Air-side thermal hydraulic performance of multi-louvered fin aluminum heat exchangers
AI snapshot
Written from the paper’s full text.
TL;DR
This experimental study measured air-side heat transfer and pressure drop for 45 multi-louvered fin and flat-tube aluminum heat exchangers over louver angles of 15–29°, fin pitches of 1.0/1.2/1.4 mm, flow depths of 16/20/24 mm, and air-side Reynolds numbers based on louver pitch of 100–600. General Colburn j and Fanning friction f correlations were developed with rms errors of ±14.5% and ±7%, respectively.
Key findings
- Heat transfer coefficients decrease with flow depth and increase with face air velocity; pressure drops increase with flow depth and air velocity. For 24 mm flow depth, heat transfer coefficients increase with louver angle up to a maximum at 27° and then decrease; for 16 mm flow depth they do not change much with louver angle.
- Friction factors increase with louver angle, but the effect decreases for louver angles larger than 21°. For louver angles below 19°, heat transfer coefficients decrease with fin pitch; for louver angles larger than 23°, they increase with fin pitch. The effect of fin spacing on heat transfer is relatively small (2–15%) and depends on flow depth and Reynolds number.
- The j factors for 16 and 20 mm flow depths are similar, while those for 24 mm are smaller; the f factors for 20 and 24 mm flow depths are similar, while those for 16 mm are relatively smaller. The paper attributes this partly to different tube geometry (2 mm for 20 and 24 mm flow depths and 3 mm for 16 mm).
- The j correlation predicts 225 test data points within an rms error of ±14.5%, and the f correlation within ±7%. The f correlation indicates that flow depth is an important parameter for pressure drop; the present and Sunden and Svantesson correlations reflect flow-depth effects, while other compared correlations do not.
Methods
- Tests used a suction-type wind tunnel in a constant-temperature and humidity chamber with 45 multi-louvered fin and flat-tube heat exchangers. Louver pitch, louver length, and fin height were 1.7, 6.4, and 8.15 mm; tested core size was 350×255 mm; tube pitches were 11.15 and 10.15 mm.
- Test conditions were air-side Reynolds numbers based on louver pitch and maximum velocity of 100–600, a constant tube-side water flow rate of 0.32 m³/h, and inlet air and water temperatures of 21°C and 45°C. Data were reduced using the effectiveness-NTU method for cross-flow with both fluids unmixed, and results were expressed as Colburn j and Fanning friction f factors versus Reynolds number based on louver pitch.
- Measurement uncertainties were less than ±3% for heat transfer rate, ±12% for heat transfer coefficients, and ±10% for pressure drops.
Limitations
- The paper states no dedicated limitations section. Stated constraints include that the j and f correlations were developed from 225 test data points for Fp/Lp < 1, with rms errors of ±14.5% and ±7%, and that tests covered only air-side Reynolds numbers of 100–600, a water flow rate of 0.32 m³/h, and inlet air/water temperatures of 21°C/45°C.
- Evident from the text: the 45 samples cover limited geometry ranges (louver angles 15–29°, fin pitches 1.0–1.4 mm, flow depths 16–24 mm), so extrapolation beyond these configurations and test conditions is not supported. Comparisons with other correlations use only two sample heat exchangers (type I and type II), and some explanations for differences among correlations are described as difficult to explain.
- The published record includes an erratum correcting Figs. 9 and 11 of the original paper.
Model-written summary. Check it against the paper before relying on it.
Integrity signals
Registry
Cites
Statistics
Claims the paper makes
0 of 10 cited sources checked · 0 supported · 0 flagged
- Findingown data§ 3. Results and discussion · p. 7
The effect of louver angle on the heat transfer coefficients depends on flow depth.
“the effect of louver angle on the heat transfer coefficients depends on flow depth”
Quote in the paperSubstantial claim - Findingown data§ 3. Results and discussion · p. 8
For a 20 mm flow depth, the effect of louver angle on heat transfer and pressure drop varies with face velocity, decreasing with face air velocity due to more mixing at larger face velocities.
“For 20 mm flow depth, the effect of louver angle on the heat transfer and pressure drop varies with face velocity. It decreases with face air velocity due to more mixing for larger face velocities.”
Quote in the paperSubstantial claim - Findingown data§ 3. Results and discussion · p. 7
Pressure drops for all tested flow depths increase with louver angle.
“Pressure drops for all flow depths increase with louver angle”
- Also stated in: § 4. Concluding remarks · p. 10 · plain
“Pressure drops increase with louver angle and flow depth and decrease with increasing fin pitch.”
Quote in the paperSubstantial claim - Also stated in: § 4. Concluding remarks · p. 10 · plain
- Findingown data§ 3. Results and discussion · p. 7
For a 16 mm flow depth, heat transfer coefficients do not change much with louver angle.
“For 16 mm flow depth, heat transfer coefficients do not change much with louver angle.”
Quote in the paperNot a substantial claim - Findingown data§ 3. Results and discussion · p. 8
The heat transfer behaviors with fin pitch observed here are different compared to conventional finned tube heat exchangers.
“These heat transfer behaviors with fin pitch are different, compared to the conventional finned tube heat exchangers.”
Quote in the paperSubstantial claim
- Findingown data§ 4. Concluding remarks · p. 10
Pressure drops decrease with increasing fin pitch.
“Pressure drops increase with louver angle and flow depth and decrease with increasing fin pitch.”
Quote in the paperSubstantial claim - Findingreasoning§ 3. Results and discussion · p. 8
For louver angles larger than 23 degrees, heat transfer coefficients increase with fin pitch.
“for louver angle larger than 23 heat transfer coefficients increase with fin pitch”
Quote in the paperSubstantial claim - Findingown data§ 3.1. Heat transfer correlation · p. 9
The present j-factor correlation predicts the test data within an rms error of 14.5%.
“The present correlation predicts the test data within rms error of 14.5%.”
Quote in the paperSubstantial claim - Findingown data§ 3.2. Pressure drop correlation · p. 10
The present f-factor correlation and the test data are in good agreement within an rms error of 7%.
“The correlation and test data are in good agreement within rms error of 7%.”
Quote in the paperSubstantial claim - Findingnone given§ 4. Concluding remarks · p. 10
The effect of fin spacing on the pressure drop decreases with louver angle.
“The effect of fin spacing on the pressure drop decreases with louver angle.”
