Minimizing data center cooling and server power costs
The DOI matches its Crossref record; 6 of the 6 references it cites were found in a registry or an index.
Abstract
This paper focuses on power minimization in a data center accounting for both the information technology equipment and the air conditioning power usage. In particular we address the server consolidation (on/off state assignment) concurrently with the task assignment. We formulate the resulting optimization problem as an Integer Linear Programming problem and present a heuristic algorithm that solves it in polynomial time. Experimental results show an average of 13% power saving for different data center utilization rates compared to a baseline task assignment technique, which does not perform server consolidation.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Heat Transfer: A Practical Approach
Çengel, Y. A. (1997) · Cited by 2,358
Making scheduling cool: temperature-aware workload placement in data centers
Moore, J., Chase, J., Ranganathan, P., & Sharma, R. K. (2005) · USENIX Annual Technical Conference · Cited by 651
Dynamic load balancing on Web-server systems
Cardellini, V., Colajanni, M., & Yu, P. S. (1999) · IEEE Internet Computing · doi:10.1109/4236.769420 · Cited by 559 · cited 1×
“The Environmental Protection Agency (EPA), in its August 2007 report to the US Congress, affirmed that data centers consumed about 61 billion kilowatt-hours (kWh) in 2006, roughly 1.5 percent of total U.S. electricity consumption, for a total electricity cost of about $4.5 billion [1].”
BackgroundInfluentialTang, Q., Gupta, S. K. S., & Varsamopoulos, G. (2008) · IEEE Transactions on Parallel and Distributed Systems · doi:10.1109/tpds.2008.111 · Cited by 481 · cited 1×
“The EPA report also stated that the energy consumption of servers and data centers has doubled in the past five years and is expected to quadruple in the next five years to more than 100 billion kWh at a cost of about $7.4 billion annually.”
BackgroundInfluentialLoad balancing and unbalancing for power and performance in cluster-based systems
Bianchini, R., Carrera, E. V., Heath, T., & Pinheiro, E. (2001) · doi:10.7282/t3-agfw-yt73 · Cited by 479 · cited 1×
“This assumption is also made by the authors of [10].”
Sensor-Based Fast Thermal Evaluation Model For Energy Efficient High-Performance Datacenters
Tang, Q., Mukherjee, T., Gupta, S. K. S., & Cayton, P. (2006) · 2006 Fourth International Conference on Intelligent Sensing and Information Processing · doi:10.1109/icisip.2006.4286097 · Cited by 206 · cited 3×
“The heat rate can be transformed to the temperature using thermodynamic constants [11]:”
BackgroundMethodInfluential
Cited by
Data Center Energy Consumption Modeling: A Survey
Dayarathna, M., Wen, Y., & Fan, R. (2016) · IEEE Communications Surveys & Tutorials · doi:10.1109/comst.2015.2481183 · Cited by 1,165
Habibi Khalaj, A., & Halgamuge, S. K. (2017) · Applied Energy · doi:10.1016/j.apenergy.2017.08.037 · Cited by 707
Greening geographical load balancing
Liu, Z., Lin, M., Wierman, A., Low, S. H., & Andrew, L. L. H. (2011) · Proceedings of the ACM SIGMETRICS joint international conference on Measurement and modeling of computer systems · doi:10.1145/1993744.1993767 · Cited by 467
Renewable and cooling aware workload management for sustainable data centers
Liu, Z., Chen, Y., Bash, C., Wierman, A., Gmach, D., Wang, Z., Marwah, M., & Hyser, C. (2012) · Proceedings of the 12th ACM SIGMETRICS/PERFORMANCE joint international conference on Measurement and Modeling of Computer Systems · doi:10.1145/2254756.2254779 · Cited by 413
Optimizing energy consumption for data centers
Rong, H., Zhang, H., Xiao, S., Li, C., & Hu, C. (2016) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2015.12.283 · Cited by 398
Online algorithms for geographical load balancing
Lin, M., Liu, Z., Wierman, A., & Andrew, L. L. H. (2012) · 2012 International Green Computing Conference (IGCC) · doi:10.1109/igcc.2012.6322266 · Cited by 290
Transforming Cooling Optimization for Green Data Center via Deep Reinforcement Learning
Li, Y., Wen, Y., Tao, D., & Guan, K. (2020) · IEEE Transactions on Cybernetics · doi:10.1109/tcyb.2019.2927410 · Cited by 274
Wahlroos, M., Pärssinen, M., Manner, J., & Syri, S. (2017) · Energy · doi:10.1016/j.energy.2017.08.078 · Cited by 249
“[14] have explained that there are two main systems for DC air conditioning: the Heating Ventilation Air Conditioner (HVAC) and Computer RoomAir Conditioner (CRAC).”
