Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China
Open accessAbstract
Indoor air quality in four naturally ventilated schools was influenced by building defects and occupants' activities; indoor particulate concentrations could exceed outdoor levels during occupied periods.
Overview
CoChat Summary
TL;DR
In four naturally ventilated primary schools in Tai’an, North China, winter indoor PM2.5, PM10, CO2, and temperature mostly failed IAQ and comfort standards. Building air tightness and occupant activities strongly influenced indoor PM and CO2, with tighter buildings reducing particle penetration but closed windows raising CO2.
Key findings
- Occupied classrooms had mean PM2.5 concentrations of 149–199 µg/m³ and mean PM10 concentrations of 138–205 µg/m³, about 5 times higher than WHO and Chinese standard requirements; the highest PM2.5 was 274 µg/m³ in School D, and the highest PM10 was 267 µg/m³ in School C.
- In unoccupied classrooms, School B had the lowest indoor/outdoor ratios (0.49 for PM2.5, 0.47 for PM10), while School C had the highest (0.85 for PM2.5, 0.9 for PM10); Schools A and D, both air tightness level 4, had I/O ratios around 0.54–0.69.
- Occupied CO2 means all exceeded the WHO 600 ppm and China 1000 ppm limits, ranging from 1237 to 1932 ppm; the highest reading was 4692 ppm in School B, and CO2 dropped to around 500–700 ppm during lunch breaks.
- Only School B met the CIBSE thermal comfort range of 19–21 °C; mean indoor air temperatures ranged from 11.5 °C to 19.4 °C, with School C performing worst.
Methods
- Four naturally ventilated primary schools in Tai’an city, North China, built at different times under different building codes, were selected as case studies; classrooms had similar floor area, floor height, and student numbers.
- Field measurements ran from 20 November to 10 December 2016, 8:00 a.m. to 5:00 p.m., with windows closed; equipment was placed 1.5 m above the floor at classroom centers. PM2.5 and PM10, CO2, and indoor air temperature were measured, plus outdoor PM and weekend unoccupied measurements after cleaning.
- Indoor PM was measured with a BRAMC-SMART-126 detector, outdoor PM with a DUST TRAK model 8530, and temperature/CO2 with an HTV-M detector; results were compared with China GBT18883-2002, WHO, and CIBSE guideline values.
Limitations
- The paper states that due to limited time and resources, only four primary schools were selected and investigations were carried out over three weeks; it argues these cases represent most local primary schools because of standardized school design.
- The paper identifies future research needs: more school buildings, seasonal effects on indoor air quality, penetrability of different particle sizes, and effects of crack distribution in building envelopes.
- Evident from the text: measurements were winter-only, the sample was small, and PM2.5 and PM10 could not be measured simultaneously because the DUST TRAK model 8530 cannot measure both at once, so PM2.5 was measured in the morning and PM10 in the afternoon.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Verification
Claims the paper makes
5 Valid · 2 Not valid · 16 Not checked · 64 Own results and interpretations
The cited sources that could be checked couldn’t confirm or dispute this claim.
In the paper
“Over 70% of a pupil's school life is spent inside a classroom”
- Also stated in: § 1. Introduction · plain
“Bakó-Biró et al. [18] figured out that over 30% of a pupil's life was spent at schools, and about 70% of their time inside a classroom during school days.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > Abstract
What the sources say
- Could not verifycites [18] Wargocki, 2004, Effects of pollution from personal computers on perceived air quality, SBS symptoms and productivity in offices, Indoor Air sourceExperimental — accuracy not yet measured
The Introduction discusses how much of employees’ working time involves PCs, and the Approach describes an office experiment with adult subjects. Searches for pupils, classrooms, and the 70% figure found no passage about how pupils spend their school time. The cited paper therefore does not verify this claim. (LLM, conf=0.75)
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
- Also stated in: § 1. Introduction · plain
A result the paper states — it cites no source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“In addition, indoor comfort is not satisfied in most of the schools investigated.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > 4. Discussion
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“From Table 5 it can be seen that the schools cannot meet the requirement of thermal comfort based on the recommended values of 19 • C to 21 • C from CIBSE, except School B.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > 3.2. Temperature
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“The mean values range from 1237 ppm to 1932 ppm.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > 3.3. CO 2
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: unclear — It is unclear whether the paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
A result the paper reports from its own data — it cites no other source for it, so there is none to check. The quote shows it is in the paper.
