Association of Ventilation Rates and CO2 Concentrations with Health andOther Responses in Commercial and Institutional Buildings
Open accessAbstract
This paper reviews current literature on the associations of ventilation rates and carbon dioxide concentrations in non-residential and non-industrial buildings (primarily offices) with health and other human outcomes. Twenty studies, with close to 30,000 subjects, investigated the association of ventilation rates with human responses, and 21 studies, with over 30,000 subjects, investigated the association of carbon dioxide concentration with these responses. Almost all studies found that ventilation rates below 10 Ls-1 per person in all building types were associated with statistically significant worsening in one or more health or perceived air quality outcomes. Some studies determined that increases in ventilation rates above 10 Ls-1 per person, up to approximately 20 Ls-1 per person, were associated with further significant decreases in the prevalence of sick building syndrome (SBS) symptoms or with further significant improvements in perceived air quality. The carbon dioxide studies support these findings. About half of the carbon dioxide studies suggest that the risk of sick building syndrome symptoms continued to decrease significantly with decreasing carbon dioxide concentrations below 800 ppm. The ventilation studies reported relative risks of 1.5-2 for respiratory illnesses and 1.1-6 for sick building syndrome symptoms for low compared to high low ventilation rates.
Overview
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
The cited source says what the claim attributes to it.
In the citing paper
“Seppänen et al. [14] found that the risk of air-related health problems can be decreased when CO 2 concentrations fall below 800 ppm.”
From Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China (2017) · cites this paper as [14]
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
(1979) · Medical Entomology and Zoology · Cited by 11,252
Quasi-experimentation: Design and analysis issues for field settings
Shrout, P. E. (1980) · Evaluation and Program Planning · doi:10.1016/0149-7189(80)90063-4 · Cited by 6,091
Ventilation for Acceptable Indoor Air Quality
Falih, M. (2019) · Cited by 2,497
ASTM Special Technical Publication
Hannula, S., Wanagel, J., & Li, C. Y. (1986) · Cited by 1,225
Estimates of Improved Productivity and Health from Better Indoor Environments
Fisk, W. J., & Rosenfeld, A. H. (1997) · Indoor Air · doi:10.1111/j.1600-0668.1997.t01-1-00002.x · Cited by 551
Self-citationImpact of Temperature and Humidity on the Perception of Indoor Air Quality
Fang, L., Clausen, G., & Fanger, P. O. (1998) · Indoor Air · doi:10.1111/j.1600-0668.1998.t01-2-00003.x · Cited by 534
Risk of Sick Leave Associated with Outdoor Air Supply Rate, Humidification, and Occupant Complaints
Milton, D. K., Glencross, P. M., & WALTERS, M. D. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004212.x · Cited by 364
Apte, M. G., Fisk, W. J., & Daisey, J. M. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004246.x · Cited by 341
Self-citationHEALTH HAZARD EVALUATION REPORT
Reh, C. M., Fleeger, A., & Collins, J. W. (1989) · Cited by 316
Non-Specific Symptoms In Office Workers: A Review And Summary Of The Epidemiologic Literature
Mendell, M. J. (1993) · Indoor Air · doi:10.1111/j.1600-0668.1993.00003.x · Cited by 282
Self-citationAn Epidemic of Pneumococcal Disease in an Overcrowded, Inadequately Ventilated Jail
