Summary of human responses to ventilation
Open accessThe DOI matches its Crossref record; 49 of the 49 references it cites were found in a registry or an index.
Abstract
UNLABELLED: It is known that ventilation is necessary to remove indoor-generated pollutants from indoor air or dilute their concentration to acceptable levels. But as the limit values of all pollutants are not known the exact determination of required ventilation rates based on pollutant concentrations is seldom possible. The selection of ventilation rates has to be based also on epidemiological research, laboratory and field experiments and experience. The existing literature indicates that ventilation has a significant impact on several important human outcomes including: (1) communicable respiratory illnesses; (2) sick building syndrome symptoms; (3) task performance and productivity, and (4) perceived air quality (PAQ) among occupants or sensory panels (5) respiratory allergies and asthma. In many studies, prevalence of sick building syndrome symptoms has also been associated with characteristics of HVAC-systems. Often the prevalence of SBS symptoms is higher in air-conditioned buildings than in naturally ventilated buildings. The evidence suggests that better hygiene, commissioning, operation and maintenance of air handling systems may be particularly important for reducing the negative effects of HVAC systems. Ventilation may also have harmful effects on indoor air quality and climate if not properly designed, installed, maintained and operated. Ventilation may bring indoors harmful substances or deteriorate indoor environment. Ventilation interacts also with the building envelope and may deteriorate the structures of the building. Ventilation changes the pressure differences across the structures of building and may cause or prevent infiltration of pollutants from structures or adjacent spaces. Ventilation is also in many cases used to control the thermal environment or humidity in buildings. The paper summarises the current knowledge on positive and negative effects of ventilation on health and other human responses. The focus is on office-type working environment and residential buildings. PRACTICAL IMPLICATIONS: The review shows that ventilation has various positive impacts on health and productivity of building occupants. Ventilation reduces the prevalence of airborne infectious diseases and thus the number of sick leave days. In office environment a ventilation rate up to 20-25 L/s per person seem to decrease the prevalence of SBS-symptoms. Air conditioning systems may increase the prevalence of SBS-symptoms relative to natural ventilation if not clean. In residential buildings the air change rate in cold climates should not be below app. 0.5 ach. Ventilation systems may cause pressure differences over the building envelope and bring harmful pollutants indoors.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Ventilation for Acceptable Indoor Air Quality
Falih, M. (2019) · Cited by 2,497
Guidelines for community noise
Berglund, B., Lindvall, T., & Schwela, D. (1999) · Cited by 1,693
Jones, A. P. (1999) · Atmospheric Environment · doi:10.1016/s1352-2310(99)00272-1 · Cited by 1,481 · cited 6×
“Several studies have been performed on the effect of improved ventilation with or without dehumidification on the population of dust mites in residences (Chivato et al., 1997, Crane et al., 1998, Jones, 1999, Harving et al., 1993, Niven et al., 1999, Warner et al., 2000).”
BackgroundInfluentialSeppanen, O. A., Fisk, W. J., & Mendell, M. J. (1999) · Indoor Air · doi:10.1111/j.1600-0668.1999.00003.x · Cited by 876 · cited 8×
“Control of CO2 is the same as to control ventilation (Seppänen et al.,1999).”
BackgroundMethodInfluentialSelf-citationWARGOCKI, P., WYON, D. P., SUNDELL, J., CLAUSEN, G., & FANGER, P. O. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004222.x · Cited by 688
Bornehag, C.-G., Blomquist, G., Gyntelberg, F., Järvholm, B., Malmberg, P., Nordvall, L., Nielsen, A., Pershagen, G., & Sundell, J. (2001) · Indoor Air · doi:10.1034/j.1600-0668.2001.110202.x · Cited by 659 · cited 1×
“…microbial growth in buildings have been associated with a number of health effects including respiratory symptoms and diseases and other symptoms (Bornehag et al., 2001, Nevalainen 2002); although, the evidence of a direct link between higher air humidity levels and adverse health is quite…”
BackgroundSpengler, J. D., McCarthy, J. F., & Samet, J. M. (2000) · Cited by 574
Impact of Temperature and Humidity on the Perception of Indoor Air Quality
Fang, L., Clausen, G., & Fanger, P. O. (1998) · Indoor Air · doi:10.1111/j.1600-0668.1998.t01-2-00003.x · Cited by 534 · cited 2×
“Laboratory experiments (Fang et al., 1998) have suggested that perceived quality of polluted air depends on the enthalpy of the air.”
