Effect of fin types of outdoor fan-supplied finned-tube heat exchanger on periodic frosting and defrosting performance of a residential air-source heat pump
AI snapshot
Written from the paper’s full text.
TL;DR
This experimental study compared flat, wavy, and louver fins on the outdoor finned-tube heat exchanger of a residential air-source heat pump over repeated frosting/defrosting cycles. Flat fins gave the best overall thermal performance, followed by wavy and louver fins, and the differences were linked to how frost accumulation interacted with the outdoor axial fan’s characteristic curve.
Key findings
- Six consecutive frosting/defrosting cycles were run for each fin type; frosting and defrosting durations were almost equal, about 46.6 min and 3.9 min, respectively, because the same defrosting control schemes were used.
- During frosting, time-average heating capacity, COP, and input power for flat fin were greater by 17.1%, 9.0%, and 7.6%, respectively, than for louver fin; wavy fin values were greater by 7.4%, 4.3%, and 2.7% than louver fin.
- Time-average values from the third, fourth, and fifth cycles: flat fin had COP 2.30, heating capacity 5894.33 W, input power 2573.46 W; wavy fin had 2.20, 5410.38 W, 2455.29 W; louver fin had 2.11, 5035.40 W, 2390.45 W.
- The heating-capacity curve began descending earliest for louver fin at 17.83 min, versus 24.33 min for wavy and 24.58 min for flat; peak heating capacities were 6121.90 W, 6438.71 W, and 6591.13 W, respectively. The paper attributes rapid drops for wavy and louver fins to the outdoor axial fan entering its stall zone, while flat fin did not experience the stall zone during the 46.6 min frosting duration.
Methods
- A split-type residential air-source heat pump with nominal 7200 W cooling capacity was tested with R22; three outdoor finned-tube heat exchangers with equal geometrical parameters but flat, wavy, or louver fins were compared.
- Tests used two environmental simulation rooms and a data acquisition system, with heating capacity measured by the indoor air enthalpy difference method based on Chinese Standard GB/T 7725-2004; indoor conditions were 20 °C dry-bulb/12 °C wet-bulb and outdoor conditions were 2 °C dry-bulb/1 °C wet-bulb for frosting/defrosting cycles.
- Defrosting was initiated when the defrosting sensor was below −2 °C and frosting time exceeded 45 min, and terminated when defrosting time exceeded 10 min or the sensor reached 12 °C; time-average values from the third, fourth, and fifth cycles were used for overall comparison, and real-time data from the fourth cycle were used for dynamic comparison.
Limitations
- The paper states that experimental measurements of frost thickness and air pressure drop were not included; the dashed lines in Fig. 13 only schematically present air pressure drops under different frost thickness and are not experimental test results.
- Evident from the text: the study is limited to one residential air-source heat pump, R22, and fixed standard test conditions, so generalization to other systems, refrigerants, or operating conditions is not established.
- Evident from the text: the fan-stall explanation is inferred from performance curves and a schematic fan/pressure-drop combination rather than from measured airflow or pressure-drop data.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Claims the paper makes
3 of 14 cited sources checked · 0 supported · 0 flagged · accuracy not yet measured
- Premisecitation§ Introduction
In most experimental researches, the airflow rate across the finned-tube heat exchanger was maintained constant throughout the frosting test, although frost grows continuously.
“Second, the airflow rate across the finned-tube heat exchanger is maintained to be constant throughout the frosting test in most of the experimental researches [5,10,11,13,20], although frost grows continuously.”
Quote in the paperSubstantial claim2 of 5 sources checked- cites [5] Kristian, 2009, Prediction of an effective cooling output of the fin-and-tube heat exchanger under frosting conditions, Appl. Therm. Eng. source
- cites [10] Yan, 2005, Thermofluid characteristics of frosted finned-tube heat exchanger, Int. J. Heat Mass Transfer source
The Experimental apparatus section (p. 2) explicitly says airflow was maintained constant throughout each test by adjusting fan speed. This confirms the cited study used that procedure during frosting, but the paper does not establish that most experimental studies did so. (LLM, conf=0.86)
Experimental — accuracy not yet measured - cites [11] Kondepudi, 1990, The effects of different fin configurations on the performance of finned-tube heat exchangers under frosting conditions, ASHRAE Trans.
- cites [13] Yan, 2003, Performance of fined tube heat exchanger operating under frosting conditions, Int. J. Heat Mass Transfer source
- cites [20] Padhmanabhan, 2011, Modeling non-uniform frost growth on a fin-and-tube heat exchanger, Int. J. Refrigeration source
The Model validation section (p. 6) says the fan's variable-frequency drive maintained airflow constant during frost growth in this paper's experiments. The paper does not establish that most experimental studies use this practice; it also reports that airflow redistributes locally across the coil as frost accumulates. (LLM, conf=0.88)
Experimental — accuracy not yet measured
- Findingown data§ 2780 2387.56 3.92 2000 1482.52
The falling amplitudes of the heating capacity relative to the peak were 1244.40 W, 2048.29 W and 1999.92 W for flat, wavy and louver fins, respectively.
“As a consequence, the falling amplitudes of the heating capacity relative to the peak valuedthe difference between the peak and the value at the defrosting initiationdwere 1244.40W, 2048.29Wand 1999.92W for flat, wavy and louver fins, respectively.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The flat fin had the greatest suction and discharge pressures at the moment of defrosting initiation, followed by the wavy and louver fin types.
“Finally, the flat fin had the greatest suction and discharge pressures at the moment of defrosting initiation, and followed by wavy and louver fin types.”
Quote in the paperNot a substantial claim - Findingown data§ Abstract
During the frosting cycle, the time-average input power for flat fin was 7.6% greater than that for louver fin.
“The time-average heating capacity, COP and input power for flat fin during frosting cycle were more by 17.1%, 9.0% and 7.6%, respectively than those for louver fin.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The starting point of the descending segment of the input power curve for the wavy fin was later than that for the louver fin.
“Despite the fact that the starting point of the descending segment of the input power curve for wavy finwas later than that for the louver fin, the input power at defrosting initiation was almost equal between wavy and louver fins.”
Quote in the paperNot a substantial claim
- Findingown data§ 2780 2387.56 3.92 2000 1482.52
The time-average heating capacities for the flat and wavy fins were greater by 17.1% and 7.4%, respectively, than the smallest one of 5035.40 W for the louver fin.
“The time-average heating capacities for flat and wavy fins were greater by 17.1% and 7.4%, respectively, than the smallest one of 5035.40 W for louver fin.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The time-average COPs for the flat and wavy fins were greater by 9.0% and 4.3% than the smallest one of 2.11 for the louver fin.
“The time-average COPs for flat and wavy fins were greater by 9.0% and 4.3% than the smallest one of 2.11 for louver fin.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The time-average input powers for the flat and wavy fins were greater by 7.6% and 2.7% than the smallest one of 2390.45 W for the louver fin.
“However, the time-average input powers for flat and wavy fins were greater by 7.6% and 2.7% than the smallest one of 2390.45 W for louver fin.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The input power curves for the three fin types were virtually overlapped before the starting points of the descending segment.
“Even, input power curves for three fin types were virtually overlapped before the starting points of the descending segment.”
Quote in the paperNot a substantial claim - Findingown data§ Abstract
The frosting curves for wavy and louver fin types increased slightly at first, then decreased rapidly and gradually at last.
“The frosting curves for flat fin increased slightly and then decreased gradually, while the curves for wavy and louver fin types increased slightly at first, then decreased rapidly and gradually at last.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The heating capacity curve for flat fin gradually increased at first and then gradually decreased.
“The heating capacity curve for flat fin was gradually increased at first, and then gradually decreased.”
Quote in the paperNot a substantial claim - Findingnone given§ Abstract
The frosting curves for louver fin decreased considerably earlier than those for wavy fin.
“Meanwhile, the curves for louver fin decreased considerably earlier than those for wavy fin.”
Quote in the paperNot a substantial claim - Findingnone given§ 2780 2387.56 3.92 2000 1482.52
The suction and discharge pressures had a smaller difference among the three fin types during the ascending segment of their curves.
“The suction and discharge pressures had smaller difference among three fin types during the ascending segment of their curves.”
