The Effects of Moderately Raised Classroom Temperatures and Classroom Ventilation Rate on the Performance of Schoolwork by Children (RP-1257)
The DOI matches its Crossref record; 20 of the 20 references it cites were found in a registry or an index.
Abstract
Two independent field intervention experiments were carried out in school classrooms in late summer (in 2004 and 2005). The air temperature was manipulated by either operating or idling split cooling units installed for the purpose. In one of these experiments, the outdoor air supply rate was also manipulated. The conditions were established for one week at a time in a blind crossover design with repeated measures on two classes of 10- to 12-year-old children. Six to eight exercises exemplifying different aspects of schoolwork (numerical and language-based) were performed as part of normal lessons. Pupils indicated their environmental perceptions and the intensity of any symptoms on visual analogue scales. Their thermal sensation changed from slightly too warm to neutral, and the performance of two numerical and two language-based tests was significantly improved when the temperature was reduced from 25°C to 20°C (77°F to 68°F). When the outdoor air supply rate was increased from 5.2 to 9.6 L/s (11.0 to 20.3 cfm) per person, their performance of four numerical exercises improved significantly, confirming the results of previously reported experiments in the same series. The above improvements were mainly in terms of the speed at which tasks were performed, with negligible effects on error rate. Most school classrooms worldwide experience raised air temperatures during increased thermal loads, e.g., in warm weather; these results show that providing some means of avoiding elevated temperatures would improve educational attainment.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Thermal Environmental Conditions for Human Occupancy
Ashrae, S. (1992) · Medical Entomology and Zoology · Cited by 6,092
Thermal comfort: Analysis and applications in environmental engineering
(1972) · Applied Ergonomics · doi:10.1016/s0003-6870(72)80074-7 · Cited by 4,451
An Introduction to Error Analysis
Taylor, J. R. (1982) · Medical Entomology and Zoology · Cited by 2,807
An Introduction to Error Analysis: The Study of Uncertainties in Physical Measurements
Taylor, J. R., & Thompson, W. (1998) · Physics Today · doi:10.1063/1.882103 · Cited by 2,734
An introduction to error analysis: the study of uncertainties in physical measurements
(1997) · Choice Reviews Online · doi:10.5860/choice.35-2173 · Cited by 2,247
Mendell, M. J., & Heath, G. A. (2005) · Indoor Air · doi:10.1111/j.1600-0668.2004.00320.x · Cited by 1,034
A 3 min reasoning test based on grammatical transformation
Baddeley, A. D. (1968) · Psychonomic Science · doi:10.3758/bf03331551 · Cited by 649
Wargocki, P., Sundell, J., Bischof, W., Brundrett, G., Fanger, P. O., Gyntelberg, F., Hanssen, S. O., Harrison, P., Pickering, A., Seppänen, O., et al. (2002) · Indoor Air · doi:10.1034/j.1600-0668.2002.01145.x · Cited by 418
Self-citationSeppänen, O., & Fisk, W. J. (2002) · Indoor Air · doi:10.1034/j.1600-0668.2002.01111.x · Cited by 277