BackgroundFuture views on waste heat utilization – Case of data centers in Northern Europe
Wahlroos, M., Pärssinen, M., Rinne, S., Syri, S., & Manner, J. (2018) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2017.10.058 · Cited by 233
“Different technologies are employed in non-energy-proportional DCs to reduce energy costs and power density, including: (1) loadbalancing evenly between different servers to distribute the workload per server and achieve uniform power density, and (2) server consolidation to assign incoming tasks to the minimum number…”
BackgroundMethodInfluentialA Review of Data Centers Energy Consumption and Reliability Modeling
Ahmed, K. M. U., Bollen, M. H. J., & Alvarez, M. (2021) · IEEE Access · doi:10.1109/access.2021.3125092 · Cited by 191
“the spatial allocation of the computing power, the airflow rate, and the efficiency of the CRAC [112], [122]–[124].”
BackgroundToward a Systematic Survey for Carbon Neutral Data Centers
Cao, Z., Zhou, X., Hu, H., Wang, Z., & Wen, Y. (2022) · IEEE Communications Surveys & Tutorials · doi:10.1109/comst.2022.3161275 · Cited by 179
“As CRAC power consumption is negatively correlated with air supply temperature [120], overprovisioning will result in unnecessary CRAC power consumption.”
BackgroundMethodInfluentialRenewable and cooling aware workload management for sustainable data centers
Liu, Z., Chen, Y., Bash, C., Wierman, A., Gmach, D., Wang, Z., Marwah, M., & Hyser, C. (2012) · ACM SIGMETRICS Performance Evaluation Review · doi:10.1145/2318857.2254779 · Cited by 176
Greening Geographical Load Balancing
Liu, Z., Lin, M., Wierman, A., Low, S., & Andrew, L. L. H. (2015) · IEEE/ACM Transactions on Networking · doi:10.1109/tnet.2014.2308295 · Cited by 159
“, [1], [7], and [8], either do not provide provable guarantees or ignore diverse network delays and/or prices.”
Background(2021) · Lancaster EPrints (Lancaster University) · Cited by 75
On the Carbon Footprint Optimization in an InterCloud Environment
Justafort, V. D., Beaubrun, R., & Pierre, S. (2018) · IEEE Transactions on Cloud Computing · doi:10.1109/tcc.2015.2511768 · Cited by 10
“The third method, CB MAX TEMP, performs carbon footprint minimization while maximizing the CRAC unit efficiency by considering the maximal value of the temperature (35 C) [12].”
BackgroundMethodInfluentialA hybrid approach for optimizing carbon footprint in intercloud environment
Justafort, V. D., Beaubrun, R., & Pierre, S. (2019) · IEEE Transactions on Services Computing · doi:10.1109/tsc.2016.2638900 · Cited by 7
Metadata
- Authors
- Pakbaznia, E., & Pedram, M.
- Venue
- Proceedings of the 2009 ACM/IEEE international symposium on Low power electronics and design
- Publisher
- ACM
- Published
- 2009-08-19
- Pages
- 145-150
- OpenAlex
- W2053211348
- Cited by
- 218
- References
- 6
- FWCI
- 12.20
- Type
- conference paper
- Language
- en
- Open access
- closed
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.