Quote in the paperSubstantial claim - Findingcitation§ 3. Results and discussion · p. 8
The observed j and f factor characteristics with flow depth are not consistent with conventional finned tube heat exchangers at low Reynolds numbers.
“These characteristics are not consistent with the conventional finned tube heat exchangers at low Reynolds numbers [27,28].”
Quote in the paperNot a substantial claim0 of 2 sources checked- cites [27] Rich, 1975, The effect of the number of tube rows on heat transfer performance of smooth plate fin-and-tube heat exchangers, ASHRAE Trans.
Not checked in the free run.
- cites [28] DeJong, 1998, A complementary experimental and numerical study of the flow and heat transfer in offset strip-fin heat exchangers, J. Heat Transfer source
- Findingreasoning§ 3. Results and discussion · p. 8
For a small louver angle (less than 19 degrees), heat transfer coefficients decrease with fin pitch.
“For a small louver angle ( L a < 19 ), heat transfer coefficients decrease with fin pitch.”
Quote in the paperSubstantial claim - Interpretationreasoning§ 3. Results and discussion · p. 8
The observed j and f factor characteristics may be caused partly by the different tube geometry (tube wall thickness of 2 mm for 20 and 24 mm flow depths and 3 mm for 16 mm flow depth).
“These may be caused partly from the different tube geometry ( t =2 mm for F d=20 and 24 mm and t =3 mm for F d=16 mm).”
Quote in the paperNot a substantial claim - Study design and conductreasoning§ 2.1. Test apparatus · p. 3
The uncertainty in the heat transfer rate measurement is less than 3%, given temperature measurement accuracy of 0.1 degrees C and air and water flow rate accuracies of 1 and 2%.
“The uncertainty in the heat transfer rate measurement is less than 3%, since accuracy of the temperature measurement is 0.1 C and accuracy of air and water flow rates are 1 and 2%, respectively.”
Quote in the paperNot a substantial claim - Study design and conductown data§ 3.2. Pressure drop correlation · p. 9
The friction factor f correlation was derived from 225 test data points for fin pitch to louver pitch ratio less than 1.
“Correlation for the friction factor f , is derived from 225 test data points for F p/ L p < 1.”
Quote in the paperNot a substantial claim - Interpretationreasoning§ 3. Results and discussion · p. 7
The decrease in heat transfer coefficients for larger flow depth and smaller velocity suggests that the effect of boundary layer growth in the duct-directed portion of the flow is larger than the effect of adding louvers in the louver-directed portion of the flow.
“The decrease in the heat transfer coefficients in case of larger flow depth and smaller velocity, suggests that the effect of boundary layer growth in the duct-directed portion of the flow is larger than the effect of adding louvers in the louver-directed portion of the flow.”
Quote in the paperSubstantial claim - Interpretationown data§ 4. Concluding remarks · p. 10
The general correlations for the Colburn j and friction f factors can be used over a wide variety of louver configurations, especially heat exchangers with larger flow depth.
“they can be used over a wide variety of louver configurations, especially heat exchangers with larger flow depth.”
Quote in the paperSubstantial claim - Interpretationreasoning§ 3.2. Pressure drop correlation · p. 10
Flow depth is one of the important parameters that significantly influences the friction factor and pressure drop.
“This suggests that the flow depth is one of the important parameters, which influences the friction factor significantly.”
- Also stated in: § 4. Concluding remarks · p. 10 · hedged
“The f correlation indicates that the flow depth is one of the important parameters, which affects the pressure drop significantly.”
Quote in the paperSubstantial claim - Also stated in: § 4. Concluding remarks · p. 10 · hedged
- Study design and conductown data§ 3.1. Heat transfer correlation · p. 9
The j-factor correlation was obtained using 225 test data points from 45 different heat exchanger configurations with fin pitch to louver pitch ratio less than 1.
“Correlation for the j factor is obtained using 225 test data points from 45 different heat exchanger configurations with F p/ L p < 1”
Quote in the paperSubstantial claim - Study design and conductcitation§ 2.4. Data reduction · p. 5
The water-side heat transfer coefficient equation was developed based on test results obtained for the same micro-channel tubes used in this study, with an rms error of 3%.
“the following equation is developed based on test results obtained for the same micro-channel tubes used in this study with a rms error of 3% [21].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [21] Kim N-H. Private communications, University of Incheon, Incheon, Korea, 1998.
Couldn’t be matched to a paper in Crossref, so it can’t be checked.
- Interpretationcitation§ 3.1. Heat transfer correlation · p. 9
Heat exchangers with a smaller non-louvered portion have relatively higher heat transfer coefficients.
“suggesting that the heat exchangers with a smaller non-louvered portion have relatively higher heat transfer coefficients.”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [5] Achaichia, 1988, Heat transfer and pressure drop characteristics of flat and louvered plate fin surface, Exp. Thermal and Fluid Sci. source
- May combine two claims. 16
- Classified as probably not a substantial claim. 4
- The quote only partly states this claim. 1
May combine two claims.
Findingown data§ 3. Results and discussion · p. 8Friction factors increase with louver angle, but the effect of louver angle on the f factor decreases for louver angles larger than 21 degrees.
“Friction factors increase with louver angle, but the effect of louver angle on the f factor decreases for louver angles larger than 21”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 3. Results and discussion · p. 7For a 24 mm flow depth, heat transfer coefficients increase with louver angle, reach a maximum at 27 degrees, and then decrease with louver angle.
“for 24 mm flow depth, heat transfer coefficients increase with louver angle, have a maximum at 27 , and again decrease with louver angle”
Quote in the paperSubstantial claimMay combine two claims.
Findingnone given§ 3. Results and discussion · p. 7For the tested heat exchangers, the air-side pressure drops increase with flow depth and air velocity.
“the pressure drops increase with flow depth and air velocity”
Quote in the paperSubstantial claimMay combine two claims.
Findingreasoning§ 3. Results and discussion · p. 7For the tested multi-louvered fin heat exchangers, the air-side heat transfer coefficients decrease with flow depth and increase with face air velocity.
“the heat transfer coefficients decrease with flow depth and increase with face velocity”
- Also stated in: § 4. Concluding remarks · p. 10 · plain
“Heat transfer coefficients decrease with flow depth and increase exponentially with face air velocity.”
Quote in the paperSubstantial claim- Also stated in: § 4. Concluding remarks · p. 10 · plain
May combine two claims.
Findingown data§ 3. Results and discussion · p. 8The j factor increases with louver angle, but the effect of louver angle on the j factor varies with flow depth.