Wargocki, P., & Wyon, D. P. (2007) · HVAC&R Research · doi:10.1080/10789669.2007.10390950 · Cited by 194
Self-citation
Cited by
What Do We Learn from the Weather? The New Climate-Economy Literature
Dell, M., Jones, B. F., & Olken, B. A. (2014) · Journal of Economic Literature · doi:10.1257/jel.52.3.740 · Cited by 2,300
Barrett, P., Davies, F., Zhang, Y., & Barrett, L. (2015) · Building and Environment · doi:10.1016/j.buildenv.2015.02.013 · Cited by 706
Ventilation rates in schools and pupils’ performance
Bakó-Biró, Z., Clements-Croome, D. J., Kochhar, N., Awbi, H. B., & Williams, M. J. (2012) · Building and Environment · doi:10.1016/j.buildenv.2011.08.018 · Cited by 580
Sadrizadeh, S., Yao, R., Yuan, F., Awbi, H., Bahnfleth, W., Bi, Y., Cao, G., Croitoru, C., de Dear, R., Haghighat, F., et al. (2022) · Journal of Building Engineering · doi:10.1016/j.jobe.2022.104908 · Cited by 375
Self-citationLan, L., Wargocki, P., Wyon, D. P., & Lian, Z. (2011) · Indoor Air · doi:10.1111/j.1600-0668.2011.00714.x · Cited by 355
Self-citationThe ventilation problem in schools: literature review
Fisk, W. J. (2017) · Indoor Air · doi:10.1111/ina.12403 · Cited by 333
Association between substandard classroom ventilation rates and students’ academic achievement
Haverinen-Shaughnessy, U., Moschandreas, D. J., & Shaughnessy, R. J. (2011) · Indoor Air · doi:10.1111/j.1600-0668.2010.00686.x · Cited by 311
Providing better thermal and air quality conditions in school classrooms would be cost-effective
Wargocki, P., & Wyon, D. P. (2013) · Building and Environment · doi:10.1016/j.buildenv.2012.10.007 · Cited by 309
Self-citationWargocki, P., & Wyon, D. P. (2017) · Building and Environment · doi:10.1016/j.buildenv.2016.11.020 · Cited by 290
Self-citationTeli, D., Jentsch, M. F., & James, P. A. B. (2012) · Energy and Buildings · doi:10.1016/j.enbuild.2012.06.022 · Cited by 284
The relationships between classroom air quality and children’s performance in school
Wargocki, P., Porras-Salazar, J. A., Contreras-Espinoza, S., & Bahnfleth, W. (2020) · Building and Environment · doi:10.1016/j.buildenv.2020.106749 · Cited by 263
Self-citationHealth Effects of Wildfire Smoke in Children and Public Health Tools: A Narrative Review
Holm, S. M., Miller, M. D., & Balmes, J. R. (2021) · Journal of Exposure Science & Environmental Epidemiology · doi:10.1038/s41370-020-00267-4 · Cited by 246
Adaptive thermal comfort in Australian school classrooms
de Dear, R., Kim, J., Candido, C., & Deuble, M. (2015) · Building Research & Information · doi:10.1080/09613218.2015.991627 · Cited by 246
“The influence of moderately elevated temperatures on student performance was investigated in a recent series of field experiments conducted in Danish classrooms (Wargocki & Wyon, 2006, 2007).”
BackgroundResultInfluentialKelly, F. J., & Fussell, J. C. (2019) · Atmospheric Environment · doi:10.1016/j.atmosenv.2018.11.058 · Cited by 246
How indoor environmental quality affects occupants’ cognitive functions: A systematic review
Wang, C., Zhang, F., Wang, J., Doyle, J. K., Hancock, P. A., Mak, C. M., & Liu, S. (2021) · Building and Environment · doi:10.1016/j.buildenv.2021.107647 · Cited by 243
The Effects of Weather Shocks on Economic Activity: What are the Channels of Impact?