Hoge, C. W., Reichler, M. R., Dominguez, E. A., Bremer, J. C., Mastro, T. D., Hendricks, K. A., Musher, D. M., Elliott, J. A., Facklam, R. R., & Breiman, R. F. (1994) · New England Journal of Medicine · doi:10.1056/nejm199409083311004 · Cited by 271
Airborne Infection: Theoretical Limits of Protection Achievable by Building Ventilation
Nardell, E. A., Keegan, J., Cheney, S., & Etkind, S. C. (1991) · American Review of Respiratory Disease · doi:10.1164/ajrccm/144.2.302 · Cited by 261
Proceedings of Healthy Buildings
Brohus, H. (2006) · Cited by 247
European Indoor Air Quality Audit Project in 56 Office Buildings
Bluyssen, P. M., Fernandes, E. D. O., Groes, L., Clausen, G., Fanger, P. O., Valbjørn, O., Bernhard, C. A., & Roulet, C.-A. (1996) · Indoor Air · doi:10.1111/j.1600-0668.1996.00002.x · Cited by 238
Menzies, D., & Bourbeau, J. (1997) · New England Journal of Medicine · doi:10.1056/nejm199711203372107 · Cited by 171
Health and Indoor Climate Complaints of 7043 office Workers in 61 Buildings in the Netherlands
Zweers, T., Preller, L., Brunekreef, B., & Boleij, J. S. M. (1992) · Indoor Air · doi:10.1111/j.1600-0668.1992.00001.x · Cited by 159
Building-Associated Risk of Febrile Acute Respiratory Diseases in Army Trainees
Brundage, J. F. (1988) · JAMA · doi:10.1001/jama.1988.03720140028029 · Cited by 158
The Effect of Varying Levels of Outdoor-Air Supply on the Symptoms of Sick Building Syndrome
Menzies, R., Tamblyn, R. M., Farant, J.-P., Hanley, J. A., Nunes, F., & Tamblyn, R. T. (1993) · New England Journal of Medicine · doi:10.1056/nejm199303253281201 · Cited by 148
Jaakkola, J. J. K., Heinoneon, O. P., & Seppänen, O. (1991) · Indoor Air · doi:10.1111/j.1600-0668.1991.02-12.x · Cited by 132
Subjective Indoor Air Quality in Schools in Relation to Exposure
Smedje, G., Norbäck, D., & Edling, C. (1997) · Indoor Air · doi:10.1111/j.1600-0668.1997.00009.x · Cited by 120
Ventilation requirements in buildings—I. Control of occupancy odor and tobacco smoke odor
Cain, W. S., Leaderer, B. P., Isseroff, R., Berglund, L. G., Huey, R. J., Lipsitt, E. D., & Perlman, D. (1983) · Atmospheric Environment (1967) · doi:10.1016/0004-6981(83)90341-4 · Cited by 112
Stenberg, B., Eriksson, N., Höög, J., Sundell, J., & Wall, S. (1994) · International Journal of Epidemiology · doi:10.1093/ije/23.6.1190 · Cited by 102
Sick buildings and the experimental approach
Wyon, D. P. (1992) · Environmental Technology · doi:10.1080/09593339209385159 · Cited by 88
Report of an outbreak: nursing home architecture and influenza-A attack rates
Drinka, P. J., Krause, P., Schilling, M., Miller, B. A., Shult, P., & Gravenstein, S. (1996) · Journal of the American Geriatrics Society · doi:10.1111/j.1532-5415.1996.tb01859.x · Cited by 77
Nordström, K., Norbäck, D., & Akselsson, R. (1995) · Occupational and Environmental Medicine · doi:10.1136/oem.52.3.170 · Cited by 77
Wålinder, R., Norbäck, D., Wieslander, G., Smedje, G., Erwall, C., & Venge, P. (1998) · International Archives of Occupational and Environmental Health · doi:10.1007/s004200050309 · Cited by 74
Phase 1 of the California Healthy Building Study: A Summary
Fisk, W. J., Mendell, M. J., Daisey, J. M., Faulkner, D. M., Hodgson, A. T., Nematollahi, M., & Macher, J. M. (1993) · Indoor Air · doi:10.1111/j.1600-0668.1993.00005.x · Cited by 74
Self-citationSundell, J., Lindvall, T., & Stenberg, B. (1994) · Environment International · doi:10.1016/0160-4120(94)90141-4 · Cited by 70
Ventilation rate in office buildings and sick building syndrome.