In the paper
“All of the indoor mean values of PM 2.5 are above the annual standard and the 24 h guideline values of the WHO and the GBT18883-2002 of China.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > 3.1. PM 2.5 and PM 10
plain- Asserted: passes — The authors put it forward as true.
- Checkable: passes — It can be checked against evidence.
- Load-bearing: passes — The paper’s conclusions depend on it.
- Based: passes — The paper gives a reason why it holds.
24 more claims
Create a free account to see all 87 claims and to verify the 2 references still open.
- Probably not a substantial claim. 31
- It may state two separate claims as one. 39
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Rated major: it would touch a result — a value a result rests on, reported and recomputed p-values on opposite sides of the significance level, two passages that conflict with no sign which is right, or a cited work retracted before this paper was published.
In the paper
“The average indoor PM 2.5 and PM 10 concentrations in occupied classrooms range from 199 µg/m 3 to 149 µg/m 3 and 205 µg/m 3 to 138 µg/m 3 , respectively, which is 5 times higher than the requirements of the WHO's and China's standards.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > 3.1. PM 2.5 and PM 10
Reported 5 · recomputed 2.76
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
“the results indicated that 33% of the samples had a CO 2 concentration above 1700 ppm, which is two times greater than the CIBSE value.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > 1. Introduction
Reported 2 · recomputed 2.833333
Rated minor: it would not touch a result — a value no result rests on, a p-value that stays on the same side of the significance level, or a conflict that is clerical, resolved elsewhere in the paper, or outside its own findings.
In the paper
“Ramalho et al. [34] investigated the indoor CO 2 concentration in 489 mechanically ventilated classrooms in France, and the results indicated that 33% of the samples had a CO 2 concentration above 1700 ppm, which is two times greater than the CIBSE value.”
§ Investigation of Indoor Air Quality and the Identification of Influential Factors at Primary Schools in the North of China > 1. Introduction
Reported 2 · recomputed 2.833333
Citations
Cites
Daisey, J. M., Angell, W. J., & Apte, M. G. (2003) · Indoor Air · doi:10.1034/j.1600-0668.2003.00153.x · Cited by 977
Seppanen, O. A., Fisk, W. J., & Mendell, M. J. (1999) · Indoor Air · doi:10.1111/j.1600-0668.1999.00003.x · Cited by 876 · cited 1×
“[14] found that the risk of air-related health problems can be decreased when CO2 concentrations fall below 800 ppm.”
BackgroundVentilation rates and health: Multidisciplinary review of the scientific literature
Sundell, J., Levin, H., Nazaroff, W. W., Cain, W. S., Fisk, W. J., Grimsrud, D. T., Gyntelberg, F., Li, Y., Persily, A. K., Pickering, A. C., et al. (2011) · Indoor Air · doi:10.1111/j.1600-0668.2010.00703.x · Cited by 740 · cited 1×
“[8] concluded that the incidence of inflammation, respiratory infections, asthma symptoms, and short-term sickness is enhanced as a result of high exposure to air pollutants.”
BackgroundJanssen, N. A. H., Brunekreef, B., van Vliet, P., Aarts, F., Meliefste, K., Harssema, H., & Fischer, P. (2003) · Environmental Health Perspectives · doi:10.1289/ehp.6243 · Cited by 422 · cited 1×
“[27] pointed out that schools close to roadways with heavy traffic usually have higher numbers of children suffering from bronchial hyper responsiveness, positive allergic sensitization, or both, compared with schools located far away from the traffic or industrial areas.”
BackgroundIndoor particulate matter of outdoor origin: Importance of size-dependent removal mechanisms
Riley, W. J., McKone, T. E., Lai, A. C. K., & Nazaroff, W. W. (2002) · Environmental Science & Technology · doi:10.1021/es010723y · Cited by 417 · cited 1×
“[10] suggested that the penetration of particles through building cracks would significantly affect indoor air quality, especially for buildings where air exchange through openings or cracks is dominated by pressure differences arising from natural forces.”
BackgroundRelative contribution of outdoor and indoor particle sources to indoor concentrations
Abt, E., Suh, H. H., Catalano, P., & Koutrakis, P. (2000) · Environmental Science & Technology · doi:10.1021/es990348y · Cited by 411 · cited 1×
“[12] found that cleaning activities and the movement of people significantly increased PM(0.”