“The j factor increases with louver angle, but its effect on the j factor varies with flow depth.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 3. Results and discussion · p. 8The j factors for flow depths of 16 and 20 mm are similar, while those for a 24 mm flow depth are smaller.
“the j factors for F d=16 and 20 mm are similar and for F d=24 mm are smaller”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 4. Concluding remarks · p. 10The effect of louver angle on heat transfer is different according to flow depth, fin spacing and Reynolds number, but the effect of fin spacing is relatively small.
“The effect of louver angle on heat transfer is different according to flow depth, fin spacing and Reynolds number, but the effect of fin spacing is relatively small.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 3. Results and discussion · p. 8For a 24 mm flow depth, the j factor increases with louver angle for louver angles up to 27 degrees and decreases with louver angle for louver angles greater than 27 degrees.
“for F d=24 mm, j factor increases with louver angle for L a 4 27 , and decreases with louver angle for L a >27”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 3. Results and discussion · p. 8The effect of fin spacing on the heat transfer is relatively small (2-15%) and depends on flow depth and Reynolds number.
“The effect of fin spacing on the heat transfer is relatively small (2-15%) and depends on flow depth and Reynolds number.”
Quote in the paperSubstantial claimMay combine two claims.
Findingown data§ 3. Results and discussion · p. 8The f factors for flow depths of 20 and 24 mm are similar, while those for a 16 mm flow depth are relatively smaller than those of larger flow depth.
“the f factors for F d=20 and 24 mm are similar and for F d=16 mm are relatively smaller than those of larger flow depth”
Quote in the paperNot a substantial claimMay combine two claims.
Findingreasoning§ 3.1. Heat transfer correlation · p. 9The present, Sunden and Svantesson's, and Chang and Wang's j-factor correlations reflect the effect of different flow depths, while the other correlations give similar j factors for both heat exchangers because flow depth is not included in them.
“The present, Sunden and Svantesson's [13] and Chang and Wang's correlations [16] reflect the effect of different flow depths, while the other correlations have the similar j factors for both heat exchangers since the flow depth is not included in their correlations.”
Quote in the paperSubstantial claim0 of 2 sources checked- cites [13] Sunden B, Svantesson J. Correlation of j- and f-factors for multilouvered heat transfer surfaces. In: Proceedings of the 3rd UK National Conference on Heat Transfer, 1992. pp. 805-11.
Couldn’t be matched to a paper in Crossref, so it can’t be checked.
- cites [16] Chang, 1997, A generalized heat transfer correlation for louvered fin geometry, Int. J. Heat Transfer source
May combine two claims.
Findingnone given§ 3.2. Pressure drop correlation · p. 10The present and Sunden and Svantesson's f-factor correlations reflect the effect of flow depth on the pressure drop, while other correlations do not.
“The present and Sunden and Svantesson's [13] correlations reflect the effect of flow depth on the pressure drop, while other correlations do not reflect.”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [13] Sunden B, Svantesson J. Correlation of j- and f-factors for multilouvered heat transfer surfaces. In: Proceedings of the 3rd UK National Conference on Heat Transfer, 1992. pp. 805-11.
Couldn’t be matched to a paper in Crossref, so it can’t be checked.
Classified as probably not a substantial claim.
Premisenone given§ 1. Introduction · p. 2The air-side thermal-hydraulic performance of multi-louvered fin and flat tube heat exchangers depends on louver geometry such as fin and louver pitches, louver angle, and flow depth.
“The air-side thermal-hydraulic performance of multilouvered fin and flat tube heat exchangers depends on louver geometry such as fin and louver pitches, louver angle, and flow depth.”
Quote in the paperSubstantial claimProbably not a substantial claim: may not pass S3 (load-bearing), S4 (based). May combine two claims.
Study design and conductnone given§ 2.2. Test heat exchangers · p. 4All louver geometries were checked before brazing and the overall heat exchanger quality after brazing was excellent.
“All louver geometries were checked before brazing and overall heat exchanger quality after brazing was excellent.”
Quote in the paperNot a substantial claimProbably not a substantial claim: may not pass S4 (based).
Premisenone given§ 1. Introduction · p. 2A general f correlation for the pressure drop of louvered fin heat exchangers is not available in the open literature.
“the general f correlation for the pressure drop is not available in the open literature.”
Quote in the paperNot a substantial claimMay combine two claims.
Interpretationreasoning§ 3. Results and discussion · p. 8When Reynolds number and louver angle are small and the ratio of fin pitch to louver pitch is large, friction loss along the flow depth becomes less significant so the airflow becomes duct-directed, and this decrease of flow efficiency causes the heat transfer coefficient to decrease.
“When Reynolds number and louver angle are small and the ratio of fin pitch to louver pitch is large, friction loss along the flow depth becomes less significant so the airflow becomes duct-directed. This decrease of flow efficiency causes the heat transfer coefficient to decrease.”
Quote in the paperSubstantial claimMay combine two claims.
Interpretationown data§ 3.1. Heat transfer correlation · p. 9Davenport's correlation is more suitable for heat exchangers with larger flow depth and does not reflect the effect of flow depth.
“indicating that Davenport's correlation [3] is more suitable for the heat exchangers with larger flow depth and does not reflect the effect of flow depth.”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [3] Davenport, 1983, Correlation for heat transfer and friction characteristics of louvered fin, AICHE Sym. Ser.
Not checked in the free run.
Classified as probably not a substantial claim.
Premisecitation§ 1. Introduction · p. 2A multi-louver fin and flat tube heat exchanger is one of the potential alternatives for replacing conventional finned tube heat exchangers.
“A multi-louver fin and flat tube heat exchanger is one of the potential alternatives for replacing conventional finned tube heat exchangers [1].”
Quote in the paperSubstantial claim0 of 1 sources checked- cites [1] Webb RL. Advances in air-cooled heat exchanger technology. In: Proceedings of the International Conference on Heat Exchangers for Sustainable Development, Lisbon, Portugal, 1998. p. 677–92.
Couldn’t be matched to a paper in Crossref, so it can’t be checked.
May combine two claims. The quote only partly states this claim.
Study design and conductcitation§ 2.4. Data reduction · p. 6Accounting for all instrument errors, property uncertainties, and geometric tolerances, the uncertainties for the heat transfer coefficients and pressure drops were 12 and 10%, respectively.
“uncertainties for the heat transfer coefficients and pressure drops were 12 and 10%, respectively [24].”