Quote in the paperNot a substantial claim - Findingown data
The differences in time-average values of heating capacity and COP among the three fin types were bigger than those in the peak values of heating capacity and COP.
“Apparently, the differences in the time-average values of the heating capacity and COP among three fin types were bigger than those in the peak values of the heating capacity and COP.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The input power curves for the three fin types had smaller variation amplitude than the heating capacity curves.
“However, the input power curves for three fin types had smaller variation amplitude than those of the heating capacity in Fig. 5.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The input power at defrosting initiation was almost equal between the wavy and louver fins.
“Despite the fact that the starting point of the descending segment of the input power curve for wavy finwas later than that for the louver fin, the input power at defrosting initiation was almost equal between wavy and louver fins.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The COP curves for the wavy and louver fin types increased quite gradually, and then decreased at a stable rate instead of rapidly and gradually at last.
“The COP curves for wavy and louver fin types increased quite gradually, and then decreased at a stable rate instead of then rapidly and gradually at last, which was different from the variation”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The suction and discharge pressures for the flat fin increased at first, and then gradually decreased.
“Similar to the heating capacity in Fig. 5 and the input power in Fig. 6, the suction and discharge pressures for flat fin increased at first, and then gradually decreased, while the input power for wavy and louver fin types gradually increased at first, then decreased rapidly and gradually at last.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The COP curve for the flat fin ascended almost throughout the frosting time.
“Even, Fig. 8 indicated that the curve of COP for flat fin ascended almost throughout the frosting time.”
Quote in the paperNot a substantial claim - Findingown data§ Abstract
During the frosting cycle, the time-average heating capacity for flat fin was 17.1% greater than that for louver fin.
“The time-average heating capacity, COP and input power for flat fin during frosting cycle were more by 17.1%, 9.0% and 7.6%, respectively than those for louver fin.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The time-average heating capacity for the louver fin was the smallest among the three fin types.
“Obviously, time-average heating capacity for the louver fin was the smallest, which predominantly attributed to the shortest ascending segment, the smallest peak value and greater falling amplitude relative to the peak value.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The input power for the flat fin increased gradually at first, and then decreased gradually.
“Similar to the heating capacity curves in Figs. 5 and 6 showed that the input power for flat fin increased gradually at first, and then decreased gradually, while the input power for wavy and louver fin types increased gradually at first, then decreased rapidly and gradually at last.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The heating capacity curves for wavy and louver fin types gradually increased at first, then decreased rapidly and gradually at last.
“However, heating capacity curves for wavy and louver fin types gradually increased at first, then decreased rapidly and gradually at last.”
Quote in the paperNot a substantial claim - Findingreasoning§ 2780 2387.56 3.92 2000 1482.52
The falling amplitudes of the input power relative to the peak for the wavy and louver fin types were almost equal.
“Hence, the falling amplitudes of the input power relative to the peak for wavy and louver fin types were almost equal.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The input power for the wavy and louver fin types increased gradually at first, then decreased rapidly and gradually at last.
“Similar to the heating capacity curves in Figs. 5 and 6 showed that the input power for flat fin increased gradually at first, and then decreased gradually, while the input power for wavy and louver fin types increased gradually at first, then decreased rapidly and gradually at last.”
Quote in the paperNot a substantial claim - Findingown data§ Abstract
During the frosting cycle, the time-average COP for flat fin was 9.0% greater than that for louver fin.
“The time-average heating capacity, COP and input power for flat fin during frosting cycle were more by 17.1%, 9.0% and 7.6%, respectively than those for louver fin.”
Quote in the paperSubstantial claim - Findingown data§ Abstract
The frosting curves for flat fin increased slightly and then decreased gradually.
“The frosting curves for flat fin increased slightly and then decreased gradually, while the curves for wavy and louver fin types increased slightly at first, then decreased rapidly and gradually at last.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The COP curves had a longer ascending segment than the heating capacity curves.
“The starting points of the descending segment in COP curves for three fin types were significantly delayed andmuch later than those in the heating capacity curves in Fig. 5dthat is, the curves of COP had the longer ascending segment than those of the heating capacity.”
Quote in the paperNot a substantial claim - Findingreasoning§ 2780 2387.56 3.92 2000 1482.52
The discharge temperature for the flat fin was always greater than those for the wavy and louver fins.
“The discharge temperature for flat fin was always greater than those for wavy and louver fins, which suggested the superheat or the refrigerant quality at compressor suction was higher for flat fin than those for wavy and louver fin types.”
Quote in the paperSubstantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The sequence according to the starting points of the descending segment of the suction and discharge pressure curves was louver, wavy and flat fin types, respectively.
“The sequence according to the starting points of the descending segment of the suction and discharge pressure curves was louver, wavy and flat fin types, respectively.”
Quote in the paperNot a substantial claim - Findingown data§ 2780 2387.56 3.92 2000 1482.52
The starting points of the descending segment in the COP curves for the three fin types were significantly delayed and much later than those in the heating capacity curves.
“The starting points of the descending segment in COP curves for three fin types were significantly delayed andmuch later than those in the heating capacity curves in Fig. 5dthat is, the curves of COP had the longer ascending segment than those of the heating capacity.”
Quote in the paperNot a substantial claim - Findingreasoning§ 2780 2387.56 3.92 2000 1482.52
The differences in the time-average values of the overall performance parameters among the three fin types were bigger than their peak values.
“In addition, the differences in the time-average values of the overall performance parameters among three fin types were bigger than their peak values, which were attributed to a bigger ratio of the descending segment duration to the ascending duration in the performance parameter curves.”
Quote in the paperSubstantial claim - Interpretationown data§ 2780 2387.56 3.92 2000 1482.52
The higher superheat or refrigerant quality was ascribed to the greater heat amount absorbed by the outdoor heat exchanger.
“The higher superheat or the refrigerant quality was ascribed to the greater heat amount absorbed by the outdoor heat exchanger in Fig. 7.”
Quote in the paperSubstantial claim- The authors state this as an assumption: The frosting period can be regarded as a quasi-static process for computing the heat amount absorbed by the outdoor heat exchanger.
- Premisereasoning§ Introduction
Differences in the distribution of both heat transfer coefficient and temperature along the flowing path between two-phase and single-phase working fluids will influence frosting behavior.
“Inevitably, the differences in the distribution of both the heat transfer coefficient and temperature along the flowing path between the two-phase and single-phase working fluids will influence the frosting behavior.”
Quote in the paperSubstantial claim - Premisecitation§ 2780 2387.56 3.92 2000 1482.52
The first effect of frost is negative: frost increases the thermal resistance between air and refrigerant.
“The first effect of frost is negative that the frost increased the thermal resistance between air and refrigerant.”
Quote in the paperNot a substantial claim0 of 2 sources checked- cites Lenic and Trp [5]
Couldn’t be matched to a paper in Crossref, so it can’t be checked.
- cites Lenic and Trp [15]
Couldn’t be matched to a paper in Crossref, so it can’t be checked.
- Interpretationreasoning§ Abstract
The frosting curves for flat fin decreased always slightly because the outdoor axial fan did not experience the stall zone during the frosting duration of 46.6 min.
“The frosting curves for flat fin decreased always slightly because the outdoor axial fan did not experience the stall zone during the frosting duration of 46.6 min.”
Quote in the paperSubstantial claim - Interpretationown data§ 2780 2387.56 3.92 2000 1482.52
The smallest time-average heating capacity for the louver fin was predominantly attributed to its shortest ascending segment, smallest peak value, and greater falling amplitude relative to the peak.
“Obviously, time-average heating capacity for the louver fin was the smallest, which predominantly attributed to the shortest ascending segment, the smallest peak value and greater falling amplitude relative to the peak value.”
Quote in the paperSubstantial claim - Premisecitation§ Introduction
Under certain outdoor winter conditions, frost forms on the outdoor finned-tube heat exchanger and decreases its thermal performance due to the combined effects of increased thermal resistance and decreased airflow rate caused by frost blocking.
“Under certain outdoor winter conditions, frost forms on the outdoor finned-tube heat exchanger and decreases its thermal performance due to the combined effects of the increased thermal resistance and the decreased airflow rate caused by frost blocking.”