BackgroundFang, L., Wyon, D. P., Clausen, G., & Fanger, P. O. (2004) · Indoor Air · doi:10.1111/j.1600-0668.2004.00276.x · Cited by 380 · cited 1×
“[15] indicated that indoor air temperature has great impact on perceived air quality in office buildings, and high air temperatures can promote the generation of other pollutants, such as volatile organic compounds (VOCs) and formaldehyde.”
BackgroundCharacterization of Indoor Particle Sources Using Continuous Mass and Size Monitors
Long, C. M., Suh, H. H., & Koutrakis, P. (2000) · Journal of the Air & Waste Management Association · doi:10.1080/10473289.2000.10464154 · Cited by 364 · cited 1×
“[13] investigated nine homes in Boston and figured out that dusting, vigorous walking, and sautéing were the key factors affecting indoor air quality.”
BackgroundMechanisms underlying Children's susceptibility to environmental toxicants.
Faustman, E. M., Silbernagel, S. M., Fenske, R. A., Burbacher, T. M., & Ponce, R. A. (2000) · Environmental Health Perspectives · doi:10.1289/ehp.00108s113 · Cited by 344 · cited 1×
“Children are more sensitive when they are exposed to unhealthy air, because they generally breathe a higher volume of air relative to body weight at a faster rate [16,17].”
BackgroundAssociation between substandard classroom ventilation rates and students’ academic achievement
Haverinen-Shaughnessy, U., Moschandreas, D. J., & Shaughnessy, R. J. (2011) · Indoor Air · doi:10.1111/j.1600-0668.2010.00686.x · Cited by 311 · cited 1×
“[20] investigated one hundred elementary schools in the southwest of the U.”
BackgroundA Method to Estimate the Chronic Health Impact of Air Pollutants in U.S. Residences
Logue, J. M., Price, P. N., Sherman, M. H., & Singer, B. C. (2012) · Environmental Health Perspectives · doi:10.1289/ehp.1104035 · Cited by 251
Indoor air quality investigation according to age of the school buildings in Korea
Yang, W., Sohn, J., Kim, J., Son, B., & Park, J. (2009) · Journal of Environmental Management · doi:10.1016/j.jenvman.2007.10.003 · Cited by 235 · cited 1×
“In school buildings, the resuspension of particles by students’ indoor activities also affects the indoor particle concentration in occupied classrooms [28,29].”
BackgroundShaughnessy, R. J., Haverinen-Shaughnessy, U., Nevalainen, A., & Moschandreas, D. (2006) · Indoor Air · doi:10.1111/j.1600-0668.2006.00440.x · Cited by 230 · cited 1×
“[19] claimed that poor indoor air quality caused by excessive CO2 and VOC concentrations have a negative impact on students’ attendance and learning potential, and lead to poor academic performance.”
BackgroundSources of indoor and outdoor PM2.5 concentrations in primary schools
Amato, F., Rivas, I., Viana, M., Moreno, T., Bouso, L., Reche, C., Àlvarez-Pedrerol, M., Alastuey, A., Sunyer, J., & Querol, X. (2014) · Science of The Total Environment · doi:10.1016/j.scitotenv.2014.05.051 · Cited by 207 · cited 1×
“[26] investigated 39 primary schools in Barcelona and found that 53% of the indoor PM2.”
BackgroundBako-Biro, Z., Wargocki, P., Weschler, C. J., & Fanger, P. O. (2004) · Indoor Air · doi:10.1111/j.1600-0668.2004.00218.x · Cited by 180 · cited 1×
“[18] figured out that over 30% of a pupil’s life was spent at schools, and about 70% of their time inside a classroom during school days.”
BackgroundControl of CO2 in a naturally ventilated classroom
Griffiths, M., & Eftekhari, M. (2008) · Energy and Buildings · doi:10.1016/j.enbuild.2007.04.013 · Cited by 159 · cited 5×
“Sustainability 2017, 9, 1180 3 of 14 Apart from those chemical toxicants and particulate matters, it is found that the CO2 level may exceed 1500 ppm in classrooms in East London, which is much higher than the recommended level of 600 ppm from the Chartered Institution of Building Services Engineers (CIBSE) [33].”