Jaakkola, J. J. K., & Miettinen, P. (1995) · Occupational and Environmental Medicine · doi:10.1136/oem.52.11.709 · Cited by 68
Health symptoms and the work environment in four nonproblem United States office buildings
Nelson, N. A., Kaufman, J. D., Burt, J., & Karr, C. J. (1995) · Scandinavian Journal of Work Environment & Health · doi:10.5271/sjweh.8 · Cited by 63
Norbäck, D. (1995) · Indoor Air · doi:10.1111/j.1600-0668.1995.00003.x · Cited by 58
Sundell, J., Lindvall, T., Stenberg, B., & Wall, S. (1994) · Indoor Air · doi:10.1111/j.1600-0668.1994.t01-2-00003.x · Cited by 56
The effect of air humidification on different symptoms in office workers — An epidemiologic study
Reinikainen, L. M., Jaakkola, J. J. K., & Heinonen, O. P. (1991) · Environment International · doi:10.1016/0160-4120(91)90009-f · Cited by 54
Ventilation requirements for the control of body odor in spaces occupied by women
Berg-Munch, B., Clausen, G., & Fanger, P. O. (1986) · Environment International · doi:10.1016/0160-4120(86)90030-9 · Cited by 53
The Relation of CO2 Concentration to Office Building Ventilation
Persily, A. K., & Dols, W. S. (1990) · doi:10.1520/stp17206s · Cited by 50
Proceedings of the 8th international conference healthy buildings
Fernandes, E. D. O., Pinto, J. R., & da Silva, M. G. (2006) · Cited by 49
Nasal Mucosal Swelling in Relation to Low Air Exchange Rate in Schools
Wålinder, R., Norbäck, D., Wieslander, G., Smedje, G., & Erwall, C. (1997) · Indoor Air · doi:10.1111/j.1600-0668.1997.t01-1-00005.x · Cited by 48
European audit project to optimise indoor air quality and energy consumption in office buildings
Bluyssen, P. M., Fernandes, E. D. O., Fanger, P. O., Groes, L., Glausen, G., Roulet, C.-A., Bernhard, C., & Valbjørn, O. (1994) · Cited by 39
Air recirculation and sick building syndrome: a blinded crossover trial.
Jaakkola, J. J. K., Tuomaala, P., & Seppänen, O. (1994) · American Journal of Public Health · doi:10.2105/ajph.84.3.422 · Cited by 39
Potential Nationwide Improvements in Productivity and Health From Better Indoor Environments
Fisk, W. J., & Rosenfeld, A. H. (1998) · University of North Texas Digital Library (University of North Texas) · Cited by 36
Self-citationJaakkola, J. J. K., Reinikainen, L. M., Heinonen, O. P., Majanen, A., & Seppänen, O. (1991) · Environment International · doi:10.1016/0160-4120(91)90025-l · Cited by 34
Building-associated risk of febrile acute respiratory diseases in Army trainees
Brundage, J. F. (1988) · JAMA · doi:10.1001/jama.259.14.2108 · Cited by 34
Individual and Occupational Correlates of the Sick Building Syndrome
Hedge, A., Erickson, W., & Rubin, G. (1995) · Indoor Air · doi:10.1111/j.1600-0668.1995.t01-3-00003.x · Cited by 32
Nordström, K., Norbäck, D., & Akselsson, R. (1995) · Indoor Environment · doi:10.1177/1420326x9500400105 · Cited by 31
Ventilation for buildings. Design criteria for the indoor environment
(2015) · doi:10.3403/01739104u · Cited by 31
The effect of ventilation and air pollution on perceived indoor air quality in five town halls
Zweers, T., Skov, P., Valbjørn, O., & Mølhave, L. (1990) · Energy and Buildings · doi:10.1016/0378-7788(90)90038-k · Cited by 25
Nasal Congestion in Relation to Low Air Exchange Rate in Schools: Evaluation by Acoustic Rhinometry
Wålinder, R., Norbäck, D., Wieslander, G., Smedje, G., & Erwall, C. (1997) · Acta Oto-Laryngologica · doi:10.3109/00016489709113467 · Cited by 24
Mental performance by secondary school pupils in relation to the quality of indoor air
Smedje, G., Norbäck, D., & Edling, C. (1996) · Cited by 22
Air Exchange Effectiveness in Office Buildings: Measurement Techniques and Results
Fisk, W. J., & Faulkner, D. M. (1992) · University of North Texas Digital Library (University of North Texas) · Cited by 20
Self-citationHill, B. A., Craft, B. F., & Burkart, J. A. (1992) · Applied Occupational and Environmental Hygiene · doi:10.1080/1047322x.1992.10388030 · Cited by 20
Simultaneous measurements of infiltration and intake in an office building
Persily, A. K., & Norford, L. K. (1987) · ASHRAE winter conference papers · Cited by 16
Design, construction, and operation of healthy buildings : solutions to global and regional concerns
Moschandreas, D. J., & Buildings, H. (1998) · American Society of Heating, Refrigerating and Air-Conditioning Engineers eBooks · Cited by 13
Ventilation rate as a determinant of symptoms and perceived odors among workers in daycare centers
Ruotsalainen, R., Jaakkola, N., & Jaakkola, J. J. K. (1994) · Environment International · doi:10.1016/0160-4120(94)90305-0 · Cited by 13
The Helsinki Office Environment Study: Air Change in Mechanically Ventilated Buildings
Teijonsalo, J., Jaakkola, J. J. K., & Seppaunen, O. (1996) · Indoor Air · doi:10.1111/j.1600-0668.1996.t01-2-00007.x · Cited by 12
Turk, B. H., Brown, J. T., Geisling-Sobotka, K., Froehlich, D. A., Grimsrud, D. T., Harrison, J. A., Koonce, J. F., Prill, R. J., & Revzan, K. L. (1987) · Cited by 8
ASHRAE Standard 62-1989: Energy, Cost, and Program Implications.