Quote in the paperSubstantial claim0 of 2 sources checked - Interpretationown data
The near equality of frosting and defrosting durations among the three fin types was due to the same defrosting control schemes.
“The frosting time in Table 3 and the defrosting time in Table 4 were almost equal among three fin types, which were ascribed to the same control schemes of the defrosting initiation and termination.”
Quote in the paperNot a substantial claim - Interpretationreasoning§ Introduction
The frosted evaporator will receive feedback from the other components of the closed-loop system.
“Meanwhile, the frosted evaporator also will receive the feedback from the other components.”
Quote in the paperSubstantial claim - Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52
The negative second frost effect of decreased airflow rate surpassed both the negative first frost effect of increased frost layer thermal resistance and the positive third frost effect of increased surface roughness, and resulted in the decrease in the frosting curves for the three fin types in the middle or later frosting period.
“From the analysis above, it was found that the negative second frost effect of decreased airflow rate surpassed both the negative first frost effect of increased frost layer thermal resistance and the positive third frost effect of increased surface roughness, and resulted in the decrease in the frosting curves for three fin types in the middle or later frosting period.”
Quote in the paperSubstantial claim - Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52
The performance curves for the flat fin decreased always gradually instead of rapidly and gradually at last.
“Hence, performance curves for flat fin decreased always gradually instead of then rapidly and gradually at last.”
Quote in the paperSubstantial claim - Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52
The bigger differences in the time-average values than the peak values were attributed to a bigger ratio of the descending segment duration to the ascending duration in the performance parameter curves.
“In addition, the differences in the time-average values of the overall performance parameters among three fin types were bigger than their peak values, which were attributed to a bigger ratio of the descending segment duration to the ascending duration in the performance parameter curves.”
Quote in the paperSubstantial claim - Interpretationown data§ 2780 2387.56 3.92 2000 1482.52
The heat amount absorbed by the outdoor heat exchanger was the dominant factor in the variation of the heating capacity with frosting time.
“These suggested that the heat amount absorbed by the outdoor heat exchanger was the dominant factor in the variation of the heating capacity with the frosting time.”
Quote in the paperSubstantial claim- The authors state this as an assumption: The frosting period can be regarded as a quasi-static process for computing the heat amount absorbed by the outdoor heat exchanger.
- Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52
The superheat or refrigerant quality at compressor suction was higher for the flat fin than for the wavy and louver fin types.
“The discharge temperature for flat fin was always greater than those for wavy and louver fins, which suggested the superheat or the refrigerant quality at compressor suction was higher for flat fin than those for wavy and louver fin types.”
Quote in the paperSubstantial claim - Study design and conductown data
The experimental data had good repetitiveness for louver fin.
“Both Fig. 4 and Table 2 suggested that the experimental data had good repetitiveness for louver fin.”
Quote in the paperNot a substantial claim - Interpretationnone given§ 2780 2387.56 3.92 2000 1482.52
The first and second effects of frost could not explain the initial ascending segments of the performance parameter curves, especially the longer ascending segments for the flat fin type.
“However, the first and second effects could not explain the initial ascending segments of performance parameter curves in Figs. 5e12, especially longer ascending segments for flat fin type.”
Quote in the paperSubstantial claim - Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52
The frosting curves for the flat fin decreased always slightly instead of rapidly and gradually at last.
“Hence, frosting curves for flat fin decreased always slightly instead of then rapidly and gradually at last.”
Quote in the paperSubstantial claim - Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52
Different variation modes of the frosting curves among the three fin types were ascribed to the combination of the outdoor axial fan characteristic curve with air pressure drops across the outdoor heat exchanger under different frost thickness.
“Different variation modes of the frosting curves among three fin types were ascribed to the combination of outdoor axial fan characteristic curve with air pressure drops across the outdoor heat exchanger under different frost thickness.”
Quote in the paperSubstantial claim
- Classified as probably not a substantial claim. 13
- May combine two claims. 29
Probably not a substantial claim: may not pass S3 (load-bearing). May combine two claims.
Premisecitation§ 2780 2387.56 3.92 2000 1482.52The louver fin had the most frost accumulation amount and the greatest air pressure drop, followed by the wavy and flat fins.
“Some experimental results showed the louver fin had the most frost accumulation amount and the greatest air pressure drop, followed the wavy and flat fins.”
Quote in the paperNot a substantial claim1 of 3 sources checked- cites Silva and Hermes [1] da Silva, 2011, Experimental study of frost accumulation on fan-supplied tube-fin evaporators, Appl. Therm. Eng. source
- cites Yan and Li [10] Yan, 2005, Thermofluid characteristics of frosted finned-tube heat exchanger, Int. J. Heat Mass Transfer source
The Results and discussion (pp. 4–5) report the greatest frost accumulation and pressure drop for re-direction louver fins. The paper compares re-direction louver, one-sided louver, and flat plate fins—not wavy fins—so it does not support the claimed louver–wavy–flat ranking. (LLM, conf=0.88)
Experimental — accuracy not yet measured - cites Kondepudi and O'Neal [11] Kondepudi, 1990, The effects of different fin configurations on the performance of finned-tube heat exchangers under frosting conditions, ASHRAE Trans.
May combine two claims.
Findingown dataThe differences in time-average COP among the three fin types were greater, and the flat fin had the greatest COP, followed by wavy and louver fins respectively.
“However, the differences in the time-average COP among three fin types were greater, and the flat fin had the greatest COP, followed by wavy and louver fins, respectively.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52The heating capacity curve for wavy fin started to drop at the 24.33rd minute with a peak value of 6438.71 W.
“The heating capacity curve for wavy fin started to drop at the 24.33rd minute with the peak value of 6438.71 W.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown dataThe peak and time-average heating capacity for wavy fin were 6428.82 W and 5410.38 W, respectively, greater by 5.2% and 7.4% than those for louver fin.
“Those for wavy fin were 6428.82Wand 5410.38W, respectively, which were greater by 5.2% and 7.4% than those for louver fin.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52The curves of the heat amount absorbed by the outdoor heat exchanger were similar in shape to the heating capacity and input power curves, but had greater amplitude of variation than the input power curves.
“Obviously, the curves of the heat amount absorbed by outdoor heat exchanger in Fig. 7 were similar in the shapes to the curves of heating capacity in Fig. 5 and input power in Fig. 6, but had greater amplitude of variation than those of the input power in Fig. 6.”
Quote in the paperSubstantial claim- The authors state this as an assumption: The frosting period can be regarded as a quasi-static process for computing the heat amount absorbed by the outdoor heat exchanger.
Probably not a substantial claim: may not pass S3 (load-bearing). May combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52Because the input power was almost zero at the moments of both defrosting initiation and termination, the corresponding COP was beyond the range of normal value.
“In addition, because the input power in Fig. 6 was almost a zero at the moments of both the defrosting initiation and termination, accordingly the corresponding COP in Fig. 8 was beyond the range of normal value.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52The points where the heating capacity curves started to descend and the peak values of heating capacity had great differences among the three fin types.
“However, the points where the heating capacity curves started to descend and the peak values of the heating capacity had great differences among three fin types.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52The starting point was at the 24.58th minute for flat fin, the latest among the three fin types, and the corresponding maximum heating capacity was 6591.13 W.
“The starting point was at the 24.58th minute for flat fin, the latest one among three fin types, and the corresponding maximum heating capacity was 6591.13 W.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown dataThe peak and time-average heating capacity for flat fin were 6590.61 W and 5894.33 W, respectively, greater by 7.8% and 17.1% than 6112.68 W and 5035.4 W for louver fin.
“Meanwhile, the peak and time-average values of the heating capacity for flat fin were 6590.61 W and 5894.33 W, respectively, which were greater by 7.8% and 17.1% than those of 6112.68 W and 5035.4 for louver fin.”
Quote in the paperSubstantial claimProbably not a substantial claim: may not pass S3 (load-bearing).
Findingown data§ 2780 2387.56 3.92 2000 1482.52The suction and discharge temperatures had similar curve shapes to the suction and discharge pressures.
“Obviously, suction and discharge temperatures had the similar curve shapes as the suction and discharge pressures in Figs. 9 and 10.”