Quote in the paperNot a substantial claim0 of 1 sources checked- cites [24] Moffat, 1988, Describing the uncertainties in experimental results, Exp. Thermal and Fluid Sci. source
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
All correlations by Chang and co-workers and Kim and Bullard can only correlate less than 67% (as low as 36.56%) of the current experimental data with a deviation of ±25%.
“As can be seen from the previously discussed four correlations, all the correlations by Chang and co-works and Kim and Bullard can only correlate less than 67% (as low as 36.56%) of the current experimental data with a deviation of ± 25%.”
From A heat transfer and friction factor correlation for low air-side Reynolds number applications of compact heat exchangers (1535-RP) (2017) · cites this paper as Kim and Bullard (2002)
Sections 3.1 (p. 9) and 3.2 (pp. 9–10) establish that Kim and Bullard developed heat-transfer and friction-factor correlations. They do not report that the correlations capture less than 67%, or as little as 36.56%, of the citing study’s experimental data within ±25%; those figures appear to be the citing authors’ own comparison. (LLM, conf=0.84)
Experimental — accuracy not yet measuredKim and Bullard presented fluid-flow and heat transfer correlations for dry air using 40 configurations.
“Also, Kim and Bullard [61] presented fluid-flow and heat transfer correlations for dry air using 40 configurations.”
From Compact and microchannel heat exchangers: A comprehensive review of air-side friction factor and heat transfer correlations (2018) · cites this paper as [61]
The heat-transfer correlation section (p. 9) says the j-factor correlation used 225 data points from 45 heat-exchanger configurations, not 40. The pressure-drop correlation section (p. 9) also reports an f-factor correlation. These sections establish air-side heat-transfer and flow-resistance correlations but do not explicitly describe the air as dry. (LLM, conf=0.92)
Experimental — accuracy not yet measured
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
Each contradiction between two passages listed here was confirmed by an independent check.
Type-I tube pitch differs between tables
MinorTable 1 assigns a tube pitch of 11.15 mm to the 16 mm flow-depth exchangers, including the 1.4 mm fin-pitch, 23° louver-angle configuration. Table 2 gives the matching type-I configuration a tube pitch of 10.15 mm.
“| 16 | 1.0, 1.2, 1.4 | 11.15 | 8 | 23, 25, 27, 29 |”
“| I | 23 | 1.4 | 1.7 | 6.4 | 8.15 | 10.15 | 16 | 0.1 |”
Cites
Describing the uncertainties in experimental results
Moffat, R. J. (1988) · Experimental Thermal and Fluid Science · doi:10.1016/0894-1777(88)90043-x · Cited by 9,860 · see citing works
Fundamentals of heat and mass transfer
Larkin, A. V. (2018) · BSU Digital Library (Belarusian State University) · Cited by 8,063 · see citing works
Fundamentals of Heat and Mass Transfer
Incropera, F. P. (1985) · Cited by 3,679 · see citing works
Kays, W. M., London, A. L., & Eckert, E. R. G. (1960) · Journal of Applied Mechanics · doi:10.1115/1.3644004 · Cited by 2,846 · see citing works
(1978) · Cited by 1,056 · see citing works
A generalized heat transfer correlation for Iouver fin geometry
Chang, Y.-J., & Wang, C.-C. (1997) · International Journal of Heat and Mass Transfer · doi:10.1016/0017-9310(96)00116-0 · Cited by 493 · see citing works
Heat transfer and pressure drop characteristics of flat tube and louvered plate fin surfaces
Achaichia, A., & Cowell, T. A. (1988) · Experimental Thermal and Fluid Science · doi:10.1016/0894-1777(88)90032-5 · Cited by 235 · see citing works
Flow structure in the louvered fin heat exchanger geometry
Webb, R. L., & Trauger, P. (1991) · Experimental Thermal and Fluid Science · doi:10.1016/0894-1777(91)90065-y · Cited by 119 · see citing works
Air Side Performance of Brazed Aluminum Heat Exchangers
Chang, Y., & Wang, C. (1996) · Enhanced heat transfer/Journal of enhanced heat transfer · doi:10.1615/jenhheattransf.v3.i1.20 · Cited by 93 · see citing works
Prediction of Heat Transfer and Friction for the Louver Fin Geometry
Sahnoun, A., & Webb, R. L. (1992) · Journal of Heat Transfer · doi:10.1115/1.2911898 · Cited by 69 · see citing works
DeJong, N. C., Zhang, L. W., Jacobi, A. M., Balachandar, S., & Tafti, D. K. (1998) · Journal of Heat Transfer · doi:10.1115/1.2824338 · Cited by 56 · see citing works
An experimental study of the local heat transfer characteristics in automotive louvered fins
Aoki, H., Shinagawa, T., & Suga, K. (1989) · Experimental Thermal and Fluid Science · doi:10.1016/0894-1777(89)90018-6 · Cited by 51 · see citing works
Experimental design for flowfield studies of louvered fins
Springer, M. E., & Thole, K. A. (1998) · Experimental Thermal and Fluid Science · doi:10.1016/s0894-1777(98)10022-5 · Cited by 50 · see citing works
HEAT TRANSFER AND FRICTION CHARACTERISTICS OF CONVEX-LOUVER FIN-AND-TUBE HEAT EXCHANGERS
Wang, C.-C., Chen, P.-Y., & Jang, J. (1996) · Experimental Heat Transfer · doi:10.1080/08916159608946514 · Cited by 36 · see citing works
Tafti, D. K. (1999) · Numerical Heat Transfer Part A Applications · doi:10.1080/104077899275227 · Cited by 34 · see citing works
Heat transfer and flow characteristics of automotive brazed aluminum heat exchangers
Chang, Y. J., Wang, C., & Chang, W.-J. (1994) · ASHRAE winter conference papers · Cited by 31 · see citing works
Huihua, Z., & Xuesheng, L. (1989) · Experimental Thermal and Fluid Science · doi:10.1016/0894-1777(89)90054-x · Cited by 26 · see citing works
Rationally Based Heat Transfer and Friction Correlations for the Louver Fin Geometry
Dillen, E. R., & Webb, R. L. (1994) · SAE technical papers on CD-ROM/SAE technical paper series · doi:10.4271/940504 · Cited by 23 · see citing works
The Flow Structure in the Louvered Fin Heat Exchanger Geometry
Webb, R. L. (1990) · SAE technical papers on CD-ROM/SAE technical paper series · doi:10.4271/900722 · Cited by 22 · see citing works
Development of a Micro-Channel Evaporator Model for a CO2 Mobile Air-Conditioner
Kim, M.-H., Yin, J., Bullard, C. W., & Hrnjak, P. (2000) · Advanced Energy Systems · doi:10.1115/imece2000-1295 · Cited by 6 · see citing works
Self-citation
Flagged first, then by citations
Research works printed but not linked: 8
- Webb RL. Advances in air-cooled heat exchanger technology. In: Proceedings of the International Conference on Heat Exchangers for Sustainable Development, Lisbon, Portugal, 1998. p. 677–92.