BackgroundAssociations between classroom CO2 concentrations and student attendance in Washington and Idaho
Shendell, D. G., Prill, R., Fisk, W. J., Apte, M. G., Blake, D., & Faulkner, D. (2004) · Indoor Air · doi:10.1111/j.1600-0668.2004.00251.x · Cited by 462 · cited 1×
“Shendell et al. (2004) found that higher indoor CO2 concentrations (indicating less ventilation) in classrooms were associated with increased student absence, after controlling for a variety of other factors.”
BackgroundSelf-citationWargocki, P., Sundell, J., Bischof, W., Brundrett, G., Fanger, P. O., Gyntelberg, F., Hanssen, S. O., Harrison, P., Pickering, A., Seppänen, O., et al. (2002) · Indoor Air · doi:10.1034/j.1600-0668.2002.01145.x · Cited by 418
Fanger, P. O. (1988) · Energy and Buildings · doi:10.1016/0378-7788(88)90051-5 · Cited by 371
MILTON, D. K., GLENCROSS, P. M., & WALTERS, M. D. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004212.x · Cited by 364 · cited 2×
“The strongest evidence is provided by the most recent study of these (Milton et al., 2000).”
APTE, M. G., FISK, W. J., & DAISEY, J. M. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004246.x · Cited by 341 · cited 1×
“Dose-response relation between measured average CO2 - concentration and several typical SBS-symptoms was reported also from the analysis of the US BASE study data (Apte et al., 2000, Erdmann et al., 2002).”
MethodSelf-citationNon-Specific Symptoms In Office Workers: A Review And Summary Of The Epidemiologic Literature
Mendell, M. J. (1993) · Indoor Air · doi:10.1111/j.1600-0668.1993.00003.x · Cited by 284 · cited 2×
“Additionally, the presence or absence of statisticallysignificant associations of HVAC system types with outcomes is illustrated graphically within the tables using an adaptation of the format of ( Mendell, 1993 ).”
MethodSeppänen, O., & Fisk, W. J. (2002) · Indoor Air · doi:10.1034/j.1600-0668.2002.01111.x · Cited by 277 · cited 8×
“Summaries ( Seppanen and Fisk, 2002, Wargocki et al., 2002a) showed that most studies on the association of ventilation systems and human responses indicate that relative to natural ventilation, air conditioning (with or without humidification) was consistently associated with a statistically significant increase in t…”
BackgroundInfluentialSelf-citationProceedings of the 8th International Conference on Indoor Air Quality and Climate
Santos, A. M. B., & Gunnarsen, L. (1999) · Indoor Air · Cited by 274
An Epidemic of Pneumococcal Disease in an Overcrowded, Inadequately Ventilated Jail
Hoge, C. W., Reichler, M. R., Dominguez, E. A., Bremer, J. C., Mastro, T. D., Hendricks, K. A., Musher, D. M., Elliott, J. A., Facklam, R. R., & Breiman, R. F. (1994) · New England Journal of Medicine · doi:10.1056/nejm199409083311004 · Cited by 271
Airborne Infection: Theoretical Limits of Protection Achievable by Building Ventilation
Nardell, E. A., Keegan, J., Cheney, S. A., & Etkind, S. C. (1991) · American Review of Respiratory Disease · doi:10.1164/ajrccm/144.2.302 · Cited by 261
Treptow, W. (1927) · Angewandte Chemie · doi:10.1002/ange.19270400214 · Cited by 258
Formation of Strong Airway Irritants in Terpene/Ozone Mixtures
WOLKOFF, P., CLAUSEN, P. A., WILKINS, C. K., & NIELSEN, G. D. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010002082.x · Cited by 253 · cited 2×
“Ozone may react with the indoor generated compounds and result in more harmful compounds than the original chemicals in the reaction (Wolkoff et al., 2000)”
BackgroundPerformance and costs of particle air filtration technologies: Air filtration technology
Fisk, W. J., Faulkner, D., Palonen, J., & Seppanen, O. (2002) · Indoor Air · doi:10.1034/j.1600-0668.2002.01136.x · Cited by 242 · cited 4×
“Particle size strongly influences the effectiveness of ventilation and filtration in controlling indoor air concentrations as discussed in (IOM 2000, Chapter 10) and Fisk et al. (2002) .”