Quote in the paperNot a substantial claimProbably not a substantial claim: may not pass S1 (asserted), S3 (load-bearing), S4 (based).
Findingnone given§ 2780 2387.56 3.92 2000 1482.52The suction and discharge pressures for the wavy and louver fin types gradually increased at first, then decreased rapidly and gradually at last.
“Similar to the heating capacity in Fig. 5 and the input power in Fig. 6, the suction and discharge pressures for flat fin increased at first, and then gradually decreased, while the input power for wavy and louver fin types gradually increased at first, then decreased rapidly and gradually at last.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown data§ AbstractThe flat fin had the best thermal performance of the air-source heat pump, followed by wavy and louver fins.
“The experimental results showed the flat fin had the best thermal performance of the air-source heat pump, followed by wavy and louver fins.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown dataThe peak and time-average COP for flat fin were 2.52 and 2.3, respectively, greater by 3.7% and 9.0% than 2.43 and 2.11 for louver fin.
“The peak and time-average values of COP for flat fin were 2.52 and 2.3, respectively, and were greater by 3.7% and 9.0% than those of 2.43 and 2.11 for louver fin.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52The input power for the flat fin began to drop latest and most gently.
“Input power for flat fin began to drop not only the latest but also most gently.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52The flat fin had the best thermal performance of the residential heat pump in the periodic frosting/defrosting cycles, followed by the wavy and louver fins.
“The experimental results the flat fin had the best thermal performance of the residential heat pump in the periodic frosting/defrosting cycles, followed by wavy and louver fins.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52The starting point of the descending segment was at the 17.83rd minute for louver fin, the earliest among the three fin types, and the heating capacity arrived at a peak value of 6121.90 W.
“The starting point of the descending segment was at the 17.83rdminute for louver fin in Fig. 5, the earliest one among three fin types, and the heating capacity arrived at the peak value of 6121.90 W.”
Quote in the paperNot a substantial claimMay combine two claims.
Findingown dataThe peak and time-average COP for wavy fin were 2.5 and 2.2, respectively, greater by 2.9% and 4.3% than those for louver fin.
“Those for wavy fin were 2.5 and 2.2, respectively, which were greater by 2.9% and 4.3% than those for louver fin.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 2780 2387.56 3.92 2000 1482.52Although the starting points of the descending segment were almost equal for flat and wavy fins, the peak heating capacity for flat fin was bigger by 2.37% or 152.51 W than that for wavy fin.
“Regardless of the fact that the starting points of the descending segment were almost equal for flat and wavy fins, but the peak value of the heating capacity for flat fin was bigger by 2.37% or 152.51 W than that for wavy fin.”
Quote in the paperNot a substantial claimMay combine two claims.
Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52The frosting curves for the wavy fin decreased rapidly when the axial fan experienced the stall zone, and decreased slightly at last after the stall zone was passed through.
“Hence, frosting curves for wavy fin decreased rapidly when the axial fan experienced the stall zone, and decreased slightly at last after the stall zone was went through.”
Quote in the paperSubstantial claimProbably not a substantial claim: may not pass S4 (based). May combine two claims.
Premisenone given§ IntroductionThe real refrigerant temperature along the flowing path at the evaporating two-phase zone decreases owing to pressure drop, while the temperature of a single-phase working fluid always increases.
“The real refrigerant temperature along the flowing path at the evaporating two-phase zone decreases owing to the pressure drop, while the temperature of a single-phaseworking fluid always increases.”
Quote in the paperNot a substantial claimMay combine two claims.
Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52The wavy fin had less frost accumulation amount and smaller air pressure drop than the louver fin, and it experienced the stall zone of the axial fan later.
“The wavy fin had less frost accumulation amount and smaller air pressure drop than the louver fin, and it experienced the stall zone of the axial fan later.”
Quote in the paperSubstantial claimMay combine two claims.
Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52The axial fan experienced the stall zone from Point 3 to Point 4 and its airflow rate decreased faster, and accordingly the frosting curves for the louver fin decreased rapidly.
“Therefore the axial fan experienced the stall zone from Point 3 to Point 4 and its airflow rate was faster decreased, and accordingly the frosting curves for louver fin in Figs. 5e12 decreased rapidly.”
Quote in the paperSubstantial claimProbably not a substantial claim: may not pass S4 (based). May combine two claims.
Premisenone given§ IntroductionThe real air-source heat pump is a closed-loop system and consists of four main components that interrelate with each other.
“The real air-source heat pump is a closed-loop system, and consists of the four main components which interrelate with each other.”
Quote in the paperNot a substantial claimProbably not a substantial claim: may not pass S3 (load-bearing).
Study design and conductnone givenAll temperature and pressure sensors on the residential heat pump were calibrated to reduce experimental uncertainties.
“All temperature and pressure sensors on the residential heat pump were calibrated to reduce experimental uncertainties.”
Quote in the paperNot a substantial claimProbably not a substantial claim: may not pass S3 (load-bearing).
Study design and conductnone givenThe relative error of pressure sensors over an effective measurement range of 0 to 25 bars was ±0.25%.
“The relative error of pressure sensors over effective measurement range of 0e25 bars was �0.25%.”
Quote in the paperNot a substantial claimProbably not a substantial claim: may not pass S3 (load-bearing).
Study design and conductnone givenThe temperature sensors were T-type thermocouples calibrated with a standard water bath over a temperature range of -30 to 120 °C and having an error of ±0.2 °C.
“The temperature sensors were T-type thermocouples calibrated with a standard water bath over a temperature range of �30e120 �C and having an error of �0.2 �C.”
Quote in the paperNot a substantial claimProbably not a substantial claim: may not pass S3 (load-bearing).
Study design and conductcitationUncertainties reported in the present study were estimated following the single-sample method proposed by Moffat [25].
“Uncertainties reported in the present study are estimated following the single-sample method proposed by Moffat [25].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites Moffat [25] Moffat, 1988, Describing the uncertainties in experimental results, Exp. Therm. Fluid Sci. source
Probably not a substantial claim: may not pass S4 (based). May combine two claims.
Premisenone given§ IntroductionThe heat transfer coefficient of real two-phase refrigerant varies markedly along the flowing path due to quality variation, while that of a single-phase working fluid stays almost constant except for a shorter entrance effect.
“The heat transfer coefficient of the real two-phase refrigerant varies along the flowing path markedly due to its quality variation, while that of a single-phase working fluid stays almost constant except the shorter entrance effect.”
Quote in the paperNot a substantial claimMay combine two claims.
Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52The flat fin had the least frost accumulation amount and smallest air pressure drop, and it did not experience the stall zone of the axial fan during the frosting time of 46.6 min.
“However, the flat fin had the least frost accumulation amount and smallest air pressure drop, and it did not experience the stall zone of the axial fan, during the frosting time of 46.6 min.”
Quote in the paperSubstantial claimProbably not a substantial claim: may not pass S4 (based). May combine two claims.
Interpretationreasoning§ IntroductionThe frosted evaporator will affect compressor performance by decreasing suction pressure and temperature, and will furthermore influence the performance of the condenser and the expansion valve.
“The frosted evaporator will affect the compressor performance by the decrease in the suction pressure and temperature, and furthermore influence the performance of the condenser and the expansion valve.”
Quote in the paperNot a substantial claimProbably not a substantial claim: may not pass S4 (based).
Interpretationnone given§ 2780 2387.56 3.92 2000 1482.52There should be decisive effects of frost that resulted in the initial ascending segments of the performance parameter curves.
“There should be the decisive effects of frost which resulted in the initial ascending segments of performance parameter curves.”
Quote in the paperNot a substantial claimMay combine two claims.
Interpretationreasoning§ AbstractThe frosting curves for wavy and louver fin types decreased rapidly because the outdoor axial fan experienced the stall zone caused by more frost accumulation and greater air pressure drop, and decreased slightly at last after the stall zone was passed through.
“The frosting curves for wavy and louver fin types decreased rapidly because the outdoor axial fan experienced the stall zone caused by more frost accumulation and greater air pressure drop, and decreased slightly at last after the stall zone was went through.”
Quote in the paperSubstantial claimMay combine two claims.
Interpretationreasoning§ IntroductionThe experimental results in this paper were widely dissimilar from those of Kondepudi and O'Neal [11], and even contrary to each other.
