Multiterminal DC Wind Farm Collection Grid Internal Fault Analysis and Protection Design
Open accessAbstract
The multiterminal dc wind farm is a promising topology with a voltage-source inverter (VSI) connection at the onshore grid. Voltage-source converters (VSCs) are robust to ac-side fault conditions. However, they are vulnerable to dc faults on the dc side of the converter. This paper analyzes dc faults, their transients, and the resulting protection issues. Overcurrent faults are analyzed in detail and provide an insight into protection system design. The radial wind farm topology with star or string connection is considered. The outcomes may be applicable for VSCs in the multi-VSC dc wind farm collection grid and VSC-based high-voltage direct current (HVDC) offshore transmission systems.
Overview
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
HVDC Connection of Offshore Wind Farms to the Transmission System
Bresesti, P., Kling, W. L., Hendriks, R. L., & Vailati, R. (2007) · IEEE Transactions on Energy Conversion · doi:10.1109/tec.2006.889624 · Cited by 750
Locating and Isolating DC Faults in Multi-Terminal DC Systems
Tang, L., & Ooi, B.-T. (2007) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2007.899276 · Cited by 640
DC distribution for industrial systems: opportunities and challenges
Baran, M. E., & Mahajan, N. R. (2003) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2003.818969 · Cited by 582
Overcurrent Protection on Voltage-Source-Converter-Based Multiterminal DC Distribution Systems
Baran, M. E., & Mahajan, N. R. (2007) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2006.877086 · Cited by 380
Control and Design of DC Grids for Offshore Wind Farms
Meyer, C., Hoing, M., Peterson, A., & De Doncker, R. W. (2007) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2007.908182 · Cited by 351
VSC Transmission Operating Under Unbalanced AC Conditions—Analysis and Control Design
Xu, L., Andersen, B. R., & Cartwright, P. (2005) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2004.835032 · Cited by 231
Protection of VSC-multi-terminal HVDC against DC faults
Tang, L., & Ooi, B.-T. (2003) · 2002 IEEE 33rd Annual IEEE Power Electronics Specialists Conference. Proceedings (Cat. No.02CH37289) · doi:10.1109/psec.2002.1022539 · Cited by 161
A New Architecture for Offshore Wind Farms
Prasai, A., Yim, J.-S., Divan, D. M., et al. (2008) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2008.921194 · Cited by 116
Cited by
Protection of Nonpermanent Faults on DC Overhead Lines in MMC-Based HVDC Systems
Li, X., Song, Q., Liu, W., Rao, H., Xu, S., & Li, L. (2013) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2012.2226249 · Cited by 402
A Non-unit Protection Scheme for DC Microgrid Based on Local Measurements
Meghwani, A., Srivastava, S. C., & Chakrabarti, S. (2017) · IEEE Transactions on Power Delivery · doi:10.1109/tpwrd.2016.2555844 · Cited by 351
An enhanced MMC topology with DC fault ride-through capability
Li, X., Liu, W., Song, Q., Rao, H., & Xu, S. (2013) · IECON 2013 - 39th Annual Conference of the IEEE Industrial Electronics Society · doi:10.1109/iecon.2013.6700152 · Cited by 92
Protection Systems for DC Shipboard Microgrids
Bayati, N., & Savaghebi, M. (2021) · Energies · doi:10.3390/en14175319 · Cited by 21
Metadata
- Authors
- Yang, J., Fletcher, J. E., & O'Reilly, J.
- Venue
- IEEE Transactions on Power Delivery
- Published
- 2010-10
- Volume
- 25
- Issue
- 4
- Pages
- 2308-2318
- ISSN
- 0885-8977 (ISSN-L)
- 1937-4208
- OpenAlex
- W2122328510
- Cited by
- 321
- References
- 8
- FWCI
- 11.71
- Type
- journal article
- Language
- en
- Open access
- green
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
How to cite
Cite CoChat for the checks on this page, and the paper for its own findings.
- This page
- CoChat. (2026). Citation check: Multiterminal DC Wind Farm Collection Grid Internal Fault Analysis and Protection Design. https://app.cochat.ai/papers/10.1109/tpwrd.2010.2044813
- The paper
- Yang, J., Fletcher, J. E., & O'Reilly, J. (2010). Multiterminal DC Wind Farm Collection Grid Internal Fault Analysis and Protection Design. IEEE Transactions on Power Delivery. https://doi.org/10.1109/tpwrd.2010.2044813
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.