Summary of human responses to ventilation
Open accessThe DOI matches its Crossref record; 49 of the 49 references it cites were found in a registry or an index.
Abstract
UNLABELLED: It is known that ventilation is necessary to remove indoor-generated pollutants from indoor air or dilute their concentration to acceptable levels. But as the limit values of all pollutants are not known the exact determination of required ventilation rates based on pollutant concentrations is seldom possible. The selection of ventilation rates has to be based also on epidemiological research, laboratory and field experiments and experience. The existing literature indicates that ventilation has a significant impact on several important human outcomes including: (1) communicable respiratory illnesses; (2) sick building syndrome symptoms; (3) task performance and productivity, and (4) perceived air quality (PAQ) among occupants or sensory panels (5) respiratory allergies and asthma. In many studies, prevalence of sick building syndrome symptoms has also been associated with characteristics of HVAC-systems. Often the prevalence of SBS symptoms is higher in air-conditioned buildings than in naturally ventilated buildings. The evidence suggests that better hygiene, commissioning, operation and maintenance of air handling systems may be particularly important for reducing the negative effects of HVAC systems. Ventilation may also have harmful effects on indoor air quality and climate if not properly designed, installed, maintained and operated. Ventilation may bring indoors harmful substances or deteriorate indoor environment. Ventilation interacts also with the building envelope and may deteriorate the structures of the building. Ventilation changes the pressure differences across the structures of building and may cause or prevent infiltration of pollutants from structures or adjacent spaces. Ventilation is also in many cases used to control the thermal environment or humidity in buildings. The paper summarises the current knowledge on positive and negative effects of ventilation on health and other human responses. The focus is on office-type working environment and residential buildings. PRACTICAL IMPLICATIONS: The review shows that ventilation has various positive impacts on health and productivity of building occupants. Ventilation reduces the prevalence of airborne infectious diseases and thus the number of sick leave days. In office environment a ventilation rate up to 20-25 L/s per person seem to decrease the prevalence of SBS-symptoms. Air conditioning systems may increase the prevalence of SBS-symptoms relative to natural ventilation if not clean. In residential buildings the air change rate in cold climates should not be below app. 0.5 ach. Ventilation systems may cause pressure differences over the building envelope and bring harmful pollutants indoors.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Ventilation for Acceptable Indoor Air Quality
Falih, M. (2019) · Cited by 2,497
Guidelines for community noise
Berglund, B., Lindvall, T., & Schwela, D. (1999) · Cited by 1,693
Jones, A. P. (1999) · Atmospheric Environment · doi:10.1016/s1352-2310(99)00272-1 · Cited by 1,481 · cited 6×
“Several studies have been performed on the effect of improved ventilation with or without dehumidification on the population of dust mites in residences (Chivato et al., 1997, Crane et al., 1998, Jones, 1999, Harving et al., 1993, Niven et al., 1999, Warner et al., 2000).”
BackgroundInfluentialSeppanen, O. A., Fisk, W. J., & Mendell, M. J. (1999) · Indoor Air · doi:10.1111/j.1600-0668.1999.00003.x · Cited by 876 · cited 8×
“Control of CO2 is the same as to control ventilation (Seppänen et al.,1999).”
BackgroundMethodInfluentialSelf-citationWARGOCKI, P., WYON, D. P., SUNDELL, J., CLAUSEN, G., & FANGER, P. O. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004222.x · Cited by 688
Bornehag, C.-G., Blomquist, G., Gyntelberg, F., Järvholm, B., Malmberg, P., Nordvall, L., Nielsen, A., Pershagen, G., & Sundell, J. (2001) · Indoor Air · doi:10.1034/j.1600-0668.2001.110202.x · Cited by 659 · cited 1×
“…microbial growth in buildings have been associated with a number of health effects including respiratory symptoms and diseases and other symptoms (Bornehag et al., 2001, Nevalainen 2002); although, the evidence of a direct link between higher air humidity levels and adverse health is quite…”
BackgroundSpengler, J. D., McCarthy, J. F., & Samet, J. M. (2000) · Cited by 574
Impact of Temperature and Humidity on the Perception of Indoor Air Quality
Fang, L., Clausen, G., & Fanger, P. O. (1998) · Indoor Air · doi:10.1111/j.1600-0668.1998.t01-2-00003.x · Cited by 534 · cited 2×
“Laboratory experiments (Fang et al., 1998) have suggested that perceived quality of polluted air depends on the enthalpy of the air.”
BackgroundAssociations between classroom CO2 concentrations and student attendance in Washington and Idaho
Shendell, D. G., Prill, R., Fisk, W. J., Apte, M. G., Blake, D., & Faulkner, D. (2004) · Indoor Air · doi:10.1111/j.1600-0668.2004.00251.x · Cited by 462 · cited 1×
“Shendell et al. (2004) found that higher indoor CO2 concentrations (indicating less ventilation) in classrooms were associated with increased student absence, after controlling for a variety of other factors.”