BackgroundMethodInfluentialSelf-citationEuropean Indoor Air Quality Audit Project in 56 Office Buildings
Bluyssen, P. M., Oliveira Fernandes, E., Groes, L., Clausen, G., Fanger, P. O., Valbjorn, O., Bernhard, C. A., & Roulet, C. A. (1996) · Indoor Air · doi:10.1111/j.1600-0668.1996.00002.x · Cited by 237 · cited 2×
“The European audit project on indoor air quality (Bluyssen et al., 1996), the European Data Base Project on Air Pollution Sources and the European Airless project (Bluyssen et al.”
BackgroundSkov, P., Valbjorn, O., & Pedersen, B. V. (1990) · Scandinavian Journal of Work, Environment & Health · doi:10.5271/sjweh.1772 · Cited by 214 · cited 1×
“In one of the five assessments (Skov et al.,1990) with increased symptoms in buildings with simple mechanical ventilation, two buildings with mechanical ventilation had humidifiers, a possible risk factor.”
BackgroundFang, L., Clausen, G., & Fanger, P. O. (1998) · Indoor Air · doi:10.1111/j.1600-0668.1998.00008.x · Cited by 202 · cited 1×
“Studies with a whole body exposure did not show as strong effect of the enthalpy of the air on perceived air quality (Fang et al., 1997).”
Health and Indoor Climate Complaints of 7043 office Workers in 61 Buildings in the Netherlands
Zweers, T., Preller, L., Brunekreef, B., & Boleij, J. S. M. (1992) · Indoor Air · doi:10.1111/j.1600-0668.1992.00001.x · Cited by 159 · cited 1×
“The results reported in Figure 6 of Zweers et al. (1992), comparing symptom prevalences with simple mechanical ventilation (independently with and without humidification) to symptom prevalences with natural ventilation, also suggest that humidification may be associated with higher prevalences of…”
ResultBuilding-Associated Risk of Febrile Acute Respiratory Diseases in Army Trainees
Brundage, J. F. (1988) · JAMA: The Journal of the American Medical Association · doi:10.1001/jama.1988.03720140028029 · Cited by 158 · cited 3×
“,1994, Brundage et al., 1988, Drinka et al., 1996, Milton et al., 2000). Even though the ventilation rates were estimated and not measured, the consistent findings are a strong indication of the association of ventilation rates with health effects. The strongest evidence is provided by the most recent study of these (…”
InfluentialSchäppi, G. F., Suphioglu, C., Taylor, P. E., & Knox, R. B. (1997) · Journal of Allergy and Clinical Immunology · doi:10.1016/s0091-6749(97)70170-2 · Cited by 158 · cited 2×
“However, some plant allergens (e.g., grass and birch allergen) are present substantially in particles smaller than 1 µm (e.g., Rantio-Lehtimaki et al.,1994, Schappi et al., 1997, Spieksma et al., 1990, 1991).”
BackgroundMenzies, D., Popa, J., Hanley, J. A., Rand, T., & Milton, D. K. (2003) · The Lancet · doi:10.1016/s0140-6736(03)14897-0 · Cited by 149 · cited 2×
“However, Menzies et al. (2003) did not find that UV irradiation reduced the measured levels of bioaerosols in the occupied space, so the reason for the symptom reduction remains uncertain.”