Acevedo, S., Mrkaic, M., Novta, N., Pugacheva, E., & Topalova, P. (2020) · Journal of Macroeconomics · doi:10.1016/j.jmacro.2020.103207 · Cited by 229
Yang, Z., Becerik-Gerber, B., & Mino, L. (2013) · Building and Environment · doi:10.1016/j.buildenv.2013.08.030 · Cited by 214
Jia, L.-R., Han, J., Chen, X., Li, Q.-Y., Lee, C.-C., & Fung, Y.-H. (2021) · Buildings · doi:10.3390/buildings11120591 · Cited by 212
Macintyre, H. L., Heaviside, C., Taylor, J., Picetti, R., Symonds, P., Cai, X.-M., & Vardoulakis, S. (2018) · Science of The Total Environment · doi:10.1016/j.scitotenv.2017.08.062 · Cited by 205
Progress in thermal comfort studies in classrooms over last 50 years and way forward
Singh, M. K., Ooka, R., Rijal, H. B., Kumar, S., Kumar, A., & Mahapatra, S. (2019) · Energy and Buildings · doi:10.1016/j.enbuild.2019.01.051 · Cited by 202
Children's well-being at schools: Impact of climatic conditions and air pollution
Salthammer, T., Uhde, E., Schripp, T., Schieweck, A., Morawska, L., Mazaheri, M., Clifford, S., He, C., Buonanno, G., Querol, X., et al. (2016) · Environment International · doi:10.1016/j.envint.2016.05.009 · Cited by 198
Wargocki, P., & Wyon, D. P. (2007) · HVAC&R Research · doi:10.1080/10789669.2007.10390950 · Cited by 194
Self-citationEffects of Classroom Ventilation Rate and Temperature on Students’ Test Scores
Haverinen-Shaughnessy, U., & Shaughnessy, R. J. (2015) · PLOS ONE · doi:10.1371/journal.pone.0136165 · Cited by 194
Indoor CO 2 concentrations and cognitive function: A critical review
Du, B., Tandoc, M. C., Mack, M. L., & Siegel, J. A. (2020) · Indoor Air · doi:10.1111/ina.12706 · Cited by 190
The relationship between classroom temperature and children’s performance in school
Wargocki, P., Porras-Salazar, J. A., & Contreras-Espinoza, S. (2019) · Building and Environment · doi:10.1016/j.buildenv.2019.04.046 · Cited by 189
Self-citationWhat Do We Learn from the Weather? The New Climate-Economy Literature
Dell, M., Jones, B., & Olken, B. (2013) · National Bureau of Economic Research · doi:10.3386/w19578 · Cited by 185
What do we know about indoor air quality in school classrooms? A critical review of the literature
Chatzidiakou, L., Mumovic, D., & Summerfield, A. J. (2012) · Intelligent Buildings International · doi:10.1080/17508975.2012.725530 · Cited by 182
Indoor air quality and academic performance
Stafford, T. M. (2015) · Journal of Environmental Economics and Management · doi:10.1016/j.jeem.2014.11.002 · Cited by 178
Kim, J., & de Dear, R. (2018) · Building and Environment · doi:10.1016/j.buildenv.2017.10.031 · Cited by 177
A study on pupils' learning performance and thermal comfort of primary schools in China
Jiang, J., Wang, D., Liu, Y., Xu, Y., & Liu, J. (2018) · Building and Environment · doi:10.1016/j.buildenv.2018.02.036 · Cited by 175
Lakhdari, K., Sriti, L., & Painter, B. (2021) · Building and Environment · doi:10.1016/j.buildenv.2021.108173 · Cited by 163
“Studies of student achievement confirmed that 11 thermal conditions can affect the health of building users and adverse situations can cause 12 apathy, and even stress, and impact schoolwork performance [1, 14].”
BackgroundHeracleous, C., & Michael, A. (2019) · Journal of Building Engineering · doi:10.1016/j.jobe.2019.100917 · Cited by 159
Realyvásquez-Vargas, A., Maldonado-Macías, A. A., Arredondo-Soto, K. C., Baez-Lopez, Y., Carrillo-Gutiérrez, T., & Hernández-Escobedo, G. (2020) · Sustainability · doi:10.3390/su12219194 · Cited by 154
“In turn, this coincides with what was obtained by Wargocki and Wyon [59], and Haverinen-Shaughnessy et al.”
BackgroundResult
Metadata
- Authors
- Wargocki, P., & Wyon, D. P.
- Venue
- HVAC&R Research
- Publisher
- Informa UK Limited
- Published
- 2007-03
- Volume
- 13
- Issue
- 2
- Pages
- 193-220
- ISSN
- 1078-9669 (ISSN-L)
- 1938-5587
- OpenAlex
- W2079690637
- Cited by
- 364
- References
- 20
- FWCI
- 19.70
- Type
- journal article
- Language
- en
- Open access
- closed
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.