United States Data Center Energy Usage Report
Open accessAbstract
This report estimates historical data center electricity consumption back to 2000, relying on previous studies and historical shipment data, and forecasts consumption out to 2020 based on new trends and the most recent data available. Figure ES-1 provides an estimate of total U.S. data center electricity use (servers, storage, network equipment, and infrastructure) from 2000-2020. In 2014, data centers in the U.S. consumed an estimated 70 billion kWh, representing about 1.8% of total U.S. electricity consumption. Current study results show data center electricity consumption increased by about 4% from 2010-2014, a large shift from the 24% percent increase estimated from 2005-2010 and the nearly 90% increase estimated from 2000-2005. Energy use is expected to continue slightly increasing in the near future, increasing 4% from 2014-2020, the same rate as the past five years. Based on current trend estimates, U.S. data centers are projected to consume approximately 73 billion kWh in 2020.
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Integrity signals
Registry
Cites
Statistics
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Run the check — free, no account needed. It reads the open-access text and checks the sources it cites.
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
The report estimates nearly 211 billion gallons of indirect water use in 2023.
“the report estimates nearly 211 billion gallons of indirect water use in 2023”
From Navigating Environmental Concerns Confronting U.S. Data Centers Related to Water Quantity and Quality (2026) · cites this paper as [4]
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Cites
Energy efficiency and consumption—The rebound effect—A survey
A. Greening, L., Greene, D. L., & Difiglio, C. (2000) · Energy Policy · doi:10.1016/s0301-4215(00)00021-5 · Cited by 2,077 · see citing works
Worldwide electricity used in data centers
Koomey, J. (2008) · Environmental Research Letters · doi:10.1088/1748-9326/3/3/034008 · Cited by 977 · see citing works
Self-citation(2010) · doi:10.5555/1855711.1855728 · Cited by 970 · see citing works
The Rebound Effect and Energy Efficiency Policy
Gillingham, K., Rapson, D., & Wagner, G. (2016) · Review of Environmental Economics and Policy · doi:10.1093/reep/rev017 · Cited by 672 · see citing works
Trends in worldwide ICT electricity consumption from 2007 to 2012
Van Heddeghem, W., Lambert, S., Lannoo, B., Colle, D., Pickavet, M., & Demeester, P. (2014) · Computer Communications · doi:10.1016/j.comcom.2014.02.008 · Cited by 533 · see citing works
Implications of Historical Trends in the Electrical Efficiency of Computing
Koomey, J., Berard, S., Sanchez, M., & Wong, H. (2011) · IEEE Annals of the History of Computing · doi:10.1109/mahc.2010.28 · Cited by 513 · see citing works
Self-citationLo, D., Cheng, L., Govindaraju, R., Ranganathan, P., & Kozyrakis, C. (2015) · Proceedings - International Symposium on Computer Architecture/Proceedings · doi:10.1145/2749469.2749475 · Cited by 469 · see citing works
Hilty, L. M., Arnfalk, P., Erdmann, L., Goodman, J., Lehmann, M., & Wäger, P. A. (2006) · Environmental Modelling & Software · doi:10.1016/j.envsoft.2006.05.007 · Cited by 388 · see citing works
De-materialising and re-materialising: Digital technologies and the environment
Berkhout, F., & Hertin, J. (2004) · Futures · doi:10.1016/j.futures.2004.01.003 · Cited by 373 · see citing works
Environmental effects of information and communications technologies
Williams, E. (2011) · Nature · doi:10.1038/nature10682 · Cited by 304 · see citing works
Consumptive Water Use for U.S. Power Production
Torcellini, P., Long, N. L., & Judkoff, R. (2003) · doi:10.2172/15005918 · Cited by 215 · see citing works
Best Practices for Data Centers: Lessons Learned from Benchmarking 22 Data Centers
Greenberg, S., Mills, E., Tschudi, B., & Rumsey, P. (2006) · Cited by 214 · see citing works
Plepys, A. (2002) · Environmental Impact Assessment Review · doi:10.1016/s0195-9255(02)00025-2 · Cited by 201 · see citing works
Erdmann, L., & Hilty, L. M. (2010) · Journal of Industrial Ecology · doi:10.1111/j.1530-9290.2010.00277.x · Cited by 183 · see citing works
Known unknowns: Indirect energy effects of information and communication technology
Horner, N. C., Shehabi, A., & Azevedo, I. L. (2016) · Environmental Research Letters · doi:10.1088/1748-9326/11/10/103001 · Cited by 177 · see citing works
Self-citationA review of research on the environmental impact of e-business and ICT
Yi, L., & Thomas, H. R. (2007) · Environment International · doi:10.1016/j.envint.2007.03.015 · Cited by 154 · see citing works
Consumer End-Use Energy Efficiency and Rebound Effects
Azevedo, I. M. L. (2014) · Annual Review of Environment and Resources · doi:10.1146/annurev-environ-021913-153558 · Cited by 144 · see citing works
Self-citationShipping news: the implications of electronic commerce for logistics and freight transport
Heße, M. (2002) · Resources Conservation and Recycling · doi:10.1016/s0921-3449(02)00083-6 · Cited by 142 · see citing works
Including second order effects in environmental assessments of ICT
Börjesson Rivera, M., Håkansson, C., Svenfelt, Å., & Finnveden, G. (2014) · Environmental Modelling & Software · doi:10.1016/j.envsoft.2014.02.005 · Cited by 117 · see citing works
Smart Everything: Will Intelligent Systems Reduce Resource Use?