“Hence, the experimental results in this paper were widely dissimilar from those of Kondepudi and O'Neal [11], and even contrary to each other.”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites Kondepudi and O'Neal [11] Kondepudi, 1990, The effects of different fin configurations on the performance of finned-tube heat exchangers under frosting conditions, ASHRAE Trans.
May combine two claims.
Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52The louver fin had the most frost accumulation amount and the greatest and fastest air pressure drop, resulting in the earliest occurrence of Point 3.
“The louver fin had the most frost accumulation amount and the greatest and fastest air pressure drop, resulting in the earliest occurrence of Point 3.”
Quote in the paperSubstantial claimMay combine two claims.
Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52The flat fin had the least frost accumulation amount and smallest air pressure drop, and the axial fan did not experience the stall zone during the frosting time of 46.6 min.
“However, the flat fin had the least frost accumulation amount and smallest air pressure drop, and the axial fan did not experience the stall zone, during the frosting time of 46.6 min.”
Quote in the paperSubstantial claimMay combine two claims.
Interpretationreasoning§ 2780 2387.56 3.92 2000 1482.52The frosting curves for the wavy and louver fin types decreased rapidly when the axial fan experienced the stall zone, and decreased slightly at last after the stall zone was passed through.
“The frosting curves for wavy and louver fin types decreased rapidly when the axial fan experienced the stall zone, and decreased slightly at last after the stall zone was went through.”
Quote in the paperSubstantial claim
The authors state this as an assumption.
The frosting period can be regarded as a quasi-static process for computing the heat amount absorbed by the outdoor heat exchanger.
“the heat amount absorbed by outdoor heat exchanger in Fig. 7 was obtained by subtracting the input power from the heating capacity if the frosting period was regarded as a quasi-static process.”
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
The time-average COP of wavy fins was 4.3% higher than that of louver fins.
“The time-average COP values for flat and wavy fins were 9.0% and 4.3% higher than, those for louver fins, respectively.”
The differences in time-average heating capacity and COP values among the three fin types were greater than those in the peak heating capacity and COP values.
“In addition, the differences in time-average heating capacity and COP values among the three fin types were greater than those in the peak heating capacity and COP values.”
The time-average heating capacity of flat fins was 17.1% greater than that of louver fins.
“The time-average heating capacity values for flat and wavy fins were 17.1% and 7.4% greater than, those for louver fins, respectively.”
The time-average heating capacity of wavy fins was 7.4% greater than that of louver fins.
“The time-average heating capacity values for flat and wavy fins were 17.1% and 7.4% greater than, those for louver fins, respectively.”
The time-average COP of flat fins was 9.0% higher than that of louver fins.
“The time-average COP values for flat and wavy fins were 9.0% and 4.3% higher than, those for louver fins, respectively.”
The heat exchanger with flat fins had the best thermal performance of the air-source heat pump, followed by those with wavy and louver fins.
“They concluded that the heat exchanger with flat fins had the best thermal performance of the air-source heat pump, followed by those with wavy and louver fins.”
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Flat-fin defrosting time differs from abstract claim
MajorThe abstract says defrosting lasted about 3.9 minutes for each fin type, but Table 4 gives 4.72 minutes for the flat fin.
“the frosting/ defrosting durations were almost equal, about 46.6 min and 3.9 min for each fin type”
“Flat 4.72 2015.67 1219.35”
Performance ranking names the flat fin twice
MinorThe text ranks flat first and then says the remaining fin types are wavy and flat, contradicting its stated ranking of flat, wavy and louver.
“the flat fin had the best thermal performance of the air-source heat pump, followed by the wavy and flat fin types.”
“the flat fin had the best thermal performance of the air-source heat pump, followed by wavy and louver fins.”
Cites
Describing the uncertainties in experimental results
Moffat, R. J. (1988) · Experimental Thermal and Fluid Science · doi:10.1016/0894-1777(88)90043-x · Cited by 9,860 · see citing works
Experimental study on frost growth and dynamic performance of air source heat pump system
Guo, X.-M., Chen, Y.-G., Wang, W.-H., & Chen, C.-Z. (2008) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2008.01.007 · Cited by 173 · see citing works
Effect of surface treatments on the frosting/defrosting behavior of a fin-tube heat exchanger
Jhee, S., Lee, K.-S., & Kim, W.-S. (2002) · International Journal of Refrigeration · doi:10.1016/s0140-7007(02)00008-7 · Cited by 149 · see citing works
Experimental study of frost accumulation on fan-supplied tube-fin evaporators
da Silva, D. L., Hermes, C. J. L., & Melo, C. (2011) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2010.11.006 · Cited by 118 · see citing works
Frosting and defrosting characteristics of a fin according to surface contact angle
Kim, K., & Lee, K.-S. (2011) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2011.02.065 · Cited by 108 · see citing works
Performance of finned tube heat exchangers operating under frosting conditions
Yan, W.-M., Li, H.-Y., Wu, Y.-J., Lin, J.-Y., & Chang, W.-R. (2003) · International Journal of Heat and Mass Transfer · doi:10.1016/s0017-9310(02)00346-0 · Cited by 95 · see citing works
Transient two-dimensional model of frost formation on a fin-and-tube heat exchanger
Lenic, K., Trp, A., & Frankovic, B. (2009) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2008.06.005 · Cited by 92 · see citing works
Zhang, P., & Hrnjak, P. S. (2009) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2008.11.006 · Cited by 75 · see citing works
Tso, C. P., Cheng, Y. C., & Lai, A. C. K. (2006) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2005.04.009 · Cited by 75 · see citing works
A new model for predicting performance of fin-and-tube heat exchanger under frost condition
Cui, J., Li, W. Z., Liu, Y., & Zhao, Y. S. (2011) · International Journal of Heat and Fluid Flow · doi:10.1016/j.ijheatfluidflow.2010.11.004 · Cited by 74 · see citing works
Self-citationFirst-principles modeling of frost accumulation on fan-supplied tube-fin evaporators
da Silva, D. L., Hermes, C. J. L., & Melo, C. (2011) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2011.04.029 · Cited by 70 · see citing works
Modeling non-uniform frost growth on a fin-and-tube heat exchanger
Padhmanabhan, S. K., Fisher, D. E., Cremaschi, L., & Moallem, E. (2011) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2011.06.005 · Cited by 66 · see citing works
Lee, M., Kim, Y., Lee, H.-S., & Kim, Y. (2010) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2010.02.047 · Cited by 63 · see citing works
Fan supplied heat exchanger fin performance under frosting conditions
Chen, H., Thomas, L., & Besant, R. W. (2003) · International Journal of Refrigeration · doi:10.1016/s0140-7007(02)00011-7 · Cited by 59 · see citing works
Kim, K., & Lee, K.-S. (2012) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2012.06.076 · Cited by 56 · see citing works
(1990) · ASHRAE Transactions (American Society of Heating, Refrigerating and Air-Conditioning Engineers) · Cited by 55 · see citing works
Thermofluid characteristics of frosted finned-tube heat exchangers
Yan, W.-M., Li, H.-Y., & Tsay, Y.-L. (2005) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2005.02.018 · Cited by 52 · see citing works
Huang, J.-M., Hsieh, W.-C., Ke, X.-J., & Wang, C.-C. (2008) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2007.06.020 · Cited by 41 · see citing works
Song, X., Huang, D., Li, X., & Chen, Q. (2012) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2012.02.024 · Cited by 39 · see citing works
