Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China

Open access
Peng, Zhen, Deng, Wu, Tenorio, Rosangela · 2017 · Sustainability

Abstract

Indoor air quality in four naturally ventilated schools was influenced by building defects and occupants' activities; indoor particulate concentrations could exceed outdoor levels during occupied periods.

Overview

CoChat Summary

TL;DR

In four naturally ventilated primary schools in Tai’an, North China, winter indoor PM2.5, PM10, CO2, and temperature mostly failed IAQ and comfort standards. Building air tightness and occupant activities strongly influenced indoor PM and CO2, with tighter buildings reducing particle penetration but closed windows raising CO2.

Key findings

  • Occupied classrooms had mean PM2.5 concentrations of 149–199 µg/m³ and mean PM10 concentrations of 138–205 µg/m³, about 5 times higher than WHO and Chinese standard requirements; the highest PM2.5 was 274 µg/m³ in School D, and the highest PM10 was 267 µg/m³ in School C.
  • In unoccupied classrooms, School B had the lowest indoor/outdoor ratios (0.49 for PM2.5, 0.47 for PM10), while School C had the highest (0.85 for PM2.5, 0.9 for PM10); Schools A and D, both air tightness level 4, had I/O ratios around 0.54–0.69.
  • Occupied CO2 means all exceeded the WHO 600 ppm and China 1000 ppm limits, ranging from 1237 to 1932 ppm; the highest reading was 4692 ppm in School B, and CO2 dropped to around 500–700 ppm during lunch breaks.
  • Only School B met the CIBSE thermal comfort range of 19–21 °C; mean indoor air temperatures ranged from 11.5 °C to 19.4 °C, with School C performing worst.

Methods

  • Four naturally ventilated primary schools in Tai’an city, North China, built at different times under different building codes, were selected as case studies; classrooms had similar floor area, floor height, and student numbers.
  • Field measurements ran from 20 November to 10 December 2016, 8:00 a.m. to 5:00 p.m., with windows closed; equipment was placed 1.5 m above the floor at classroom centers. PM2.5 and PM10, CO2, and indoor air temperature were measured, plus outdoor PM and weekend unoccupied measurements after cleaning.
  • Indoor PM was measured with a BRAMC-SMART-126 detector, outdoor PM with a DUST TRAK model 8530, and temperature/CO2 with an HTV-M detector; results were compared with China GBT18883-2002, WHO, and CIBSE guideline values.

Limitations

  • The paper states that due to limited time and resources, only four primary schools were selected and investigations were carried out over three weeks; it argues these cases represent most local primary schools because of standardized school design.
  • The paper identifies future research needs: more school buildings, seasonal effects on indoor air quality, penetrability of different particle sizes, and effects of crack distribution in building envelopes.
  • Evident from the text: measurements were winter-only, the sample was small, and PM2.5 and PM10 could not be measured simultaneously because the DUST TRAK model 8530 cannot measure both at once, so PM2.5 was measured in the morning and PM10 in the afternoon.

Model-written summary. Check it against the paper before relying on it.

Integrity signals

Registry

Crossref · 10.3390/su9071180

Cites

31 of 31 references verified0 citation errors · 0 not checkable

Statistics

Nothing to recompute.

Verification

Claims the paper makes

5 Valid · 2 Not valid · 16 Not checked · 64 Own results and interpretations

24 more claims

Create a free account to see all 87 claims and to verify the 2 references still open.

See all claims — free account
  • Probably not a substantial claim. 31
  • It may state two separate claims as one. 39

Create a free account to see these claims.

Self-check

Percentages, sums and reported differences re-computed from the paper’s own numbers.

3 of 3

Citations

Cites

Show all 32 references

Research works printed but not linked: 1

  1. Lin, B. (2012). China Energy Development Report 2012, Press of Peking University.

Cited by

See all 109

Metadata

Authors
Peng, Z., Deng, W., & Tenorio, R.
Affiliations
  • University of Nottingham Ningbo China (CN)
  • Department of Architecture and Built Environment, the University of Nottingham Ningbo China, 199 Taikang East Road, Ningbo 315100, China
Corresponding author
Deng, Wu
Venue
Sustainability
Publisher
MDPI AG
Published
2017-07-05
Volume
9
Issue
7
Pages
1180
ISSN
2071-1050 (ISSN-L)
OpenAlex
W2729710293
Cited by
109
References
32
Citations by year
2026: 8 · 2025: 14 · 2024: 13 · 2023: 21 · 2022: 13 · 2021: 9 · 2020: 14 · 2019: 8 · 2018: 9
FWCI
4.31
Type
journal article
Language
en
Open access
Locations
  • Sustainability (publishedVersion, cc-by)
  • Nottingham ePrints (University of Nottingham) (submittedVersion, cc-by)
  • Repository@Nottingham (University of Nottingham) (submittedVersion, cc-by)
  • RePEc: Research Papers in Economics (submittedVersion)
  • DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
Topics
  • Physical Sciences › Environmental Science › Health, Toxicology and Mutagenesis › Indoor Air Quality and Microbial Exposure
  • Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
  • Health Sciences › Medicine › Pulmonary and Respiratory Medicine › Infection Control and Ventilation
Keywords
indoor air quality, elementary school, naturally ventilated buildings, particulate matter, PM2.5, PM10, carbon dioxide, indoor-outdoor concentration ratio, construction defects, occupant activities, indoor temperature, ambient air pollution, mechanical ventilation, air purification, North China

About these checks

Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.

The claim verdicts this report counts are experimental: their accuracy is not yet measured.

A language model drew the claims from the paper on 2026-09-28, under version 3 of the claim definition (prompt extract-v3).

A second model labelled each claim on 2026-09-28 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).

Cited sources are checked with a language model’s help (gpt-6-sol).

Statistics and arithmetic are recomputed, not judged.

Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.

What counts as a claim ›How we measure confidence ›How we check this ›

Are you an author, or do you see a problem with this page? Request a review

How to cite

Cite CoChat for the checks on this page, and the paper for its own findings.

This page
CoChat. (2026). Citation check: Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China. https://app.cochat.ai/papers/10.3390/su9071180
The paper
Peng, Z., Deng, W., & Tenorio, R. (2017). Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China. Sustainability. https://doi.org/10.3390/su9071180

Data sources

Bibliographic data: Semantic Scholar, OpenAlex, Crossref.

Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).

Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.