Koomey, J., Matthews, H. S., & Williams, E. (2013) · Annual Review of Environment and Resources · doi:10.1146/annurev-environ-021512-110549 · Cited by 97 · see citing works
Self-citationEstimating the Energy Use and Efficiency Potential of U.S. Data Centers
Masanet, E. R., Brown, R. E., Shehabi, A., Koomey, J. G., & Nordman, B. (2011) · Proceedings of the IEEE · doi:10.1109/jproc.2011.2155610 · Cited by 87 · see citing works
Self-citationBurst Transmission in Energy Efficient Ethernet
Reviriego, P., Hernadez, J.-A., Larrabeiti, D., & Maestro, J. A. (2010) · IEEE Internet Computing · doi:10.1109/mic.2010.52 · Cited by 86 · see citing works
Data network equipment energy use and savings potential in buildings
Lanzisera, S., Nordman, B., & Brown, R. E. (2011) · Energy Efficiency · doi:10.1007/s12053-011-9136-4 · Cited by 69 · see citing works
Self-citationAn Analysis of Hard Drive Energy Consumption
Hylick, A., Sohan, R., Rice, A. C., & Jones, B. (2008) · Proceedings - International Symposium on Modeling, Analysis, and Simulation of Computer and Telecommunication Systems · doi:10.1109/mascot.2008.4770567 · Cited by 63 · see citing works
The energy and greenhouse-gas implications of internet video streaming in the United States
Shehabi, A., Walker, B., & Masanet, E. (2014) · Environmental Research Letters · doi:10.1088/1748-9326/9/5/054007 · Cited by 63 · see citing works
Self-citationThe Energy Efficiency Potential of Cloud-Based Software: A U.S. Case Study
Masanet, E. R., Shehabi, A., Liang, J., Ramakrishnan, L., Ma, X., Hendrix, V., Walker, B., & Mantha, P. K. (2013) · doi:10.2172/1171159 · Cited by 60 · see citing works
Self-citationExternal air pollution costs of telework
Kitou, E., & Horvath, A. (2007) · The International Journal of Life Cycle Assessment · doi:10.1065/lca2007.06.338 · Cited by 58 · see citing works
Power usage effectiveness in data centers: overloaded and underachieving
Horner, N., & Azevedo, I. L. (2016) · The Electricity Journal · doi:10.1016/j.tej.2016.04.011 · Cited by 51 · see citing works
Self-citationElectricity Requirements for a Digital Society
Baer, W. S., Hassell, S., & Vollaard, B. (2002) · RAND Corporation eBooks · doi:10.7249/mr1617 · Cited by 41 · see citing works
High-performance data centers: A research roadmap
Tschudi, W., Xu, T. T., Sartor, D., & Stein, J. (2004) · doi:10.2172/838173 · Cited by 34 · see citing works
Self-citationICT as Key Technology against Global Warming
Auweter, A., Tjoa, A. M., Tahamtan, A., et al. (2012) · Lecture notes in computer science · doi:10.1007/978-3-642-32606-6 · Cited by 8 · see citing works
Energy‐Efficient Networking in Modern Data Centers
Dudkowski, D., & Hasselmeyer, P. (2015) · doi:10.1002/9781118759257.ch16 · Cited by 3 · see citing works
Flagged first, then by citations
Research works printed but not linked: 12
- Koomey, J.G. (2011). Growth in Data Center Electricity Use 2005 to 2010. Analytics Press, Oakland, California. http://www.analyticspress.com/datacenters.html
- IDC Worldwide Quarterly Server Tracker: http://www.idc.com/tracker/showproductinfo.jsp?prod_id=7 8 International Data Corporation (IDC). 2015. IDC's Worldwide Quarterly Server Shipment Tracker, 2010-2018, Framingham, MA, March.
- International Data Corporation (IDC). 2015. IDC's Worldwide Quarterly Disk Storage Systems Tracker, 2010-2019, Framingham, MA, March.
- International Data Corporation (IDC). 2015. IDC's Worldwide Quarterly Data Center Networks, 2008-2019, Framingham, MA, March.
- International Data Corporation (IDC). 2014. IDC's Worldwide Quarterly Server Tracker - Installed Base, 2006-2018. Framingham, MA: IDC. December.
- C. Malone and C. Belady. Metrics to characterize datacenter & IT equipment energy use. In Proceedings of the Digital Power Forum, Richardson, TX, September 2006.
- Cheung, I. H., Greenberg, S., Mahdavi, R., Brown, R., & Tschudi, W. (2014, August). Energy Efficiency in Small Server Rooms: Field Surveys and Findings. Proceedings the 2014 ACEEE Summer Study on Energy Efficiency in Buildings. LBNL-6952E 38 Google 2015. "Our energy-saving data centers." Accessed December 2, 2015. http://www.google.com/about/datacenters/efficiency/internal/index.html#measuring-efficiency 39
- Koomey, Jonathan, and Samuel Naffziger. 2015. "Efficiency's brief reprieve: Moore's Law slowdown hits performance more than energy efficiency." In IEEE Spectrum. April. pp. [http://spectrum.ieee.org/computing/hardware/moores-law-might-be-slowing-down-but-not-energy- efficiency]
- Lo, D., Cheng, L., Govindaraju, R., Ranganathan, P., & Kozyrakis, C. (2015, June). Heracles: improving resource efficiency at scale. In Proceedings of the 42nd Annual International Symposium on Computer Architecture (pp. 450-462). ACM.