- Davenport CJ. Heat transfer and fluid flow in louvered triangular ducts. PhD thesis, Department of Mechanical Engineering, Lanchester Polytechnic, 1980.
- Davenport, 1983, Correlation for heat transfer and friction characteristics of louvered fin, AICHE Sym. Ser., 79, 19
- Achaichia A. The performance of louvered tube-and-plate fin heat transfer surface. PhD thesis, Department of Mechanical and Production Engineering, Brighton Polytechnic, 1987.
- Webb, 1992, Air-side performance of enhanced brazed aluminum heat exchangers, ASHRAE Trans., 98, 391
- Rugh, 1992, A study of a very compact heat exchanger used for passenger compartment heating in automobiles, ASME Symp. Ser. HTD-Vol. 201, 15-24
- Sunden B, Svantesson J. Correlation of j- and f-factors for multilouvered heat transfer surfaces. In: Proceedings of the 3rd UK National Conference on Heat Transfer, 1992. pp. 805-11.
- Rich, 1973, The effect of fin spacing of the heat transfer and friction performance of multi-row, smooth plate fin-and-tube heat exchangers, ASHRAE Trans., 79, 137
Cited by
Sorted by citations
Fundamental process and system design issues in CO2 vapor compression systems
Kim, M.-H. (2003) · Progress in Energy and Combustion Science · doi:10.1016/j.pecs.2003.09.002 · Cited by 733 · see citing works
“The heat transfer coefficients and the pressure drops for the wet conditions revealed the importance of the role of condensate drainage [119].”
BackgroundSelf-citationHeat transfer enhancement in fin-and-tube heat exchangers – A review on different mechanisms
Sadeghianjahromi, A., & Wang, C.-C. (2021) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2020.110470 · Cited by 240 · see citing works
Heat transfer and pressure drop correlations for the multi-louvered fin compact heat exchangers
Dong, J., Chen, J., Chen, Z., Zhang, W., & Zhou, Y. (2007) · Energy Conversion and Management · doi:10.1016/j.enconman.2006.11.023 · Cited by 173 · see citing works
Qasem, N. A. A., & Zubair, S. M. (2018) · Energy Conversion and Management · doi:10.1016/j.enconman.2018.06.104 · Cited by 135 · see citing works
Lei, Y., He, Y., Tian, L.-T., Chu, P., & Tao, W. (2009) · Chemical Engineering Science · doi:10.1016/j.ces.2009.10.017 · Cited by 117 · see citing works
Air-side performance of brazed aluminum heat exchangers under dehumidifying conditions
Kim, M.-H., & Bullard, C. W. (2002) · International Journal of Refrigeration · doi:10.1016/s0140-7007(01)00106-2 · Cited by 116 · see citing works
Self-citationShao, L.-L., Yang, L., & Zhang, C.-L. (2010) · Applied Energy · doi:10.1016/j.apenergy.2009.08.021 · Cited by 112 · see citing works
Yue, C., Zhang, Q., Zhai, Z. J., & Ling, L. (2018) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2018.01.011 · Cited by 103 · see citing works
Achieving near-water-cooled power plant performance with air-cooled condensers
Bustamante, J. G., Rattner, A. S., & Garimella, S. (2015) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2015.05.065 · Cited by 103 · see citing works
Thermal-hydraulic CFD study in louvered fin-and-flat-tube heat exchangers
Perrotin, T., & Clodic, D. (2004) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2003.11.005 · Cited by 97 · see citing works
Experimental and numerical investigation on a CO2 loop thermosyphon for free cooling of data centers
Zhang, H., Shi, Z., Liu, K., Shao, S., Jin, T., & Tian, C. (2016) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.10.029 · Cited by 88 · see citing works
Parametric study on the performance of a heat exchanger with corrugated louvered fins
Qi, Z., Chen, J., & Zhi-jiu, C. (2006) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2006.06.015 · Cited by 86 · see citing works
Flow and heat transfer enhancement in tube heat exchangers
Ahmed, S. E. S. S., Mesalhy, O., & Abdelatief, M. A. (2015) · Heat and Mass Transfer · doi:10.1007/s00231-015-1669-1
Ling, L., Zhang, Q., Yu, Y., Liao, S., & Sha, Z. (2016) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.03.016 · Cited by 82 · see citing works
“According to Kim and Bullard [25] correlations, the air side heat transfer coefficient in Mode 1 and Mode 2 were 109.9 W/(m2 K) and 82.9 W/ (m2 K), respectively.”