Self-citationLenic, K., Trp, A., & Frankovic, B. (2009) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2008.12.030 · Cited by 38 · see citing works
An experimental study on frosting of laminar air flow on a cold surface with local cooling
Kwon, J.-T., Lim, H. J., Kwon, Y.-C., Koyama, S., Kim, D.-H., & Kondou, C. (2006) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2005.12.009 · Cited by 35 · see citing works
Frost behavior on a fin considering the heat conduction of heat exchanger fins
Kim, J.-S., Lee, K.-S., & Yook, S.-J. (2009) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2008.12.023 · Cited by 25 · see citing works
Characteristics of frost formation on two-dimensional fins and its empirical correlations
Kim, K., Kim, J.-S., & Lee, K.-S. (2010) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2010.02.043 · Cited by 25 · see citing works
Study on heat and mass transfer characteristics of humid air-flow in a fin bundle
Kim, D.-H., Koyama, S., Kuwahara, K., Kwon, J.-T., & Park, B.-D. (2010) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2010.05.013 · Cited by 6 · see citing works
Frost distribution characteristics of laminar airflow on cold surface of mini-channels
Kwon, J., Kim, D., Huh, C., Koyama, S., & Kwon, Y.-C. (2011) · International Communications in Heat and Mass Transfer · doi:10.1016/j.icheatmasstransfer.2011.04.007 · Cited by 3 · see citing works
Flagged first, then by citations
Research works printed but not linked: 1
- Kondepudi, 1987, The effect of frost growth on extended surface heat exchanger performance: a review, ASHRAE Trans., 93, 258
Cited by
Sorted by citations
Review on improvement for air source heat pump units during frosting and defrosting
Song, M., Deng, S., Dang, C., Mao, N., & Wang, Z. (2018) · Applied Energy · doi:10.1016/j.apenergy.2017.12.022 · Cited by 384 · see citing works
Amer, M., & Wang, C.-C. (2017) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2017.01.120 · Cited by 218 · see citing works
Research of anti-frosting technology in refrigeration and air conditioning fields: A review
Feng, W., Liang, C.-H., & Zhang, X. (2018) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2017.08.046 · Cited by 142 · see citing works
Effects of surface characteristic on frosting and defrosting behaviors of fin-tube heat exchangers
Wang, F., Liang, C., Yang, M., Fan, C., & Zhang, X. (2015) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2014.10.090 · Cited by 142 · see citing works
Zhang, Y.-N., Ma, Q.-Y., Li, B.-X., Fan, X.-M., & Fu, Z.-B. (2017) · Energy and Buildings · doi:10.1016/j.enbuild.2016.12.044 · Cited by 116 · see citing works
Song, M., Mao, N., Xu, Y., & Deng, S. (2019) · Thermal Science and Engineering Progress · doi:10.1016/j.tsep.2019.03.002 · Cited by 92 · see citing works
Aljashaami, B. A., Ali, B. M., Salih, S. A., Alwan, N., Majeed, M. H., Ali, O. M., Alomar, O., Velkin, V., & Shcheklein, S. (2024) · Results in Engineering · doi:10.1016/j.rineng.2024.102769 · Cited by 78 · see citing works
Patil, M. S., Seo, J.-H., & Lee, M.-Y. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.11.107 · Cited by 86 · see citing works
Song, M., Xia, L., Mao, N., & Deng, S. (2015) · Applied Energy · doi:10.1016/j.apenergy.2015.11.036 · Cited by 85 · see citing works
Chung, Y., Yoo, J. W., Kim, G. T., & Kim, M. S. (2019) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2018.10.085 · Cited by 81 · see citing works
Bacellar, D., Aute, V., Huang, Z., & Radermacher, R. (2017) · Science and Technology for the Built Environment · doi:10.1080/23744731.2017.1333877 · Cited by 82 · see citing works
“Huang et al. (2014b) developed a variable geometry MCHX design approach to address flow mal-distributions while optimizing material usage and localized thermal-hydraulic performance.”
BackgroundMethodInfluentialSong, M., Chen, A., & Mao, N. (2015) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2015.10.082 · Cited by 62 · see citing works
Wang, C., Gong, G., Su, H., et al. (2015) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2015.04.172 · Cited by 61 · see citing works
Wang, F., Zhou, Y., Yang, W., Ni, M., Zhang, X., & Liang, C. (2020) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2020.114967 · Cited by 60 · see citing works
Effect of frost morphology on the thermal-hydraulic performance of fan-supplied tube-fin evaporators
da Silva, D. L., Melo, C., & Hermes, C. J. L. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.09.165 · Cited by 58 · see citing works
Experimental and numerical investigations of frost formation on wavy plates
Ma, Q., Wu, X., Chu, F., & Zhu, B. (2018) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2018.04.098 · Cited by 56 · see citing works
Ma, L., Sun, Y., Wang, F., Wang, M., Zhang, S., & Wang, Z. (2025) · Applied Energy · doi:10.1016/j.apenergy.2024.124358 · Cited by 54 · see citing works
Perna, C. D., Magri, G., Giuliani, G., et al. (2014) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2014.10.007 · Cited by 50 · see citing works
The frosting and soil imbalance performance issues of building heat pumps: an overview
Bisengimana, E., Zhou, J.-Z., Binama, D. M., Zhao, K., Abbas, S., & Yuan, Y. (2022) · Energy and Buildings · doi:10.1016/j.enbuild.2022.112387 · Cited by 37 · see citing works
Yang, B.-W., Dong, J.-K., Zhang, L., Song, M., Jiang, Y.-Q., & Deng, S. (2019) · Applied Energy · doi:10.1016/j.apenergy.2019.01.079 · Cited by 45 · see citing works
Klingebiel, J., Hassan, M., Venzik, V., Vering, C., & Müller, D. (2023) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2023.121072 · Cited by 44 · see citing works
Li, Z., Zhao, D. H., Ding, G., Ren, T., Miao, S., Han, X., & Noda, T. (2017) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2017.03.003 · Cited by 41 · see citing works
Feng, W., Liang, C.-H., Zhang, X., & Zhang, Y. (2018) · Experimental Thermal and Fluid Science · doi:10.1016/j.expthermflusci.2018.01.022 · Cited by 32 · see citing works
Zhao, R., Huang, D., Peng, X., & Lin, Q. (2019) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2019.12.002 · Cited by 36 · see citing works
Self-citationFrosting in heat pump evaporators part A: experimental investigation
Reichl, C., Sandström, C., Hochwallner, F., Linhardt, F., Popovac, M., & Emhofer, J. (2021) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2021.117487 · Cited by 34 · see citing works
Zhu, Z., Liang, H., & Sun, D. (2023) · ACS Applied Materials & Interfaces · doi:10.1021/acsami.3c02342 · Cited by 33 · see citing works
Research on defrost free air-source heat pump with surface stripe concavo-convex fins
Yajima, T., OHKUBO, H., & Seki, M. (2020) · Energy and Buildings · doi:10.1016/j.enbuild.2020.110568 · Cited by 32 · see citing works
Zhang, Y., Zhang, G., Zhou, D., Zhang, J., Qu, X., Zhang, Z., & He, F. (2024) · Journal of Cleaner Production · doi:10.1016/j.jclepro.2024.141469 · Cited by 27 · see citing works
A Critical Literature Review of Defrost Technologies for Heat Pumps and Refrigeration Systems
Nawaz, K., Elatar, A., & Fricke, B. A. (2018) · doi:10.2172/1474464 · Cited by 31 · see citing works
Li, Z., Wei, W., Wang, W., Sun, Y., Wang, S., Lin, Y., Huang, C., & Deng, S. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2023.122136 · Cited by 30 · see citing works
Experimental investigation on an air source heat pump system with a novel anti-frosting evaporator
Yu, S., Su, Y., Cai, W., & Qiu, G. (2023) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2022.119910 · Cited by 29 · see citing works
Sarmiento, A. P., de Sá Sarmiento, F. I. P., Shooshtari, A., & Ohadi, M. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2024.123680 · Cited by 29 · see citing works
Frosting in a heat pump evaporator part B: Numerical analysis
Popovac, M., Emhofer, J., & Reichl, C. (2021) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2021.117488 · Cited by 26 · see citing works
Bhadra, S., & Mwesigye, A. (2025) · Renewable Energy · doi:10.1016/j.renene.2025.122682 · Cited by 26 · see citing works
Zhao, R., Huang, D., Zhang, Z., & Leng, Y. (2016) · Science and Technology for the Built Environment · doi:10.1080/23744731.2016.1210972 · Cited by 26 · see citing works
“Researchers have found that frost formation will reduce the cooling capacity of refrigeration systems by as much as 20% (Chen et al. 2003; Hewitt and Huang 2008; Huang et al. 2014; O’Neal et al. 1989).”