- Hilty, L.M., Aebischer, B. (Eds.), 2015. ICT Innovations for Sustainability, Advances in Intelligent Systems and Computing. Springer International Publishing, Cham.
- Masanet, E.R., Matthews, H.S. (Eds.), 2010. Environmental Applications of Information and Communication Technology [special issue]. J. Ind. Ecol. 14, 685-862.
- Rejeski, D. (Ed.), 2002. E-Commerce, the Internet, and the Environment [special issue]. J. Ind. Ecol. 6, 1-161.
Cited by
Sorted by citations
Recalibrating global data center energy-use estimates
Masanet, E., Shehabi, A., Lei, N., Smith, S., & Koomey, J. (2020) · Science · doi:10.1126/science.aba3758 · Cited by 1,545 · see citing works
“In a series of reports starting in 2016, Lawrence Berkeley National Laboratory has published energy trend analyses of servers, storage devices, and network devices commonly used within data centers (8, 11, 13).”
BackgroundInfluentialSelf-citationDigitalization and energy consumption. Does ICT reduce energy demand?
Lange, S., Pohl, J., & Santarius, T. (2020) · Ecological Economics · doi:10.1016/j.ecolecon.2020.106760 · Cited by 1,224 · see citing works
“Data centers have also experienced fast increases in energy efficiency (Avgerinou et al., 2017; Hintemann and Clausen, 2014; Shehabi et al., 2016).”
BackgroundHow to stop data centres from gobbling up the world’s electricity
Jones, N. (2018) · Nature · doi:10.1038/d41586-018-06610-y · Cited by 1,166 · see citing works
Co-designing electronics with microfluidics for more sustainable cooling
van Erp, R., Soleimanzadeh, R., Nela, L., Kampitsis, G. E., & Matioli, E. (2020) · Nature · doi:10.1038/s41586-020-2666-1 · Cited by 1,154 · see citing works
“Consequently, cooling has an increasingly large 4 environmental impact [7], [8], and new technologies are needed to efficiently handle the 5 heat in a sustainable and cost-effective way [9].”
BackgroundAssessing ICT global emissions footprint: Trends to 2040 & recommendations
Belkhir, L., & Elmeligi, A. (2018) · Journal of Cleaner Production · doi:10.1016/j.jclepro.2017.12.239 · Cited by 970 · see citing works
“On the other hand, another estimation by the US Department of Energy done in 2016 found that US data centers consumed an estimated 70 TWh in 2014, representing 1.8% of total US electricity consumption (U.S. Department of Energy, 2016) (Shehabi et al., 2016).”
MethodInfluentialDwivedi, Y. K., Hughes, L., Kar, A. K., Baabdullah, A. M., Grover, P., Abbas, R., Andreini, D., Abumoghli, I., Barlette, Y., Bunker, D., et al. (2022) · International Journal of Information Management · doi:10.1016/j.ijinfomgt.2021.102456 · Cited by 761 · see citing works
“The United States Data Center Energy Usage Report (Shehabi et al., 2016) indicates that data centers in the U.S. alone likely consumed approximately 73 billion kWh in 2020.”
BackgroundExperimental observation of high thermal conductivity in boron arsenide
Kang, J. S., Li, M., Wu, H. Y., Nguyen, H., & Hu, Y. (2018) · Science · doi:10.1126/science.aat5522 · Cited by 648 · see citing works
Green Algorithms: Quantifying the Carbon Footprint of Computation
Lannelongue, L., Grealey, J., & Inouye, M. (2021) · Advanced Science · doi:10.1002/advs.202100707 · Cited by 604 · see citing works
Fei, C., Lee, F. C., & Li, Q. (2017) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2017.2674599 · Cited by 511 · see citing works
Aligning artificial intelligence with climate change mitigation
Kaack, L. H., Donti, P. L., Strubell, E., Kamiya, G., Creutzig, F., & Rolnick, D. (2022) · Nature Climate Change · doi:10.1038/s41558-022-01377-7 · Cited by 570 · see citing works
“NAtuRE CLImAtE CHANGE | www.nature.com/natureclimatechange centres towards large cloud and hyperscale data centres 23,67 , which have higher virtualization, more efficient cooling and increased use of specialized ‘AI accelerator’ hardware such as application-specific integrated circuits (ASICs) and…”
Usage impact on data center electricity needs: A system dynamic forecasting model
Koot, M., & Wijnhoven, F. (2021) · Applied Energy · doi:10.1016/j.apenergy.2021.116798 · Cited by 403 · see citing works
Smartly Handling Renewable Energy Instability in Supporting A Cloud Datacenter
Gao, J., Wang, H., & Shen, H. (2020) · IEEE International Parallel and Distributed Processing Symposium (IPDPS) · doi:10.1109/ipdps47924.2020.00084 · Cited by 296 · see citing works
The environmental footprint of data centers in the United States
Siddik, M. A. B., Shehabi, A., & Marston, L. (2021) · Environmental Research Letters · doi:10.1088/1748-9326/abfba1 · Cited by 281 · see citing works
“Though the amount of data center computing workloads has increased nearly 550% between 2010 and 2018, data center electricity consumption has only risen by 6% due to dramatic improvements in energy efficiency and storage-drive density across the industry [1, 3].”