BackgroundInfluentialAssessment of ventilation and indoor air pollutants in nursery and elementary schools in France
Canha, N., Mandin, C., Ramalho, O., Wyart, G., Ribéron, J., Dassonville, C., Hänninen, O., Almeida, S. M., & Derbez, M. (2015) · Indoor Air · doi:10.1111/ina.12222 · Cited by 158
de Gennaro, G., Farella, G., Marzocca, A., Mazzone, A., & Tutino, M. (2013) · International Journal of Environmental Research and Public Health · doi:10.3390/ijerph10126273 · Cited by 141
Mechanisms Underlying Children's Susceptibility to Environmental Toxicants
Faustman, E. M., Silbernagel, S. M., Fenske, R. A., et al. (2000) · Environmental Health Perspectives · doi:10.2307/3454629 · Cited by 121
Improving air pollution control policy in China—A perspective based on cost–benefit analysis
Gao, J., Yuan, Z., Liu, X., et al. (2015) · The Science of The Total Environment · doi:10.1016/j.scitotenv.2015.11.037 · Cited by 111
Indoor Air Aerosol Model: Transport Indoors and Deposition of Fine and Coarse Particles
Raunemaa, T. M., Kulmala, M., Saari, H., Olin, M., & Kulmala, M. H. (1989) · Aerosol Science and Technology · doi:10.1080/02786828908959296 · Cited by 96 · cited 1×
“[31] reported that the average concentration of particles larger than 1.”
BackgroundZwoździak, A., Sówka, I., Krupińska, B., Zwoździak, J., & Nych, A. (2013) · Building and Environment · doi:10.1016/j.buildenv.2013.04.023 · Cited by 90 · cited 1×
“[25] concluded that there is a positive correlation between outdoor air pollution and indoor air quality, suggesting that urgent action should be taken to improve a building’s air tightness and reduce air infiltration.”
BackgroundMullen, N. A., Bhangar, S., Hering, S. V., Kreisberg, N. M., & Nazaroff, W. W. (2011) · Indoor Air · doi:10.1111/j.1600-0668.2010.00690.x · Cited by 90 · cited 1×
“In school buildings, the resuspension of particles by students’ indoor activities also affects the indoor particle concentration in occupied classrooms [28,29].”
BackgroundConcentration of particulate matter, CO and CO2 in selected schools in Malaysia
Razali, N. Y. Y., Latif, M. T., Dominick, D., Mohamad, N., Sulaiman, F. R., & Srithawirat, T. (2015) · Building and Environment · doi:10.1016/j.buildenv.2015.01.015 · Cited by 85
HUANG, H., LEE, S.-C., CAO, J.-J., ZOU, C.-W., CHEN, X.-G., & FAN, S.-J. (2007) · Journal of Environmental Sciences · doi:10.1016/s1001-0742(07)60006-0 · Cited by 60 · cited 1×
“However, it may not be safer to stay indoors, as some studies suggest that indoor air quality closely correlates to the outdoor pollution level, particularly in urban and industrial areas [9].”
BackgroundAir Stuffiness and Air Exchange Rate in French Schools and Day-Care Centres
Ramalho, O., Mandin, C., Ribéron, J., & Wyart, G. (2013) · International Journal of Ventilation · doi:10.1080/14733315.2013.11684013 · Cited by 59 · cited 1×
“[34] investigated the indoor CO2 concentration in 489 mechanically ventilated classrooms in France, and the results indicated that 33% of the samples had a CO2 concentration above 1700 ppm, which is two times greater than the CIBSE value.”
Mathematical model of particle penetration through smooth/rough building envelop leakages
Tian, L., Zhang, G., Lin, Y., Yu, J., Zhou, J., & Zhang, Q. (2009) · Building and Environment · doi:10.1016/j.buildenv.2008.08.007 · Cited by 57 · cited 1×
“[11] concluded that for naturally ventilated buildings, the key factors which determine occupants’ exposure to air pollutants were pressure difference, building air tightness, and air flow path.”
BackgroundEnvironmental hazards for children in USA.
Pj, L. (1998) · PubMed · Cited by 39
Particulates in Domestic Premises: II. Ambient Levels and Indoor-Outdoor Relationships
Lefcoe, N. M., & Inculet, I. I. (1975) · Archives of Environmental Health: An International Journal · doi:10.1080/00039896.1975.10666780 · Cited by 37 · cited 2×
“Lefcoe and Inculet [30] found that indoor activities, such as cleaning and children playing, had significant impacts on the indoor concentration of particles greater than 1 µm.”