BackgroundNevalainen, A. I., & Seuri, M. (2005) · Indoor Air · doi:10.1111/j.1600-0668.2005.00344.x · Cited by 142
Cost benefit analysis of the night-time ventilative cooling in office building
Seppänen, O., Fisk, W. J., & Faulkner, D. M. (2003) · University of North Texas Digital Library (University of North Texas) · Cited by 129
Self-citationAirborne birch pollen antigens in different particle sizes
RANTIO–LEHTIMÄKI, A., VIANDER, M., & KOIVIKKO, A. (1994) · Clinical & Experimental Allergy · doi:10.1111/j.1365-2222.1994.tb00912.x · Cited by 123
Evidence of grass‐pollen allergenic activity in the smaller micronic atmospheric aerosol fraction
SPIEKSMA, F. T. M., KRAMPS, J. A., VAN DER LINDEN, A. C., NIKKELS, B. H., PLOMP, A., KOERTEN, H. K., & DIJKMAN, J. H. (1990) · Clinical & Experimental Allergy · doi:10.1111/j.1365-2222.1990.tb02683.x · Cited by 119 · cited 1×
“However, some plant allergens (e.g., grass and birch allergen) are present substantially in particles smaller than 1 µm (e.g., Rantio-Lehtimäki et al.,1994, Schappi et al., 1997, Spieksma et al., 1990, 1991).”
Sundell, J. (1994) · Indoor Air · doi:10.1111/j.1600-0668.1994.tb00031.x · Cited by 119 · cited 1×
“The study with the largest number of buildings (Sundell 1994) did not find a significantly higher symptom prevalence with simple mechanical ventilation; however, only ten of 540 rooms in this study had natural ventilation.”
Warner, J. A., Frederick, J. M., Bryant, T. N., Weich, C., Raw, G. J., Hunter, C., Stephend, F. R., McIntyre, D. A., & Warner, J. O. (2000) · Journal of Allergy and Clinical Immunology · doi:10.1016/s0091-6749(00)90181-7 · Cited by 112 · cited 1×
“Several studies have been performed on the effect of improved ventilation with or without dehumidification on the population of dust mites in residences (Chivato et al., 1997, Crane et al., 1998, Jones, 1999, Harving et al., 1993, Niven et al., 1999, Warner et al., 2000).”
An Enforceable Indoor Air Quality Standard for Environmental Tobacco Smoke in the Workplace1
Repace, J., & Lowrey, A. H. (1993) · Risk Analysis · doi:10.1111/j.1539-6924.1993.tb00747.x · Cited by 106
House‐dust mites and associated environmental conditions in Danish homes
Harving, H., Korsgaard, J., & Dahl, R. (1993) · Allergy · doi:10.1111/j.1398-9995.1993.tb00694.x · Cited by 101
Erdmann, C. A., Steiner, K. C., & Apte, M. G. (2002) · University of North Texas Digital Library (University of North Texas) · Cited by 89
Report of an outbreak: nursing home architecture and influenza-A attack rates
Drinka, P. J., Krause, P., Schilling, M., Miller, B. A., Shult, P., & Gravenstein, S. (1996) · Journal of the American Geriatrics Society · doi:10.1111/j.1532-5415.1996.tb01859.x · Cited by 77
Wargocki, P. L., Bakó-Bíró, Z., Clausen, G., & Fanger, P. O. (2002) · Energy and Buildings · doi:10.1016/s0378-7788(02)00096-8 · Cited by 63 · cited 8×
“A recent study (Wargocki et al., 2002b) has shown a slightly lower but still significant pollution load from building sources including the air handling systems (0.04 – 0.27 olf /m2).”
BackgroundInfluentialGold, D. R. (1992) · Clinics in Chest Medicine · doi:10.1016/s0272-5231(21)00852-2 · Cited by 59
The Right to Healthy Indoor Air
Mølhave, L., & KRZYZANOWSKI, M. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004211.x · Cited by 51
Niven, R. M., Fletcher, A. M., Pickering, A. C., Čustović, A., Sivour, J. B., Preece, A. R., Oldham, L. A., & Francis, H. (1999) · Journal of Allergy and Clinical Immunology · doi:10.1016/s0091-6749(99)70416-1 · Cited by 49 · cited 1×
“Several studies have been performed on the effect of improved ventilation with or without dehumidification on the population of dust mites in residences (Chivato et al., 1997, Crane et al., 1998, Jones, 1999, Harving et al., 1993, Niven et al., 1999, Warner et al., 2000).”