BackgroundMethodInfluentialSelf-citationMorley, J., Widdicks, K., & Hazas, M. (2018) · Energy Research & Social Science · doi:10.1016/j.erss.2018.01.018 · Cited by 258 · see citing works
A Systematic Survey on Energy-Efficient Techniques in Sustainable Cloud Computing
Bharany, S., Sharma, S., Khalaf, O. I., Abdulsahib, G. M., Al-Humaimeedy, A. S., Aldhyani, T. H. H., Maashi, M. S., & Alkahtani, H. S. (2022) · Sustainability · doi:10.3390/su14106256 · Cited by 242 · see citing works
Mytton, D. (2021) · npj Clean Water · doi:10.1038/s41545-021-00101-w · Cited by 238 · see citing works
A review of power consumption models of servers in data centers
Jin, C., Bai, X., Yang, C., Mao, W., & Xu, X. (2020) · Applied Energy · doi:10.1016/j.apenergy.2020.114806 · Cited by 232 · see citing works
DNA stability: a central design consideration for DNA data storage systems
Matange, K. R., Tuck, J. M., & Keung, A. J. (2021) · Nature Communications · doi:10.1038/s41467-021-21587-5 · Cited by 212 · see citing works
Energy-Efficient Edge-Fog-Cloud Architecture for IoT-Based Smart Agriculture Environment
Alharbi, H. A., & Aldossary, M. (2021) · IEEE Access · doi:10.1109/access.2021.3101397 · Cited by 200 · see citing works
Intelligent Resource Management in Blockchain-Based Cloud Datacenters
Xu, C., Wang, K., & Guo, M. (2017) · IEEE Cloud Computing · doi:10.1109/mcc.2018.1081060 · Cited by 198 · see citing works
Data center growth in the United States: decoupling the demand for services from electricity use
Shehabi, A., Smith, S. J., Masanet, E. R., & Koomey, J. (2018) · Environmental Research Letters · doi:10.1088/1748-9326/aaec9c · Cited by 219 · see citing works
Self-citationCui, Y., Li, M., & Hu, Y. (2019) · Journal of Materials Chemistry C · doi:10.1039/c9tc05415d · Cited by 189 · see citing works
Exploring the sustainability challenges facing digitalization and internet data centers
Kez, D. A., Foley, A. M., Laverty, D., Rio, D. D. F. D., & Sovacool, B. K. (2022) · Journal of Cleaner Production · doi:10.1016/j.jclepro.2022.133633 · Cited by 202 · see citing works
Li, P., Yang, J., Islam, M. A., & Ren, S. (2025) · Communications of the ACM · doi:10.1145/3724499 · Cited by 176 · see citing works
“Different power plants use different amounts of water for each kWh generation, depending on the cooling techniques.”
InfluentialEco‐Friendly Electronics—A Comprehensive Review
Cenci, M. P., Scarazzato, T., Munchen, D. D., Dartora, P. C., Veit, H. M., Bernardes, A. M., & Dias, P. (2021) · Advanced Materials Technologies · doi:10.1002/admt.202001263 · Cited by 175 · see citing works
Vertical Stacked LEGO-PoL CPU Voltage Regulator
Baek, J.-I., Elasser, Y., Radhakrishnan, K., Gan, H., Douglas, J. P., Krishnamurthy, H. K., Li, X., Jiang, S., Sullivan, C. R., & Chen, M. (2021) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2021.3135386 · Cited by 166 · see citing works
Ye, Z., Lei, Y., & Pilawa-Podgurski, R. C. N. (2019) · IEEE Transactions on Power Electronics · doi:10.1109/tpel.2019.2947218 · Cited by 165 · see citing works
“IN [1], it is reported that in 2014, data centers use more than 1.”
BackgroundHuang, Y., Xu, H., Gao, H., Ma, X., & Hussain, W. (2021) · IEEE Transactions on Green Communications and Networking · doi:10.1109/tgcn.2021.3067374 · Cited by 160 · see citing works
“According to published research, data centers in the United States are expected to consume approximately 73 billion kWh in 2020 [7].”
BackgroundFei, C., Yang, Y., Li, Q., & Lee, F. C. (2017) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2017.2733473 · Cited by 159 · see citing works
Data centres in future European energy systems—energy efficiency, integration and policy
Koronen, C., Åhman, M., & Nilsson, L. J. (2019) · Energy Efficiency · doi:10.1007/s12053-019-09833-8 · Cited by 163 · see citing works
“Several extensive studies (Masanet et al. 2011; Shehabi et al. 2016) have been carried out to estimate the total electricity consumption of the full spectrum of US data centres.”
BackgroundA review on airflow management in data centers
Chu, W., & Wang, C.-C. (2019) · Applied Energy · doi:10.1016/j.apenergy.2019.02.041 · Cited by 156 · see citing works
Sources of data center energy estimates: A comprehensive review
Mytton, D., & Ashtine, M. (2022) · Joule · doi:10.1016/j.joule.2022.07.011 · Cited by 183 · see citing works
Integrated energy systems of data centers and smart grids: State-of-the-art and future opportunities
Guo, C., Luo, F., Cai, Z., & Dong, Z. Y. (2021) · Applied Energy · doi:10.1016/j.apenergy.2021.117474 · Cited by 148 · see citing works
Khosravi, A., Andrew, L. L. H., & Buyya, R. (2017) · IEEE Transactions on Sustainable Computing · doi:10.1109/tsusc.2017.2709980 · Cited by 141 · see citing works
99.1% Efficient 10 kV SiC-Based Medium-Voltage ZVS Bidirectional Single-Phase PFC AC/DC Stage
Rothmund, D., Guillod, T., Bortis, D., & Kolar, J. W. (2018) · IEEE Journal of Emerging and Selected Topics in Power Electronics · doi:10.1109/jestpe.2018.2886140 · Cited by 140 · see citing works
“8% of the national electric energy generation [2].”