BackgroundSelf-citationZhao, R., Huang, D., Peng, X., & Yang, H. (2018) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2018.12.003 · Cited by 26 · see citing works
Self-citationDuan, L., Ling, X., & Peng, H. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2017.09.026 · Cited by 24 · see citing works
Wei, W.-Z., Feng, Z., Ni, L., Wang, W., Jin, X., Tang, R., & Zhao, S. (2023) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2023.121698 · Cited by 21 · see citing works
Park, J.-S., Kim, J., & Lee, K.-S. (2017) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2017.01.043 · Cited by 24 · see citing works
A novel design method for ASHPs considering output heating capacity and frosting suppression
Liang, S., Wang, W., Sun, Y.-Y., Li, Z.-Y., Zhao, J.-H., Lin, Y., & Deng, S. (2020) · Energy and Buildings · doi:10.1016/j.enbuild.2020.110099 · Cited by 26 · see citing works
Review and prospect of air source heat pump research: A bibliometric insight
Jiang, S., Zhao, H., & Ni, L. (2024) · International journal of refrigeration · doi:10.1016/j.ijrefrig.2024.11.029 · Cited by 20 · see citing works
Pu, J., Shen, C., Zhang, C., & Yan, X. (2022) · Energy and Buildings · doi:10.1016/j.enbuild.2022.111939 · Cited by 23 · see citing works
Ma, D., Chen, Q., & Yan, G. F. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2024.123359 · Cited by 22 · see citing works
Anti-frosting operation and regulation technology of air-water dual-source heat pump evaporator
Zhong, H., Li, Z., Long, J., Xia, K., Lu, H., & Yongga, A. (2022) · Energy · doi:10.1016/j.energy.2022.124393 · Cited by 21 · see citing works
Bai, X., Liu, S., Deng, S., Zhang, L., & Wei, M. (2023) · Energy and Buildings · doi:10.1016/j.enbuild.2023.113136 · Cited by 21 · see citing works
Wang, F., Xiang, M., & Yang, W. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2023.121881 · Cited by 20 · see citing works
Liang, X.-Y., & Wu, L. (2022) · Energy and Buildings · doi:10.1016/j.enbuild.2022.112366 · Cited by 18 · see citing works
Kwon, J., Yun, S., Lee, S., Cho, W., & Kim, Y. (2021) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2021.122245 · Cited by 19 · see citing works
An experimental study on a novel defrosting method for cold room
Abdulla, M. O. A., Deniz, E., Karagöz, M., & Gürüf, G. (2021) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2021.116573 · Cited by 17 · see citing works
Wang, W., Di, H., Tang, R., Wei, W., Sun, Y., & Dai, C. (2024) · Building and Environment · doi:10.1016/j.buildenv.2024.112258 · Cited by 16 · see citing works
Simulation and Optimization Study on the Performance of Fin-and-Tube Heat Exchanger
Jing, N.-J., Xia, Y.-D., Ding, Q., Chen, Y.-Z., Wang, Z.-Q., & Zhang, X.-J. (2023) · Sustainability · doi:10.3390/su151511587 · Cited by 13 · see citing works
Hou, Z., Yang, Z., Zhao, Y., Zhao, X., Sun, B., Wang, G., & Xie, T. (2023) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2023.122033 · Cited by 15 · see citing works
Tang, R., Wei, W.-Z., Sun, P., Zhao, J.-H., Wang, W., Sun, Y.-Y., & Deng, S. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2024.124850 · Cited by 12 · see citing works
Wu, S., Zhao, R., Huang, D., Sun, Y. J., & Wei, X. (2020) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2020.12.010 · Cited by 15 · see citing works
Self-citationInvestigation of air cooler fan start-up delay in liquid refrigerant defrosting system
Wang, M., Zang, R., Hu, E., & Ezzat, A. W. (2018) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2018.07.066 · Cited by 13 · see citing works
Wu, G., Ding, G., & Ren, T. (2020) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2020.03.016 · Cited by 12 · see citing works
Wei, H., Guo, X., Li, Z., Yang, X., Tang, Z., Fu, C., & Dong, W. (2022) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2022.118104 · Cited by 12 · see citing works
Fei, W., Zhao, R., Ma, C., Huang, D., & Qu, Z. (2022) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2022.06.021 · Cited by 12 · see citing works
Self-citationHuang, D., Zhao, R., Gong, Q., et al. (2014) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2014.08.011 · Cited by 12 · see citing works
Self-citationFrost formation non-uniformity in a multi-circuit V-shape evaporator
Alvandifar, N., Kristófersson, J., & Forooghi, P. (2023) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2023.10.018 · Cited by 11 · see citing works
Investigation on thermal-hydraulic performance of outdoor heat exchanger in air sources heat pump
Fang, Z.-S., Li, L., Cheng, Y., Wang, H.-H., & Oladokun, M. (2017) · Experimental Thermal and Fluid Science · doi:10.1016/j.expthermflusci.2017.01.008 · Cited by 6 · see citing works
“Some other researchers have equally examined the frost formation and effect of frost layer on the performance of fin-tube heat exchanger [21-26].”
BackgroundResultExperimental study of solution defrosting characteristics of air source heat pump
Jiang, P., Zhang, Y., Fan, H., Jin, Q., & Yu, Y. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2023.121575 · Cited by 7 · see citing works
A prediction model of air-source heat pump system performance with frost-retarded heater
Wu, S., Sun, Y. J., Wang, F., Ma, Z., Zhao, R., & Huang, D. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2024.123315 · Cited by 8 · see citing works
Self-citationFrost Detection and Defrost Control: Emerging Trends, Methods, and Experimental Evaluations
Hassan, H., Akbar, H., Malik, A. N., Nawaz, T., Elahi, H., Rahman, H. U., & Lazoglu, I. (2025) · International journal of refrigeration · doi:10.1016/j.ijrefrig.2025.08.005 · Cited by 4 · see citing works
Zhao, R., Wang, Z., Sun, Y. J., et al. (2022) · Applied Sciences · doi:10.3390/app12188960 · Cited by 6 · see citing works
Self-citationDing, S.-J., Zhang, Y., Zhou, D., Zhang, Z., Tian, M.-C., & Zhang, G.-M. (2025) · International Journal of Heat and Fluid Flow · doi:10.1016/j.ijheatfluidflow.2025.109761 · Cited by 6 · see citing works
Zhao, R., Sun, Y. J., Wang, F., et al. (2022) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2022.09.012 · Cited by 6 · see citing works
Self-citationMa, C., Ge, X., Zheng, H., Song, M., Sheng, W., Chen, X.-Z., Fu, D.-Y., & Dang, C.-B. (2025) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2025.127205 · Cited by 5 · see citing works
Simulation and experiment on pneumatic defrosting of evaporators with heat storage
Ni, P., Lv, Z., Jiang, H., Hua, R., Wang, X.-L., Zhang, X.-W., & Li, X. (2023) · Case Studies in Thermal Engineering · doi:10.1016/j.csite.2023.103596 · Cited by 5 · see citing works
Li, J., Long, J., Tan, X., & Zhang, R. (2024) · Advances in Building Energy Research · doi:10.1080/17512549.2024.2365944 · Cited by 5 · see citing works
“…frosting/defrosting performance in terms of the shape, structural dimensions, and surface coatings of the evaporator fi ns. Huang et al. compared the frosting/defrosting cycles of air source heat pumps fi tted with three di ff erent fi ns (corrugated, louvered, and fl at) (Huang et al., 2014).”
An analytical model for predicting the particle-deposited fin efficiency
Zhan, F., Zhuang, D., & Ding, G. (2018) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2018.03.021 · Cited by 5 · see citing works
Experimental study on performance optimization of air source heat pump using DOE method
Fang, Z., Feng, X., Zheng, Z., Zhou, X., Li, L., Huang, Y. J., Wang, H., & Liu, F. (2018) · Experimental Heat Transfer · doi:10.1080/08916152.2018.1505787 · Cited by 5 · see citing works
“[20] investigated the heat transfer characteristics of the heat exchanger with flattype, wavy-type, and louvre-type fins experimentally.”