MethodInfluentialBacellar, D., Aute, V., Huang, Z., & Radermacher, R. (2017) · Science and Technology for the Built Environment · doi:10.1080/23744731.2017.1333877 · Cited by 82 · see citing works
Air-Side Heat Transfer and Friction Correlations for Flat-Tube Louver-Fin Heat Exchangers
Park, Y.-G., & Jacobi, A. M. (2009) · Journal of Heat Transfer · doi:10.1115/1.3000609 · Cited by 80 · see citing works
Numerical investigation of fluid flow and heat transfer over louvered fins in compact heat exchanger
Malapure, V. P., Mitra, S., & Bhattacharya, A. (2007) · International Journal of Thermal Sciences · doi:10.1016/j.ijthermalsci.2006.04.010 · Cited by 85 · see citing works
Development of a microchannel evaporator model for a CO2 air-conditioning system
Kim, M.-H., & Bullard, C. W. (2001) · Energy · doi:10.1016/s0360-5442(01)00042-1 · Cited by 78 · see citing works
Self-citationLiu, Y., Yang, X., Li, J., & Zhao, X. (2018) · Energy · doi:10.1016/j.energy.2018.07.172 · Cited by 76 · see citing works
“The air side heat transfer coef fi cient, h a,c , is given by the correlation proposed by Kim and Bullard [27]. where the Colburn j -factor is calculated as: The Fanning friction factor is given by, where Re Lp is the air-side Reynolds number based on the louver pitch and is calculated as: The air…”
MethodLing, L., Zhang, Q., Yu, Y., Wu, Y., & Liao, S. (2015) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2015.08.006 · Cited by 70 · see citing works
Park, Y.-G., & Jacobi, A. M. (2009) · Journal of Heat Transfer · doi:10.1115/1.3089548 · Cited by 70 · see citing works
Mao, J.-N., Chen, H.-X., Jia, H., Wang, Y.-J., & Hu, H.-T. (2013) · International Journal of Thermal Sciences · doi:10.1016/j.ijthermalsci.2013.06.001 · Cited by 72 · see citing works
Okbaz, A., Pınarbaşı, A., & Olcay, A. (2020) · International journal of thermal sciences · doi:10.1016/j.ijthermalsci.2019.106256 · Cited by 67 · see citing works
Modelling refrigerant distribution in microchannel evaporators
Markussen, W. B., Kærn, M. R., & Elmegaard, B. (2009) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2009.05.006 · Cited by 65 · see citing works
“Air side Heat transfer coefficient Kim and Bullard (2002) Two-phase region Heat transfer coefficient Zhang et al. (2004) þ smooth transition to single phase Void fraction Homogeneous model i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 2 ( 2 0 0 9 ) 1 7 3 6 – 1 7 4 3…”
InfluentialLi, W., & Wang, X. (2010) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2010.04.002 · Cited by 65 · see citing works
Li, X., Wang, N., Wang, L., Kantor, I. D., Robineau, J.-L., Yang, Y., & Marechal, F. M. A. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2017.10.103 · Cited by 62 · see citing works
Zhang, H., Shao, S., Xu, H., Zou, H., Tang, M., & Tian, C. (2015) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2015.08.014 · Cited by 61 · see citing works
Yue, C., Zhang, Q., Zhai, Z. J., & Ling, L. (2018) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2018.10.025 · Cited by 61 · see citing works
Okbaz, A., Pınarbaşı, A., Olcay, A. B., & Aksoy, M. H. (2018) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2017.12.127 · Cited by 59 · see citing works
Zhan, F., Tang, J., Ding, G., & Zhuang, D. (2016) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.01.136 · Cited by 59 · see citing works
Wu, Z., & Du, R. (2010) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2010.09.030 · Cited by 55 · see citing works
Sadeghianjahromi, A., Kheradmand, S., & Nemati, H. (2018) · International journal of thermal sciences · doi:10.1016/j.ijthermalsci.2018.03.002 · Cited by 57 · see citing works
Kim, M.-H., Youn, B., & Bullard, C. W. (2001) · International Journal of Heat and Mass Transfer · doi:10.1016/s0017-9310(01)00104-1 · Cited by 52 · see citing works
Self-citationZhang, H., Shao, S., Xu, H., Zou, H., Tang, M., & Tian, C. (2016) · Applied Energy · doi:10.1016/j.apenergy.2016.01.053 · Cited by 50 · see citing works
Sun, X., Ling, L., Liao, S., Chu, Y., Fan, S., & Mo, Y. (2017) · Energy Conversion and Management · doi:10.1016/j.enconman.2017.10.068 · Cited by 50 · see citing works
Performance comparison of air-source heat pump water heater with different expansion devices
Peng, J.-W., Li, H., & Zhang, C. (2016) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.01.113 · Cited by 49 · see citing works
Li, J., Jia, J., Huang, L., & Wang, S. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.12.140 · Cited by 49 · see citing works
Performance evaluation of a window room air conditioner with microchannel condensers
Kim, M.-H., & Bullard, C. W. (2002) · Journal of Energy Resources Technology · doi:10.1115/1.1446072 · Cited by 48 · see citing works
Self-citationZhang, H., Shao, S., Jin, T., & Tian, C. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.12.135 · Cited by 48 · see citing works
Sok, R., & Kusaka, J. (2022) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2022.123718 · Cited by 47 · see citing works
Sok, R., & Kusaka, J. (2022) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2022.119530 · Cited by 46 · see citing works
Liang, Y. Y., Liu, C. C., Li, C. Z., & Chen, J. P. (2015) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2015.05.018 · Cited by 45 · see citing works
Saleem, A., & Kim, M.-H. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2017.07.082 · Cited by 45 · see citing works
Self-citationMicrochannel Heat Exchanger Design for Evaporator and Condenser Applications
Kim, M.-H., Lee, S.-Y., Mehendale, S., & Webb, R. (2003) · Advances in heat transfer · doi:10.1016/s0065-2717(03)37004-2 · Cited by 45 · see citing works
Self-citationDoğan, B., Altun, Ö., Uğurlubilek, N., Tosun, M., Sarıçay, T., & Erbay, L. B. (2015) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2015.07.059 · Cited by 44 · see citing works
Modelling distribution of evaporating CO2 in parallel minichannels
Markussen, W. B., Kærn, M. R., & Elmegaard, B. (2010) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2010.04.012 · Cited by 44 · see citing works
Energy-Optimal Control of an Automotive Air Conditioning System for Ancillary Load Reduction
Zhang, Q., Stockar, S., & Canova, M. (2016) · IEEE Transactions on Control Systems Technology · doi:10.1109/tcst.2015.2418322 · Cited by 42 · see citing works
“The correlations to calculate the heat transfer coefficients adopted in this paper are specific to cross-flow compact heat exchangers with louvers and fins, and have been proposed in [25] and [26].”
MethodNumerical modeling of serpentine microchannel condensers
Shao, L.-L., Yang, L., Zhang, C., & Gu, B. Q. (2009) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2009.02.007 · Cited by 42 · see citing works
Improving air-side heat transfer performance in air-cooled power plant condensers
Lin, J., Mahvi, A. J., Kunke, T. S., & Garimella, S. (2020) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2020.114913 · Cited by 42 · see citing works
Heat transfer—a review of 2002 literature
Goldstein, R. J., Eckert, E. R. G., Ibele, W. E., Patankar, S. V., Simon, T. W., Kuehn, T. H., Strykowski, P. J., Tamma, K. K., Bar‐Cohen, A., Heberlein, J. V. R., et al. (2005) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2004.10.011 · Cited by 42 · see citing works
“Additional papers discuss circular tubes with internal longitudinal fins with tapered lateral profiles and aspects of multi-louvered fin geometry [1527–1530].”