BackgroundKang, J. S., Wu, H. Y., & Hu, Y. (2017) · Nano Letters · doi:10.1021/acs.nanolett.7b03437 · Cited by 134 · see citing works
High Frequency Resonant Converters: An Overview on the Magnetic Design and Control Methods
Lee, F. C., Li, Q., & Nabih, A. (2020) · IEEE Journal of Emerging and Selected Topics in Power Electronics · doi:10.1109/jestpe.2020.3011166 · Cited by 134 · see citing works
Mitigating Curtailment and Carbon Emissions through Load Migration between Data Centers
Zheng, J., Chien, A. A., & Suh, S. (2020) · Joule · doi:10.1016/j.joule.2020.08.001 · Cited by 133 · see citing works
Data Center Cooling using Model-predictive Control
Lazic, N., Boutilier, C. E., Lu, T., Wong, E., Roy, B., Ryu, M. D., & Imwalle, G. (2018) · neural information processing systems · Cited by 131 · see citing works
Corbett, C. J. (2018) · Production and Operations Management · doi:10.1111/poms.12837 · Cited by 128 · see citing works
“Taking data from Shehabi et al. (2016), a Lawrence Berkeley National Laboratory report he coauthored, he estimates US data centers stored about 300 million TB of data in 2016 (figure 12, p. 14), which consumed around 8.3 billion kWh (figure 16, p. 17), hence 27.7 kWh per TB of data.”
BackgroundMethodInfluentialEstimating Energy Consumption of Cloud, Fog, and Edge Computing Infrastructures
Ahvar, E., Orgerie, A., & Lèbre, A. (2019) · IEEE Transactions on Sustainable Computing · doi:10.1109/tsusc.2019.2905900 · Cited by 125 · see citing works
“According to Lawrence Berkeley National Laboratory (LBNL)’s report, published in 2016 [1], DCs consumed an estimated 70 billion kWh (about 1.8% of total U.S. electricity consumption) and they are projected to consume approximately 73 billion kWh by 2020 in the U.S.”
BackgroundInfluentialPAPSO: A Power-Aware VM Placement Technique Based on Particle Swarm Optimization
Ibrahim, A. F., Noshy, M., Ali, H. A., & Badawy, M. (2020) · IEEE Access · doi:10.1109/access.2020.2990828 · Cited by 125 · see citing works
A review on energy efficiency and demand response with focus on small and medium data centers
Vasques, T. L., Moura, P., & de Almeida, A. T. (2018) · Energy Efficiency · doi:10.1007/s12053-018-9753-2 · Cited by 126 · see citing works
Goel, A., Masurkar, S., & Pathade, G. R. (2024) · Sustainability · doi:10.3390/su162411079 · Cited by 123 · see citing works
Prospects and Challenges of Photonic Switching in Data Centers and Computing Systems
Yoo, S. J. B. (2021) · Journal of Lightwave Technology · doi:10.1109/jlt.2021.3136570 · Cited by 123 · see citing works
Suárez-Albela, M., Fraga‐Lamas, P., & Fernández‐Caramés, T. M. (2018) · Sensors · doi:10.3390/s18113868 · Cited by 121 · see citing works
“Regarding energy consumption, it is estimated that the United States data centers will consume approximately 73 TWh in 2020 [2].”
BackgroundUeda, D., Walston, S. L., Fujita, S., Fushimi, Y., Tsuboyama, T., Kamagata, K., Yamada, A., Yanagawa, M., Ito, R., Fujima, N., et al. (2024) · Diagnostic and Interventional Imaging · doi:10.1016/j.diii.2024.06.002 · Cited by 133 · see citing works
Integrated planning of internet data centers and battery energy storage systems in smart grids
Guo, C., Luo, F., Cai, Z., Dong, Z. Y., & Zhang, R. (2020) · Applied Energy · doi:10.1016/j.apenergy.2020.116093 · Cited by 118 · see citing works
The Carbon Footprint of Bioinformatics
Grealey, J., Lannelongue, L., Saw, W., Marten, J., Méric, G., Carmona, S. R., & Inouye, M. (2022) · Molecular Biology and Evolution · doi:10.1093/molbev/msac034 · Cited by 115 · see citing works
“A report from 2016 estimated 267 that energy usage by data centres in the US could be reduced by 25% if 80% of the smaller 268 data centres were aggregated into larger and more efficient data centres (hyperscale 269 facilities) [66].”
BackgroundKaur, K., Garg, S., Kaddoum, G., Bou‐Harb, E., & Choo, K. R. (2019) · IEEE Transactions on Industrial Informatics · doi:10.1109/tii.2019.2939573 · Cited by 114 · see citing works
“Existing studies in this context advocate that, worldwide, cloud DCs are left under-utilized during the majority of their lifetime [8], [9].”