Steele, T. R., & Brown, M. A. (1990) · doi:10.2172/5209141 · Cited by 7
European audit project to optimize indoor air quality and energy consumption in office buildings
Bluyssen, P., de Fernandes, E. O., Fanger, P. O., Groes, L., Glausen, G., Roulet, C.-A., Bernhard, C.-A., & Valbjørn, O. (1995) · Infoscience (Ecole Polytechnique Fédérale de Lausanne) · Cited by 7
European audit study in 56 office buildings. Conclusions and recommendations
Bluyssen, P. M., Fernandes, E. D. O., Groes, L., Clausen, G., Fanger, P. O., Valbjørn, O., Bernhard, C., & Roulet, C.-A. (1995) · Cited by 6
Guide for Indoor Air Quality Surveys
Bright, P., Mader, M. J., Carpenter, D., & Hermon-Cruz, I. Z. (1992) · doi:10.21236/ada251638 · Cited by 5
Occupational and Environmental Health
Sattler, B. (1996) · AAOHN Journal · doi:10.1177/216507999604400508 · Cited by 5
Turk, B. H., Brown, J. T., Geisling-Sobotka, K., Froehlich, D. A., Grimsrud, D., Harrison, J., Koonce, J. F., Prill, R. J., & Revzan, K. L. (1987) · eScholarship (California Digital Library) · Cited by 3
Carpenter, D., & Poitrast, B. J. (1990) · Cited by 2
Research works printed but not linked: 37
- ACGIH, 1991, Documentation of the Threshold Limit Values and Biological Exposure Indices, Sixth Edition
- Aizlewood C., 1996, Proceedings of Indoor Air '96, 2, 895
- Apte M., 1999, Indoor CO2 concentrations and sick building syndrome: analysis of the 1994-1996 BASE study data
- Bluyssen P.M., 1995, Proceedings of Healthy Buildings '95, 1287
- Brightman H.S., 1999, Proceedings of Indoor Air '99, 1, 847
- Cochet C., 1995, Proceedings of Healthy Buildings '95, 3, 1359
- Emmerich S., 1999, Proceedings of IAQ '98, 191
- Fanger P.O., 1983, Proceedings of Management of Atmospheres in Tightly Enclosed Spaces, 45
- Fisk WJ., 1992, Proceedings of the 1992 International Symposium on Room Air Convection and Ventilation Effectiveness, 213
- Fisk W., 1998, Proceedings of the 1998 Summer School Study on Energy Efficiency in Buildings, 8.85
- Gamble J., 1986, Proceedings of IAQ 86, 16
- L. Groes (1995 ) "The European IAQ-audit project, Statistical analysis of indoor environmental factors ", Ph.D. thesis, Laboratory of Heating and Air Conditioning, Technical University of Denmark.