BackgroundKo, Y.-M., Song, J., Lee, J. W., Sohn, S., Song, C.-H., Khoshvaght-Aliabadi, M., Kim, Y., & Kang, Y. T. (2024) · Energy · doi:10.1016/j.energy.2023.129609 · Cited by 37 · see citing works
Generalized heat-transfer and fluid-flow correlations for corrugated louvered fins
Ryu, K., & Lee, K.-S. (2015) · International Journal of Heat and Mass Transfer · doi:10.1016/j.ijheatmasstransfer.2014.12.044 · Cited by 46 · see citing works
Zhou, K. X., Miljkovic, N., & Cai, L. (2021) · Energy and Buildings · doi:10.1016/j.enbuild.2021.110749 · Cited by 41 · see citing works
Kim, M.-H., Song, S., & Bullard, C. W. (2002) · International Journal of Refrigeration · doi:10.1016/s0140-7007(01)00061-5 · Cited by 39 · see citing works
Self-citationKim, Y. J., Jeong, M., Park, Y. G., & Ha, M. Y. (2018) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2018.03.019 · Cited by 39 · see citing works
Simulation of a micro channel separate heat pipe (MCSHP) under low heat flux and low mass flux
Ling, L., Zhang, Q., Yu, Y., Wu, Y., Liao, S., & Sha, Z. (2017) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2017.03.049 · Cited by 38 · see citing works
Saleem, A., & Kim, M.-H. (2017) · Energies · doi:10.3390/en10060823 · Cited by 38 · see citing works
Self-citationRibeiro, F. H. E., de Conde, K. E., Garcia, É. C., & Nascimento, I. P. (2020) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2020.115188 · Cited by 38 · see citing works
Experimentally Validated Model of Refrigerant Distribution in a Parallel Microchannel Evaporator
Tuo, H., Bielskus, A., & Hrnjak, P. (2012) · SAE International Journal of Materials and Manufacturing · doi:10.4271/2012-01-0321 · Cited by 37 · see citing works
Erbay, L. B., Uğurlubilek, N., Altun, Ö., & Doğan, B. (2016) · Heat Transfer Engineering · doi:10.1080/01457632.2016.1200382 · Cited by 36 · see citing works
“the numerical results of Perrotin and Clodic [37] and the experimental results of Kim and Bullard [10].”
BackgroundMethodResultInfluentialBahman, A. M., Ziviani, D., & Groll, E. A. (2018) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2018.07.024 · Cited by 35 · see citing works
Numerical study on air-side performance of an integrated fin and micro-channel heat exchanger
Li, J., Wang, S., Cai, W., & Zhang, W. (2010) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2010.07.028 · Cited by 34 · see citing works
Martínez-Ballester, S., Corberán, J. M., & Gonzálvez-Maciá, J. (2012) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2012.08.023 · Cited by 33 · see citing works
“The correlation used for the air-side heat transfer coefficient (Kim and Bullard, 2002) reported rms errors of Table 2 e Geometric characteristics of the condensers used for the model validation (Garcı́a-Cascales et al., 2010).”
BackgroundMethodJeong, C., Kim, H., Ha, M., Son, S., Lee, J., & Kim, P. Y. (2014) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2013.09.044 · Cited by 36 · see citing works
Shojaeefard, . H., & Zare, J. (2016) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.04.093 · Cited by 32 · see citing works
Performance analysis of an electric vehicle heat pump system with a desiccant dehumidifier
Na, S.-I., Chung, Y., & Kim, M. S. (2021) · Energy Conversion and Management · doi:10.1016/j.enconman.2021.114083 · Cited by 32 · see citing works
Self-citationOptimal design of a corrugated louvered fin
Ryu, K., Yook, S., & Lee, K.-S. (2014) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2014.04.022 · Cited by 31 · see citing works
Dezan, D. J., Yanagihara, J. I., Jenovencio, G., & Salviano, L. (2018) · International Journal of Thermal Sciences · doi:10.1016/j.ijthermalsci.2018.09.039 · Cited by 30 · see citing works
Wang, D., Wang, Y., Yu, B., Shi, J., & Chen, J. (2019) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2019.02.023 · Cited by 30 · see citing works
Ayad, F., Benelmir, R., & Idris, M. (2021) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2020.116218 · Cited by 30 · see citing works
Development and validation of a microchannel evaporator model for a CO 2 air-conditioning system
Jin, J., Chen, J., & Chen, Z. (2011) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2010.06.019 · Cited by 30 · see citing works
PADHMANABHAN, S., CREMASCHI, L., & FISHER, D. (2011) · International Journal of Air-Conditioning and Refrigeration · doi:10.1142/s2010132511000600 · Cited by 29 · see citing works
Optimization of fin geometry in heat convection with entransy theory
Cheng, X., Zhang, Q., Xu, X., & Liang, X. (2013) · Chinese Physics B · doi:10.1088/1674-1056/22/2/020503 · Cited by 29 · see citing works
Performance Analysis of an Automotive Heat Pump System with Desiccant Coated Heat Exchangers
Na, S.-I., Kim, M., & Kim, M. S. (2022) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2022.118723 · Cited by 29 · see citing works
Self-citationZhang, F., Bock, J., Jacobi, A. M., & Wu, H. (2013) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2013.11.046 · Cited by 29 · see citing works
Reshaeel, M., Abdelsamie, M. M., & Ali, M. I. H. (2024) · International Journal of Thermofluids · doi:10.1016/j.ijft.2024.100858 · Cited by 19 · see citing works
Air-side performance of louver-finned flat aluminum heat exchangers at a low velocity region
Kim, N.-H., & Cho, J.-P. (2007) · Heat and Mass Transfer · doi:10.1007/s00231-007-0346-4 · Cited by 28 · see citing works
Dezan, D. J., Salviano, L., & Yanagihara, J. I. (2015) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2015.08.072 · Cited by 28 · see citing works
Yan, Z., Oon, C. S., Tan, B. T., & Ooi, J. B. (2025) · Results in Engineering · doi:10.1016/j.rineng.2025.106227 · Cited by 27 · see citing works
Evaluation of microchannel condenser characteristics by numerical simulation
Yin, X.-W., Wang, W., Patnaik, V., Zhou, J.-S., & Huang, X.-C. (2015) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2015.03.006 · Cited by 27 · see citing works
Numerical model of a two-phase microchannel heat sink electronics cooling system
Saenen, T., & Baelmans, M. (2012) · International Journal of Thermal Sciences · doi:10.1016/j.ijthermalsci.2012.04.018 · Cited by 27 · see citing works
“From [27] Eqs.”