BackgroundThermal Prediction for Efficient Energy Management of Clouds Using Machine Learning
Ilager, S., Ramamohanarao, K., & Buyya, R. (2020) · IEEE Transactions on Parallel and Distributed Systems · doi:10.1109/tpds.2020.3040800 · Cited by 111 · see citing works
“According to [2], around 2 percent of global electricity is spent on data centers, and almost 50 percent of this energy is spent on cooling systems [3].”
BackgroundA survey of data center consolidation in cloud computing systems
Helali, L., & Omri, M. N. (2021) · Computer Science Review · doi:10.1016/j.cosrev.2021.100366 · Cited by 111 · see citing works
Xiao, T., Nerini, F. F., Matthews, H. D., Tavoni, M., & You, F. (2025) · Nature Sustainability · doi:10.1038/s41893-025-01681-y · Cited by 121 · see citing works
“Previous research has developed bottom-up and top-down meth-ods to assess energy–water–carbon outcomes of servers 19–21 , but these approaches face challenges with the rise of AI servers.”
Data Center Challenges and Their Power Electronics
Krein, P. T. (2017) · CPSS Transactions on Power Electronics and Applications · doi:10.24295/cpsstpea.2017.00005 · Cited by 105 · see citing works
Kwon, S. (2020) · Applied Energy · doi:10.1016/j.apenergy.2020.115424 · Cited by 103 · see citing works
Cheung, H., Wang, S., Zhuang, C., & Gu, J. (2018) · Applied Energy · doi:10.1016/j.apenergy.2018.03.138 · Cited by 101 · see citing works
“decade if the demand on their services continued to increase and their energy efficiency remained unchanged [2].”
BackgroundCost and potential of metal–organic frameworks for hydrogen back-up power supply
Peng, P., Anastasopoulou, A., Brooks, K., Furukawa, H., Bowden, M., Long, J. R., Autrey, T. S., & Breunig, H. M. (2022) · Nature Energy · doi:10.1038/s41560-022-01013-w · Cited by 97 · see citing works
High Thermal Conductivity in Isotopically Enriched Cubic Boron Phosphide
Zheng, Q., Li, S., Li, C., Lv, Y., Liu, X., Huang, P. Y., Broido, D., Lv, B., & Cahill, D. G. (2018) · Advanced Functional Materials · doi:10.1002/adfm.201805116 · Cited by 96 · see citing works
Data Center Demand Response in Deregulated Electricity Markets
Bahrami, S., Wong, V. W. S., & Huang, J. (2018) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2018.2810830 · Cited by 95 · see citing works
“5 and 2 [27].”
Critically reviewing smart home technology applications and business models in Europe
Rio, D. D. F. D., Sovacool, B. K., Bergman, N. M., & Makuch, Z. (2020) · Energy Policy · doi:10.1016/j.enpol.2020.111631 · Cited by 95 · see citing works
BEGIN: Big Data Enabled Energy-Efficient Vehicular Edge Computing
Zhou, Z., Yu, H., Xu, C. G., Chang, Z., Mumtaz, S., & Rodrı́guez, J. (2018) · IEEE Communications Magazine · doi:10.1109/mcom.2018.1700910 · Cited by 94 · see citing works
“For instance, in the United States, the annul electricity consumption of data centers is expected to reach as high as 140 billion kWh by 2020 [7].”
BackgroundA Belief Rule Based Expert System for Datacenter PUE Prediction under Uncertainty
Hossain, M. S., Rahaman, S., Kor, A.-L., Andersson, K., & Pattinson, C. (2017) · IEEE Transactions on Sustainable Computing · doi:10.1109/tsusc.2017.2697768 · Cited by 89 · see citing works
“Data Center IT equipment are: Servers, storage, and networks [3].”
BackgroundMethodRadonjič, G., & Tompa, S. (2018) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2018.09.018 · Cited by 89 · see citing works
Cheng, R., Wang, Q., Wang, Z., Jing, L., Caraveo, A. G., Li, Z., Zhong, Y., Liu, X., Luo, X., Huang, T., et al. (2025) · Nature Communications · doi:10.1038/s41467-025-56163-8 · Cited by 94 · see citing works
Li, J., & Li, Z. (2020) · Energy and Buildings · doi:10.1016/j.enbuild.2020.110407 · Cited by 87 · see citing works
Opportunities and Challenges for Industrial Water Treatment and Reuse
Meese, A. F., Kim, D. J., Wu, X., Le, L., Napier, C., Hernandez, M., Laroco, N., Linden, K. G., Cox, J., Kurup, P., et al. (2021) · ACS ES&T Engineering · doi:10.1021/acsestengg.1c00282 · Cited by 86 · see citing works
Green Cloud? An Empirical Analysis of Cloud Computing and Energy Efficiency
Park, J., Han, K., & Lee, B. (2022) · Management Science · doi:10.1287/mnsc.2022.4442 · Cited by 86 · see citing works
GREENER principles for environmentally sustainable computational science
Lannelongue, L., Aronson, H. G., Bateman, A. G., Birney, E., Caplan, T., Juckes, M. N., McEntyre, J., Morris, A. D., Reilly, G., & Inouye, M. (2023) · Nature Computational Science · doi:10.1038/s43588-023-00461-y · Cited by 87 · see citing works
Jiang, C., Han, G., Lin, J., Jia, G., Shi, W., & Wan, J. (2019) · IEEE Access · doi:10.1109/access.2019.2897898 · Cited by 85 · see citing works
Statistical analysis for predicting location-specific data center PUE and its improvement potential
Lei, N., & Masanet, E. R. (2020) · Energy · doi:10.1016/j.energy.2020.117556 · Cited by 88 · see citing works
Self-citationCarbonScaler: Leveraging Cloud Workload Elasticity for Optimizing Carbon-Efficiency
Hanafy, W. A., Liang, Q., Bashir, N., Irwin, D., & Shenoy, P. J. (2023) · Proceedings of the ACM on Measurement and Analysis of Computing Systems · doi:10.1145/3626788 · Cited by 83 · see citing works
Quarter-Turn Transformer Design and Optimization for High Power Density 1-MHz LLC Resonant Converter
Liu, Y., Chen, K.-D., Chen, C., Syu, Y.-L., Lin, G.-W., Kim, K. A., & Chiu, H. (2019) · IEEE Transactions on Industrial Electronics · doi:10.1109/tie.2019.2902821 · Cited by 81 · see citing works
“electricity consumption, and is predicted to reach 73 billion kW by 2020 [1].”
