, installation cost minimization, voltage profile, OpenDSS
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
A language model drew the claims from the paper on 2026-10-28, under version 3 of the claim definition (model deepseek-v4.1-flash, prompt extract-v3).
A second model labelled each claim on 2026-10-28 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network. https://app.cochat.ai/papers/10.1109/access.2020.2984127
- The paper
- Zeb, M. Z., Imran, K., Khattak, A., Janjua, A. K., Pal, A., Nadeem, M., Zhang, J., & Khan, S. (2020). Optimal Placement of Electric Vehicle Charging Stations in the Active Distribution Network. IEEE Access. https://doi.org/10.1109/access.2020.2984127
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.