MethodInfluentialSegarra, C. D. P., Oliet, C., & Oliva, A. (2008) · Heat Transfer Engineering · doi:10.1080/01457630701851107 · Cited by 27 · see citing works
Mukkamala, Y. S. (2017) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2017.03.106 · Cited by 27 · see citing works
Modeling air conditioning system with storage evaporator for vehicle energy management
Zhang, Q., & Canova, M. (2015) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2015.05.003 · Cited by 27 · see citing works
“The correlations to calculate the heat transfer coefficients adopted in this work are specific to cross-flow compact heat exchangers with louvers and fins, and have been proposed by Chang and Wang [26] and Kim and Bullard [27].”
MethodXiong, T., Liu, G., Gao, Q., Yan, G., & Yu, J. (2023) · Journal of Building Engineering · doi:10.1016/j.jobe.2022.105654 · Cited by 26 · see citing works
Kim, Y. J., & Ha, M. Y. (2017) · Journal of Mechanical Science and Technology · doi:10.1007/s12206-017-0622-2 · Cited by 26 · see citing works
Dezan, D. J., Salviano, L., & Yanagihara, J. I. (2016) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2015.12.107 · Cited by 25 · see citing works
Başaran, A., & Yurddaş, A. (2021) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2021.117446 · Cited by 24 · see citing works
Lee, S.-W., Chung, Y., Kim, S.-J., Jeong, Y., & Kim, M. S. (2022) · Energy Conversion and Management · doi:10.1016/j.enconman.2022.115265 · Cited by 24 · see citing works
Self-citationYuan, W., Yang, B., Yang, Y., Ren, K., Xu, J. G., & Liao, Y. (2015) · Applied Energy · doi:10.1016/j.apenergy.2015.01.001 · Cited by 24 · see citing works
Gunnasegaran, P., Shuaib, N. H., & Jalal, M. (2012) · ISRN Thermodynamics · doi:10.5402/2012/832708 · Cited by 23 · see citing works
“Kim and Bullard [9] studied experimentally the air-side thermal and hydraulic performance of multi-louvered fin aluminum heat exchangers.”
Optimum louver angle design for a louvered fin heat exchanger
Jang, J.-Y. (2011) · International Journal of the Physical Sciences · doi:10.5897/ijps11.475 · Cited by 23 · see citing works
Shojaeefard, . H., Nourbakhsh, S. D., & Zare, J. (2016) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2016.10.009 · Cited by 23 · see citing works
Critical Assessment of R410A Alternatives for Mini-split Air Conditioners in the Egyptian Market
Zaki, O. M., & Abdelaziz, O. Y. (2023) · Energy and Built Environment · doi:10.1016/j.enbenv.2023.01.003 · Cited by 19 · see citing works
Li, F., Shi, K., Sun, X., Yue, B., Huang, D., Zhao, R., & Zhao, Y. (2024) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2024.03.011 · Cited by 22 · see citing works
Boeng, J., Rametta, R. S., de Melo, C. M. R., & Hermes, C. J. L. (2020) · Thermal Science and Engineering Progress · doi:10.1016/j.tsep.2020.100479 · Cited by 22 · see citing works
Modeling of a fan-supplied flat-tube heat exchanger exposed to non-uniform frost growth
Breque, F., & Nemer, M. (2017) · International Journal of Refrigeration · doi:10.1016/j.ijrefrig.2016.12.012 · Cited by 21 · see citing works
Elibol, E. A. (2024) · Applied Thermal Engineering · doi:10.1016/j.applthermaleng.2024.124892 · Cited by 21 · see citing works
Comparison of Additively Manufactured Louvered Plate-Fin Heat Exchangers
Bichnevicius, M., Saltzman, D., & Lynch, S. (2020) · Journal of Thermal Science and Engineering Apllications · doi:10.1115/1.4044348 · Cited by 19 · see citing works
“Ryu et al. [20] found a more effective louver shape relative to a baseline from Kim and Bullard [7] and modified the Suga-Aoki equation [21] for optimal louver design to expand its ReLp range.”
MethodInfluentialComprehensive Study of Heat Exchangers with Louvered Fins
Erbay, L. B., Doğan, B., & Öztürk, M. M. (2017) · InTech eBooks · doi:10.5772/66472 · Cited by 21 · see citing works
- Authors
- Kim, M.-H., & Bullard, C. W.
- Affiliations
- University of Illinois Urbana-Champaign (US)
- Corresponding author
- Kim, Man-Hoe
- ORCID
- Kim, Man-Hoe
- Venue
- International Journal of Refrigeration
- Publisher
- Elsevier BV
- Published
- 2002-05
- Volume
- 25
- Issue
- 3
- Pages
- 390-400
- ISSN
- 0140-7007 (ISSN-L)
- OpenAlex
- W2066694433
- Semantic Scholar
- 49cfbe56084c4f5d7d84db303ee3d9a6eff9b535
- Cited by
- 280
- References
- 21
- Citations by year
- 2026: 12 · 2025: 21 · 2024: 14 · 2023: 17 · 2022: 15 · 2021: 14 · 2020: 17 · 2019: 14 · 2018: 17 · 2017: 26 · 2016: 21 · 2015: 20 · 2014: 3 · 2013: 6 · 2012: 12
- FWCI
- 10.64
- Type
- journal article
- Language
- en
- Open access
- closed
- Locations
- International Journal of Refrigeration (publishedVersion)
- Topics
- Physical Sciences › Engineering › Mechanical Engineering › Heat Transfer and Optimization
- Physical Sciences › Engineering › Mechanical Engineering › Heat Transfer Mechanisms
- Physical Sciences › Engineering › Computational Mechanics › Heat transfer and supercritical fluids
- Keywords
- louvered fin heat exchanger, aluminum heat exchangers, air-side heat transfer, pressure drop, fin angle, fin spacing, flow depth, Colburn j-factor, Fanning friction factor, heat transfer coefficient, cross-flow heat exchanger, effectiveness-NTU method, flat tube heat exchanger, air-to-water heat exchanger
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Claims read by deepseek-v4.1-flash under definition version 3 (extract-v3) on 2026-11-05.
Classified by jev-1.13-20260917 (gold-guideline-v0.2) on 2026-11-05.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review