BackgroundZhao, R., Huang, D., Peng, X., & Yang, H. (2019) · Science and Technology for the Built Environment · doi:10.1080/23744731.2019.1665445 · Cited by 5 · see citing works
“Frost exists widely on evaporator surfaces of refrigeration and air-conditioning appliances, and lowers their capacity/ coefficient of performance (COP) by increasing the thermal resistance between air and refrigerant and reducing the fansupplied airflow rate (Chen, Thomas, and Besant 2003; Silva, Hermes, and Melo 201…”
BackgroundSelf-citationSun, Y. J., Zhao, R., Wu, S., & Huang, D. (2021) · Energies · doi:10.3390/en14196069 · Cited by 5 · see citing works
“[4] experimentally studied effects of three fin types—flat, wavy and louver fins—on the periodic frosting and defrosting performance of evaporators in ASHPs.”
BackgroundSelf-citationDoğan, B., Ozturk, M. M., & Turhan, L. (2025) · Engineering Science and Technology an International Journal · doi:10.1016/j.jestch.2025.102242 · Cited by 5 · see citing works
Defrosting Properties of Structured Surfaces
Ahmadi, S. F., & Boreyko, J. B. (2020) · doi:10.1002/9781119640523.ch6 · Cited by 4 · see citing works
Liu, X., Wang, W., Yang, X., Liu, H., Wang, Y., Chen, Y., Han, L., Liu, Q., Zhao, F., & Li, R. (2025) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2025.127203 · Cited by 3 · see citing works
Optimization of distributed defrost heaters for enhanced performance in frost-free refrigerators
Wang, T., Chen, H., Qu, H., Zhao, Y., Lei, X., Yang, P., & Liu, Y. (2025) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2025.11.003 · Cited by 3 · see citing works
Self-citationHot gas bypass defrosting with auxiliary heat source in household refrigerators
Li, Y., Huang, Y., Xu, Y., Liu, Y., Yu, J., & Qian, S. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2024.124450 · Cited by 3 · see citing works
Self-citationLin, Y., Luo, J., Luo, Q., Li, X., Wang, W., & Sun, Y. (2024) · Energy and Buildings · doi:10.1016/j.enbuild.2024.115047 · Cited by 3 · see citing works
Li, C., Li, N., Li, N., et al. (2024) · Journal of Building Engineering · doi:10.1016/j.jobe.2024.111036 · Cited by 3 · see citing works
Su, M., Han, X., Liu, J., Peng, H., Wang, C., & Braimakis, K. (2026) · International Communications in Heat and Mass Transfer · doi:10.1016/j.icheatmasstransfer.2026.111303 · Cited by 2 · see citing works
Yang, H.-T., Pu, J., Yan, X., & Shen, C. (2025) · The Physics of Fluids · doi:10.1063/5.0258908 · Cited by 3 · see citing works
Research Progress on Defrosting Strategy of Heat Pump System Heat Exchanger Outside for EV
Ji, H., Guo, F., Wang, Y., & Luo, X. (2019) · World Conference on Mechanical Engineering and Intelligent Manufacturing (WCMEIM) · doi:10.1109/wcmeim48965.2019.00092 · Cited by 2 · see citing works
Sign of Frost-Free Heating Device for Air Source Heat Pump
Li, X., Zhang, X., Li, J., et al. (2019) · Academic Journal of Engineering and Technology Science · doi:10.25236/ajets.2019.020410 · Cited by 1 · see citing works
“The evaporator prevents frosting technology by installing a dehumidifying fabric heat exchanger on the windward side of the evaporator, optimizing the fin tube shape and fin material of the evaporator.[4]Photoelectric sensor is distributed between the fins with obvious heat transfer characteristics of the evaporator[5…”
BackgroundPrevious related work: A review
Song, M., & Deng, S.-M. (2019) · Defrosting for Air Source Heat Pump · doi:10.1016/b978-0-08-102517-8.00002-3
Internally Finned Tubes and Spirally Fluted Tubes
Saha, S. K., Ranjan, H., Emani, M. S., et al. (2019) · SpringerBriefs in applied sciences and technology · doi:10.1007/978-3-030-20748-9_6 · Cited by 1 · see citing works
ORINIO ŠILUMOS SIURBLIO ŠILUMOKAIČIO UŽŠALIMO MAŽINIMO IR VALDYMO BŪDAI
Kropas, T., & Streckienė, G. (2020) · Mokslas - Lietuvos ateitis · doi:10.3846/pinzs.2020.004 · Cited by 1 · see citing works
Investigation on Exergy in The Process of Heat Exchanger Defrosting
Dong, W., & Li, Y. (2020) · IOP Conference Series Earth and Environmental Science · doi:10.1088/1755-1315/514/4/042033 · Cited by 1 · see citing works
Lin, Z.-M., Hou, Y.-F., Wu, L.-K., & Wang, L.-B. (2026) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2026.129176 · Cited by 1 · see citing works
吹場, 活. (2017) · doi:10.11322/tjsrae.17-16r
A Perforated Enhanced Fin to Improve Heat Transfer Performance of a Heat Pump Type Air Conditioner
Wu, G., Ren, T., Ding, G., et al. (2018) · Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers · doi:10.11322/tjsrae.18-29ac_oa
Badanie wpływu braku kontaktu rury z ożebrowaniem na proces wymiany ciepła w wymienniku lamelowym
Andrzejewski, D., Łęcki, M., & Gutkowski, A. (2016) · Zeszyty Naukowe. Cieplne Maszyny Przepływowe - Turbomachinery / Politechnika Łódzka
Beura, S., Ray, R., Mohanty, U. K., et al. (2021) · Lecture notes in mechanical engineering · doi:10.1007/978-981-33-4795-3_43
Frost induced design challenges for heat pump heating and cooling efficiency penalties
O'Neill, N. F., Minh, J., Ding, C., & Shah, N. (2025) · Science and Technology for the Built Environment · doi:10.1080/23744731.2025.2511556
“Heat exchanger geometry, particularly fins (Huang et al. 2014; Popovac, Emhofer, and Reichl 2021; Wu et al. 2020), has been consistently analyzed for optimal anti-frosting behavior, generally varying fins to aid in drainage and frost thickness growth.”
Wang, X., Yuan, H., Mei, N., Bai, Y., Yu, X. Y. X., Sun, Y., Zhang, J., & Song, J. (2025) · Energy · doi:10.1016/j.energy.2025.139883
Ikram, H., Alexander, A., & Bach, C. K. (2026) · Energy and Buildings · doi:10.1016/j.enbuild.2026.117945
- Authors
- Huang, D., Ri-Jing, Z., Liu, Y., & Yi, D.-B.
- Affiliations
- Xi'an Jiaotong University (CN)
- Corresponding author
- Huang, Dong
- ORCID
- Venue
- Applied Thermal Engineering
- Publisher
- Elsevier BV
- Published
- 2014-08
- Volume
- 69
- Issue
- 1-2
- Pages
- 251-260
- ISSN
- 1359-4311 (ISSN-L)
- OpenAlex
- W2058672372
- Semantic Scholar
- e23b04cd5986b981e006a0527583c7cbc9aac6c1
- Cited by
- 99
- References
- 25
- Citations by year
- 2026: 4 · 2025: 10 · 2024: 13 · 2023: 12 · 2022: 9 · 2021: 6 · 2020: 8 · 2019: 8 · 2018: 9 · 2017: 9 · 2016: 5 · 2015: 3 · 2014: 3
- FWCI
- 4.87
- Type
- journal article
- Language
- en
- Open access
- closed
- Locations
- Applied Thermal Engineering (publishedVersion)
- Funders
- National Natural Science Foundation of China (51006079)
- Topics
- Physical Sciences › Engineering › Mechanical Engineering › Refrigeration and Air Conditioning Technologies
- Physical Sciences › Engineering › Mechanical Engineering › Heat Transfer and Optimization
- Physical Sciences › Engineering › Mechanical Engineering › Adsorption and Cooling Systems
- Keywords
- finned tube heat exchanger, air-source heat pump, wavy fins, louver fins, flat fins, coefficient of performance, frost accumulation
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Claims read by deepseek-v4.1-flash under definition version 3 (extract-v3) on 2026-10-26.
Classified by jev-1.13-20260917 (gold-guideline-v0.2) on 2026-10-26.
Cited sources are checked by gpt-6-sol.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review