BackgroundMajumdar, D., Gajghate, D. G., Pipalatkar, P., & Chalapati Rao, C. V. (2012) · Indoor and Built Environment · doi:10.1177/1420326x11419691 · Cited by 27
Indoor Particulate Matter of Outdoor Origin: Importance of Size-Dependent Removal Mechanisms
Riley, W. J., McKone, T. E., Lai, A. C. K., et al. (2002) · Environmental Science & Technology · doi:10.1021/es020595t
Research works printed but not linked: 1
- Lin, B. (2012). China Energy Development Report 2012, Press of Peking University.
Cited by
Tran, V. V., Park, D., & Lee, Y.-C. (2020) · International Journal of Environmental Research and Public Health · doi:10.3390/ijerph17082927 · Cited by 822
“It has been indicated that IAQ in residential areas or buildings is significantly affected by three primary factors [12,13]: (i) Outdoor air quality, (ii) human activity in buildings, and (iii) building and construction materials, equipment, and furniture.”
BackgroundAzuma, K., Kagi, N., Yanagi, U., & Osawa, H. (2018) · Environment International · doi:10.1016/j.envint.2018.08.059 · Cited by 403
Pettit, T. J., Irga, P. J., & Torpy, F. R. (2018) · Air Quality Atmosphere & Health · doi:10.1007/s11869-018-0628-7 · Cited by 106
“…poor air quality (Gulia et al. 2015; Han et al. 2014), as the activities in these areas promote the generation of airborne pollutants, primarily particulate matter (PM) (Guo et al. 2010; Morawska and Clark 2000), which can penetrate and contaminate the urban indoor environment (Perez et al. 2016).”
BackgroundOthman, M., Latif, M. T., & Matsumi, Y. (2018) · Ecotoxicology and Environmental Safety · doi:10.1016/j.ecoenv.2018.12.042 · Cited by 82
Indoor Air Pollution and Health: Bridging Perspectives from Developing and Developed Countries
Pillarisetti, A., Ye, W., & Chowdhury, S. (2022) · Annual Review of Environment and Resources · doi:10.1146/annurev-environ-012220-010602 · Cited by 93
Metadata
- Authors
- Peng, Z., Deng, W., & Tenorio, R.
- Affiliations
- University of Nottingham Ningbo China (CN)
- Department of Architecture and Built Environment, the University of Nottingham Ningbo China, 199 Taikang East Road, Ningbo 315100, China
- Corresponding author
- Deng, Wu
- ORCID
- Venue
- Sustainability
- Publisher
- MDPI AG
- Published
- 2017-07-05
- Volume
- 9
- Issue
- 7
- Pages
- 1180
- ISSN
- 2071-1050 (ISSN-L)
- OpenAlex
- W2729710293
- Cited by
- 109
- References
- 32
- Citations by year
- 2026: 8 · 2025: 14 · 2024: 13 · 2023: 21 · 2022: 13 · 2021: 9 · 2020: 14 · 2019: 8 · 2018: 9
- FWCI
- 4.31
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Licence
- Locations
- Sustainability (publishedVersion, cc-by)
- Nottingham ePrints (University of Nottingham) (submittedVersion, cc-by)
- Repository@Nottingham (University of Nottingham) (submittedVersion, cc-by)
- RePEc: Research Papers in Economics (submittedVersion)
- DOAJ (DOAJ: Directory of Open Access Journals) (submittedVersion, cc-by-sa)
- Topics
- Physical Sciences › Environmental Science › Health, Toxicology and Mutagenesis › Indoor Air Quality and Microbial Exposure
- Physical Sciences › Engineering › Building and Construction › Building Energy and Comfort Optimization
- Health Sciences › Medicine › Pulmonary and Respiratory Medicine › Infection Control and Ventilation
- Keywords
- indoor air quality, elementary school, naturally ventilated buildings, particulate matter, PM2.5, PM10, carbon dioxide, indoor-outdoor concentration ratio, construction defects, occupant activities, indoor temperature, ambient air pollution, mechanical ventilation, air purification, North China
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
The claim verdicts this report counts are experimental: their accuracy is not yet measured.
A language model drew the claims from the paper on 2026-09-28, under version 3 of the claim definition (prompt extract-v3).
A second model labelled each claim on 2026-09-28 (model jev-1.13-20260917, definition revision gold-guideline-v0.2).
Cited sources are checked with a language model’s help (gpt-6-sol).
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.