BackgroundLi, Y., Orgerie, A., Ivan Rodero, A., Amersho, B. L., Parashar, M., & Menaud, J.-M. (2017) · Future Generation Computer Systems · doi:10.1016/j.future.2017.12.048 · Cited by 80 · see citing works
Demand Response in Data Centers: Integration of Server Provisioning and Power Procurement
Kwon, S., Ntaimo, L., & Gautam, N. (2018) · IEEE Transactions on Smart Grid · doi:10.1109/tsg.2018.2871125 · Cited by 79 · see citing works
“According to a report released from the Lawrence Berkeley National Laboratory [1] in 2014, data centers in the U.S. consumed an estimated 70 billion kWh, which represents 1.8% of total U.S. electricity consumption.”
MethodInfluentialMulti-objective communication-aware optimization for virtual machine placement in cloud datacenters
Farzai, S., Shirvani, M. H., & Rabbani, M. (2020) · Sustainable Computing Informatics and Systems · doi:10.1016/j.suscom.2020.100374 · Cited by 79 · see citing works
How much energy will AI really consume? The good, the bad and the unknown
Chen, S. (2025) · Nature · doi:10.1038/d41586-025-00616-z · Cited by 78 · see citing works
Joint data center cooling and workload management: A thermal-aware approach
MirhoseiniNejad, S., Moazamigoodarzi, H., Badawy, G. H., & Down, D. G. (2019) · Future Generation Computer Systems · doi:10.1016/j.future.2019.10.040 · Cited by 78 · see citing works
An energy, performance efficient resource consolidation scheme for heterogeneous cloud datacenters
Khan, A. A., Zakarya, M., Khan, R., Rahman, I. U., Khan, M., & Khan, A. U. R. (2019) · Journal of Network and Computer Applications · doi:10.1016/j.jnca.2019.102497 · Cited by 77 · see citing works
The Datacenter as a Computer: Designing Warehouse-Scale Machines, Third Edition
Barroso, L. A., Hölzle, U., & Ranganathan, P. (2018) · Synthesis lectures on computer architecture · doi:10.2200/s00874ed3v01y201809cac046 · Cited by 76 · see citing works
Ye, Z., Lei, Y., & Pilawa-Podgurski, R. C. N. (2019) · Conference proceedings/Conference proceedings - IEEE Applied Power Electronics Conference and Exposition · doi:10.1109/apec.2019.8721812 · Cited by 75 · see citing works
“in 2014, and it is projected to increase to 10% by 2020 [1].”
BackgroundLiao, M., Lan, K., & Yao, Y. (2021) · Journal of Industrial Ecology · doi:10.1111/jiec.13214 · Cited by 80 · see citing works
“(Ahmad et al., 2021; Huang &Masanet, 2015; Shehabi et al., 2016).”
Dual Inductor Hybrid Converter for Point-of-Load Voltage Regulator Modules
Seo, G., Das, R., & Le, H. (2019) · IEEE Transactions on Industry Applications · doi:10.1109/tia.2019.2941945 · Cited by 74 · see citing works
“is expected to reach 73 billion kWh by 2020 [1], accounting for about 2% of U.”
BackgroundExploiting Renewable Energy and UPS Systems to Reduce Power Consumption in Data Centers
Peng, X., Bhattacharya, T., Cao, T., Mao, J., Tekreeti, T., & Qin, X. (2021) · Big Data Research · doi:10.1016/j.bdr.2021.100306 · Cited by 71 · see citing works
A review on the decarbonization of high-performance computing centers
Silva, C. A. M., Vilaca, R. M. P., Pereira, A., & Bessa, R. J. (2023) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2023.114019 · Cited by 71 · see citing works
The making of critical data center studies
Edwards, D. W., Cooper, Z. G. T., & Hogan, M. (2024) · Convergence The International Journal of Research into New Media Technologies · doi:10.1177/13548565231224157 · Cited by 85 · see citing works
“…to over 20,000 square feet, while colocation and cloud data centers can theoretically be as small as a studio apartment, while the largest ‘ hyperscale ’ data center in the world (Switch ’ s The Citadel in Reno, Nevada) covers over seven-million square feet (Shehabi et al., 2016; Taneja, 2020).”