Mendell, M. J., Naco, G. M., Wilcox, T. G., & Sieber, W. K. (2003) · American Journal of Industrial Medicine · doi:10.1002/ajim.10211 · Cited by 47
Fungal spore transport through a building structure
Airaksinen, M., Kurnitski, J., Pasanen, P. O., & Seppänen, O. (2004) · Indoor Air · doi:10.1046/j.1600-0668.2003.00215.x · Cited by 47 · cited 2×
“the mould spores can be carried inside through a base floor in a building with mould growth in the crawl space ( Airaksinen et al., 2004 ).”
BackgroundPollution source control and ventilation improve health, comfort and productivity
Wargocki, P. L., Wyon, D. P., & Fanger, P. O. (2000) · Cited by 42
Grass-pollen allergen carried by the smaller micronic aerosol fraction
Spieksma, F. T. M., Kramps, J. A., Plomp, A., & Koerten, H. K. (1991) · Grana · doi:10.1080/00173139109427779 · Cited by 36 · cited 2×
“However, some plant allergens (e.g., grass and birch allergen) are present substantially in particles smaller than 1 µm (e.g., Rantio-Lehtimäki et al.,1994, Schappi et al., 1997, Spieksma et al., 1990, 1991).”
BackgroundCrane, J., Ellis, I., Siebers, R. W. L., Grimmet, D., Lewis, S., & Fitzharris, P. (1998) · Allergy · doi:10.1111/j.1398-9995.1998.tb03971.x · Cited by 30 · cited 2×
“Several studies have been performed on the effect of improved ventilation with or without dehumidification on the population of dust mites in residences (Chivato et al., 1997, Crane et al., 1998, Jones, 1999, Harving et al., 1993, Niven et al., 1999, Warner et al., 2000).”
Fisk, W. J., Seppänen, O., Faulkner, D. M., & Huang, J. (2003) · University of North Texas Digital Library (University of North Texas) · Cited by 27
Self-citationDesign and Protocol for Monitoring Indoor Air Quality
Nagda, N. L., & Harper, J. (1989) · doi:10.1520/stp1002-eb · Cited by 24
Cited by
Towards sustainable, energy-efficient and healthy ventilation strategies in buildings: A review
Chenari, B., Dias Carrilho, J., & Gameiro da Silva, M. (2016) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2016.01.074 · Cited by 515
Ventilation in European dwellings: A review
Dimitroulopoulou, C. (2012) · Building and Environment · doi:10.1016/j.buildenv.2011.07.016 · Cited by 304
Wolkoff, P., Azuma, K., & Carrer, P. (2021) · International Journal of Hygiene and Environmental Health · doi:10.1016/j.ijheh.2021.113709 · Cited by 279
Haverinen-Shaughnessy, U., Shaughnessy, R. J., Cole, E. C., Toyinbo, O., & Moschandreas, D. J. (2015) · Building and Environment · doi:10.1016/j.buildenv.2015.03.006 · Cited by 264
Santamouris, M., Synnefa, A., Asssimakopoulos, M., Livada, I., Pavlou, K., Papaglastra, M., Gaitani, N., Kolokotsa, D., & Assimakopoulos, V. (2008) · Energy and Buildings · doi:10.1016/j.enbuild.2008.04.002 · Cited by 253
Metadata
- Authors
- Seppanen, O. A., & Fisk, W. J.
- Venue
- Indoor Air
- Publisher
- Hindawi Limited
- Published
- 2004-08
- Volume
- 14
- Issue
- s7
- Pages
- 102-118
- ISSN
- 0905-6947 (ISSN-L)
- 1600-0668
- OpenAlex
- W2169053172
- Cited by
- 249
- References
- 49
- FWCI
- 3.01
- Type
- journal article
- Language
- en
- Open access
- bronze
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.