- Groes L., 1995, Proceedings of 4th International conference on Healthy Buildings, 1293
- Hall J., 1998, Proceedings of IAQ '98, 171
- Hodgson M.J., 1989, Proceedings of IAQ '89, 8
- Janssen J., 1986, Proceedings of IAQ '86, 161
- Mendell M.J., 1993, Proceedings of Indoor Air '93, 1, 713
- Menzies D., 1993, Proceedings of Indoor Air '93, 6, 551
- Milton D., 1998, American Journal of Respiratory Critical Care Medicine, 157, A647
- Mudarri D., 1997, ASHRAE Transactions, 103, 244
- Myhrvold A., 1996, Proceedings of Indoor Air '96, 4, 369
- Nagda N.L., 1991, Proceedings of IAQ '91, 101
- Nagda N., 1990, Proceedings of Indoor Air '90, 1, 281
- Nardell E.A., 1997, Proceedings of Healthy Buildings '97, 1, 301
- Nelson C.J., 1991, Proceedings of IAQ '91, 14
- Palonen J., 1990, Proceedings of Indoor Air '90, 1, 299
- Persily A., 1997, ASHRAE Transactions, 103, 1
- Persily A., 1987, ASHRAE Transactions, 93, 42
- Roulet C., 1995, Proceedings of 4th International conference on Healthy Buildings, 1299
- Seppanen O., 1999, Proceedings of IAQ '98, 257
- Sieber W., 1998, Proceedings of the Section of Statistics and the Environment, 115
- Smedje G., 1996, Proceedings of Indoor Air '96, 1, 413
- Sohn J-Y, 1994, Proceedings of Healthy Buildings '94, 397
- Sundell J., 1994, Indoor Air, 4, 10.1111/j.1600-0668.1994.tb00031.x · DOI
- Wu X., 1996, Proceedings of Indoor Air '96, 2, 919
- 10.1007/s004200050309 · DOI
- WaRlinder R., 1997, Acta Otolanryngol, 117, 724, 10.3109/00016489709113467 · DOI
Cited by
Sorted by citations
Satish, U., Mendell, M. J., Shekhar, K., Hotchi, T., Sullivan, D., Streufert, S., & Fisk, W. J. (2012) · Environmental Health Perspectives · doi:10.1289/ehp.1104789 · Cited by 1,064
Self-citationLi, Y., Leung, G. M., Tang, J. W.-T., Yang, X., Chao, C. Y. H., Lin, J. Z., Lu, J. W. Z., Nielsen, P. V., Niu, J., Qian, H., et al. (2007) · Indoor Air · doi:10.1111/j.1600-0668.2006.00445.x · Cited by 1,057
Mendell, M. J., & Heath, G. A. (2005) · Indoor Air · doi:10.1111/j.1600-0668.2004.00320.x · Cited by 1,034
Self-citationIndoor air quality, ventilation and health symptoms in schools: an analysis of existing information
Daisey, J. M., Angell, W. J., & Apte, M. G. (2003) · Indoor Air · doi:10.1034/j.1600-0668.2003.00153.x · Cited by 977
Achieving better energy-efficient air conditioning – A review of technologies and strategies
Chua, K. J., Chou, S. K., Yang, W., & Yan, J. (2012) · Applied Energy · doi:10.1016/j.apenergy.2012.10.037 · Cited by 952
Metadata
- Authors
- Seppanen, O. A., Fisk, W. J., & Mendell, M. J.
- Affiliations
- Lawrence Berkeley National Laboratory (US)
- National Institute for Occupational Safety and Health (US)
- Corresponding author
- Fisk, W. J.
- Venue
- Indoor Air
- Publisher
- Hindawi Limited
- Published
- 1999-12
- Volume
- 9
- Issue
- 4
- Pages
- 226-252
- ISSN
- 0905-6947 (ISSN-L)
- 1600-0668
- OpenAlex
- W2161463298
- Cited by
- 876
- References
- 64
- Citations by year
- 2026: 41 · 2025: 45 · 2024: 36 · 2023: 46 · 2022: 48 · 2021: 53 · 2020: 74 · 2019: 56 · 2018: 45 · 2017: 32 · 2016: 31 · 2015: 52 · 2014: 51 · 2013: 29 · 2012: 38
- FWCI
- 2.63
- Type
- journal article
- Language
- en
- Open access
- bronze
- doi.org
- Locations
- Indoor Air (publishedVersion)
- PubMed (publishedVersion)
- Zenodo (CERN European Organization for Nuclear Research) (submittedVersion, public-domain)
- Funders
- U.S. Department of Energy (DE-AC03-?, AC03-76SF00098, DEAC03-76SF00098)
- Topics
- Physical Sciences › Environmental Science › Health, Toxicology and Mutagenesis › Indoor Air Quality and Microbial Exposure
- Health Sciences › Medicine › Pulmonary and Respiratory Medicine › Infection Control and Ventilation
- Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
- Keywords
- ventilation rate, CO2 concentration, sick building syndrome, office buildings, institutional building, perceived air quality, respiratory diseases, indoor air quality, occupant health
- MeSH terms
- Adult, Carbon Dioxide, Humans, Public Health, Incidence, Occupational Health, Air Pollution, Indoor, Risk Assessment, Sick Building Syndrome
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review