Energy, performance and cost efficient datacenters: A survey
Zakarya, M. (2018) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2018.06.005 · Cited by 69 · see citing works
Global trends, performance metrics, and energy reduction measures in datacom facilities
Isazadeh, A., Ziviani, D., & Claridge, D. E. (2023) · Renewable and Sustainable Energy Reviews · doi:10.1016/j.rser.2023.113149 · Cited by 68 · see citing works
Moazamigoodarzi, H., Gupta, R., Pal, S., Tsai, P. J., Ghosh, S., & Puri, I. K. (2019) · Applied Energy · doi:10.1016/j.apenergy.2019.114355 · Cited by 67 · see citing works
Manganelli, M., Soldati, A., Martirano, L., & Ramakrishna, S. (2021) · Sustainability · doi:10.3390/su13116114 · Cited by 67 · see citing works
Lei, N., & Masanet, E. R. (2022) · Resources Conservation and Recycling · doi:10.1016/j.resconrec.2022.106323 · Cited by 67 · see citing works
Self-citationReview of energy efficiency and technological advancements in data center power systems
Khosravi, A., Sandoval, O. R., Taslimi, M. S., Sahrakorpi, T., Amorim, G., & Pabón, J. J. G. (2024) · Energy and Buildings · doi:10.1016/j.enbuild.2024.114834 · Cited by 67 · see citing works
Enough hot air: the role of immersion cooling
Haghshenas, K., Setz, B., Blosch, Y., & Aiello, M. (2023) · Energy Informatics · doi:10.1186/s42162-023-00269-0 · Cited by 66 · see citing works
“The contribution of the servers, storage, and network facility in the total power consumption of a data center has been reported in several works [46], [47].”
BackgroundA 95%-Efficient 48V-to-1V/10A VRM Hybrid Converter Using Interleaved Dual Inductors
Seo, G., Das, R., & Le, H. (2018) · IEEE Energy Conversion Congress and Exposition (ECCE) · doi:10.1109/ecce.2018.8557715 · Cited by 66 · see citing works
A review on evaluation metrics of thermal performance in data centers
Gong, X.-M., Zhang, Z., Sixuan, G., Niu, B., Liu, Y., Xu, H., & Gao, M. (2020) · Building and Environment · doi:10.1016/j.buildenv.2020.106907 · Cited by 66 · see citing works
An Energy and Performance Aware Consolidation Technique for Containerized Datacenters
Khan, A. A., Zakarya, M., Buyya, R., Khan, R., Khan, M., & RANA, O. F. (2019) · IEEE Transactions on Cloud Computing · doi:10.1109/tcc.2019.2920914 · Cited by 65 · see citing works
“Furthermore, [2] also suggests that, due to migration from internal systems to the cloud, datacenter energy consumption will remain constant until 2020.”
BackgroundInfluentialMoghaddam, S. M., O’Sullivan, M., Walker, C. G., Piraghaj, S. F., & Unsworth, C. P. (2020) · Future Generation Computer Systems · doi:10.1016/j.future.2020.01.008 · Cited by 65 · see citing works
The water use of data center workloads: A review and assessment of key determinants
Lei, N., Lu, J., Shehabi, A., & Masanet, E. (2025) · Resources, Conservation and Recycling · doi:10.1016/j.resconrec.2025.108310 · Cited by 79 · see citing works
Self-citationDas, S., & Mao, E. (2020) · Sustainable Energy Grids and Networks · doi:10.1016/j.segan.2020.100408 · Cited by 63 · see citing works
Sandri, P. L. (2017) · IEEE Power Electronics Magazine · doi:10.1109/mpel.2017.2760113 · Cited by 62 · see citing works
“FIG 1 The average power draw assumptions for both midrange and high-end servers [2].”
BackgroundInfluentialThe Economics of Sustainability
Pezzey, J. C. V., & Toman, M. (2017) · Routledge eBooks · doi:10.4324/9781315240084 · Cited by 63 · see citing works
- Authors
- Lawrence Berkeley National Laboratory (LBNL), B., Shehabi, A., USDOE, Smith, S., Sartor, D., Brown, R., Herrlin, M., Koomey, J., Masanet, E., Horner, N., Azevedo, I., & Lintner, W.
- Affiliations
- Lawrence Berkeley National Laboratory (US)
- Stanford University (US)
- Northwestern University (US)
- Carnegie Mellon University (US)
- United States Department of Energy (US)
- Published
- 2016-06-01
- OpenAlex
- W2736578080
- Cited by
- 1,040
- References
- 32
- Citations by year
- 2026: 88 · 2025: 124 · 2024: 83 · 2023: 88 · 2022: 92 · 2021: 129 · 2020: 121 · 2019: 125 · 2018: 126 · 2017: 59 · 2016: 5
- Type
- report
- Language
- en
- Open access
- gold
- doi.org
- Licence
- public-domain
- Locations
- eScholarship (California Digital Library) (submittedVersion)
- OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) (submittedVersion, public-domain)
- UC Berkeley
- Funders
- USDOE
- DOE (NONE)
- Topics
- Physical Sciences › Engineering › Electrical and Electronic Engineering › Green IT and Sustainability
- Physical Sciences › Computer Science › Hardware and Architecture › Energy Efficiency in Computing
- Physical Sciences › Computer Science › Information Systems › Cloud Computing and Resource Management
- Keywords
- load forecasting, energy demand projections
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review