BackgroundSelf-citationWargocki, P., Sundell, J., Bischof, W., Brundrett, G., Fanger, P. O., Gyntelberg, F., Hanssen, S. O., Harrison, P., Pickering, A., Seppänen, O., et al. (2002) · Indoor Air · doi:10.1034/j.1600-0668.2002.01145.x · Cited by 418
Cited by
Towards sustainable, energy-efficient and healthy ventilation strategies in buildings: A review
Chenari, B., Dias Carrilho, J., & Gameiro da Silva, M. (2016) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2016.01.074 · Cited by 515
Ventilation in European dwellings: A review
Dimitroulopoulou, C. (2012) · Building and Environment · doi:10.1016/j.buildenv.2011.07.016 · Cited by 304
Wolkoff, P., Azuma, K., & Carrer, P. (2021) · International Journal of Hygiene and Environmental Health · doi:10.1016/j.ijheh.2021.113709 · Cited by 279
Haverinen-Shaughnessy, U., Shaughnessy, R. J., Cole, E. C., Toyinbo, O., & Moschandreas, D. J. (2015) · Building and Environment · doi:10.1016/j.buildenv.2015.03.006 · Cited by 264
Santamouris, M., Synnefa, A., Asssimakopoulos, M., Livada, I., Pavlou, K., Papaglastra, M., Gaitani, N., Kolokotsa, D., & Assimakopoulos, V. (2008) · Energy and Buildings · doi:10.1016/j.enbuild.2008.04.002 · Cited by 253
Ventilation control for airborne transmission of human exhaled bio-aerosols in buildings
Qian, H., & Zheng, X. (2018) · Journal of Thoracic Disease · doi:10.21037/jtd.2018.01.24 · Cited by 249
“The equation and its improvements have been widely used to predict outbreaks of airborne infections and even to study the association between sick leave and ventilation system (40-43).”
MethodKelly, F. J., & Fussell, J. C. (2019) · Atmospheric Environment · doi:10.1016/j.atmosenv.2018.11.058 · Cited by 246
Reducing burden of disease from residential indoor air exposures in Europe (HEALTHVENT project)
Asikainen, A., Carrer, P., Kephalopoulos, S., Fernandes, E. D. O., Wargocki, P., & Hänninen, O. (2016) · Environmental Health · doi:10.1186/s12940-016-0101-8 · Cited by 229
“(2004) [7], concentrating on office-type working environment and residential buildings, ventilation was considered to significant impact or association with comfort (perceived air quality, PAQ) and health (including sick building syndrome (SBS) symptoms, inflammation, infections, asthma, allergy, and short-term sick l…”
BackgroundMa, N., Aviv, D., Guo, H., & Braham, W. W. (2021) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2020.110436 · Cited by 217
School air quality related to dry cough, rhinitis and nasal patency in children
Simoni, M., Annesi-Maesano, I., Sigsgaard, T., Norback, D., Wieslander, G., Nystad, W., Canciani, M., Sestini, P., & Viegi, G. (2010) · European Respiratory Journal · doi:10.1183/09031936.00016309 · Cited by 211
An update on sick building syndrome
Norbäck, D. (2009) · Current Opinion in Allergy & Clinical Immunology · doi:10.1097/aci.0b013e32831f8f08 · Cited by 197
What do we know about indoor air quality in school classrooms? A critical review of the literature
Chatzidiakou, L., Mumovic, D., & Summerfield, A. J. (2012) · Intelligent Buildings International · doi:10.1080/17508975.2012.725530 · Cited by 182
“not generally thought to be harmful (Seppänen and Fisk 2004) and so is often accorded little significance, other than as an indicator of ventilation, but if it contributes directly to increased tiredness and a loss of concentration even at concentrations encountered in school buildings (Bakó-Biró et al.”
BackgroundCarrer, P., Wargocki, P., Fanetti, A., Bischof, W., De Oliveira Fernandes, E., Hartmann, T., Kephalopoulos, S., Palkonen, S., & Seppänen, O. (2015) · Building and Environment · doi:10.1016/j.buildenv.2015.08.011 · Cited by 172
Residential air‐change rates: A critical review
Nazaroff, W. W. (2021) · Indoor Air · doi:10.1111/ina.12785 · Cited by 161
Irga, P. J., Torpy, F. R., & Burchett, M. D. (2013) · Atmospheric Environment · doi:10.1016/j.atmosenv.2013.04.078 · Cited by 137
Ventilation in public housing: implications for indoor nitrogen dioxide concentrations
Zota, A., Adamkiewicz, G., Levy, J. I., & Spengler, J. D. (2005) · Indoor Air · doi:10.1111/j.1600-0668.2005.00375.x · Cited by 118
Metadata
- Authors
- Seppanen, O. A., & Fisk, W. J.
- Venue
- Indoor Air
- Publisher
- Hindawi Limited
- Published
- 2004-08
- Volume
- 14
- Issue
- s7
- Pages
- 102-118
- ISSN
- 0905-6947 (ISSN-L)
- 1600-0668
- OpenAlex
- W2169053172
- Cited by
- 249
- References
- 49
- FWCI
- 3.01
- Type
- journal article
- Language
- en
- Open access
- bronze
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.