Is CO2 an Indoor Pollutant? Direct Effects of Low-to-Moderate CO2 Concentrations on Human Decision-Making Performance
Open accessThe DOI matches its Crossref record; 24 of the 24 references it cites were found in a registry or an index.
Abstract
Background: Associations of higher indoor carbon dioxide (CO2) concentrations with impaired work performance, increased health symptoms, and poorer perceived air quality have been attributed to correlation of indoor CO2 with concentrations of other indoor air pollutants that are also influenced by rates of outdoor-air ventilation. Objectives: We assessed direct effects of increased CO2, within the range of indoor concentrations, on decision making. Methods: Twenty-two participants were exposed to CO2 at 600, 1,000, and 2,500 ppm in an office-like chamber, in six groups. Each group was exposed to these conditions in three 2.5-hr sessions, all on 1 day, with exposure order balanced across groups. At 600 ppm, CO2 came from outdoor air and participants’ respiration. Higher concentrations were achieved by injecting ultrapure CO2. Ventilation rate and temperature were constant. Under each condition, participants completed a computer-based test of decision-making performance as well as questionnaires on health symptoms and perceived air quality. Participants and the person administering the decision-making test were blinded to CO2 level. Data were analyzed with analysis of variance models. Results: Relative to 600 ppm, at 1,000 ppm CO2, moderate and statistically significant decrements occurred in six of nine scales of decision-making performance. At 2,500 ppm, large and statistically significant reductions occurred in seven scales of decision-making performance (raw score ratios, 0.06–0.56), but performance on the focused activity scale increased. Conclusions: Direct adverse effects of CO2 on human performance may be economically important and may limit energy-saving reductions in outdoor air ventilation per person in buildings. Confirmation of these findings is needed.
Overview
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Integrity signals
Registry
Cites
Statistics
Figures
Verification
Claims the paper makes
The claims and statistics of this paper haven’t been checked yet.
Free: it reads the open-access text and checks the first 5 claims that cite a source we can check. Create a free account to check every claim.
Claims other papers make about this one
Each is checked against this paper’s own text: does it say what the citing paper says it does?
The source backs part of the claim, not all of it — or backs it for a different population, condition or comparison.
In the citing paper
“Low ventilation rates and CO2 concentrations normally found in office buildings (approximately 1,000 ppm) have been recently associated with impairment in multiple domains of high-order cognitive function [45,46].”
From Reduced cognitive function during a heat wave among residents of non-air-conditioned buildings: An observational study of young adults in the summer of 2016 (2018) · cites this paper as [45]
Experimental — accuracy not yet measured
Self-check
Percentages, sums and reported differences re-computed from the paper’s own numbers.
The self-check needs the paper’s full text.
Citations
Cites
Seppanen, O. A., Fisk, W. J., & Mendell, M. J. (1999) · Indoor Air · doi:10.1111/j.1600-0668.1999.00003.x · Cited by 876
Self-citationWARGOCKI, P., WYON, D. P., SUNDELL, J., CLAUSEN, G., & FANGER, P. O. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004222.x · Cited by 688
Associations between classroom CO2 concentrations and student attendance in Washington and Idaho
Shendell, D. G., Prill, R., Fisk, W. J., Apte, M. G., Blake, D., & Faulkner, D. (2004) · Indoor Air · doi:10.1111/j.1600-0668.2004.00251.x · Cited by 462
Self-citationCarbon Dioxide and the Cerebral Circulation
Brian, J. E. (1998) · Anesthesiology · doi:10.1097/00000542-199805000-00029 · Cited by 395
MILTON, D. K., GLENCROSS, P. M., & WALTERS, M. D. (2000) · Indoor Air · doi:10.1034/j.1600-0668.2000.010004212.x · Cited by 364
Behavior in the complex environment.
Streufert, S., & Streufert, S. C. (1978) · Cited by 302
Self-citationPhysiological Impact of the N95 Filtering Facepiece Respirator on Healthcare Workers
Roberge, R. J., Coca, A., Williams, W. J., Powell, J. B., & Palmiero, A. J. (2010) · Respiratory Care · doi:10.4187/respcare.10550569 · Cited by 276
Woods, S. W. (1988) · Archives of General Psychiatry · doi:10.1001/archpsyc.1988.01800250051007 · Cited by 265 · cited 2×
“Inhaled CO2 at concentrations of tens of thousands of ppm has been associated with changes in respiration, cerebral blood flow, cardiac output, and anxiety (Brian Jr 1998; Kaye et al. 2004; Lipsett et al. 1994; Roberge et al. 2010; Woods et al. 1988).”
BackgroundErdmann, C. A., & Apte, M. G. (2004) · Indoor Air · doi:10.1111/j.1600-0668.2004.00298.x · Cited by 147 · cited 1×
“…perceptions of poor air quality, increased prevalence of acute health symptoms (e.g., headache, mucosal irritation), slower work performance, and increased absence (Erdmann and Apte 2004; Federspiel et al. 2004; Milton et al. 2000; Seppanen et al. 1999; Shendell et al. 2004; Wargocki et al. 2000).”
BackgroundKaye, J., Buchanan, F., Kendrick, A. H., Johnson, P. L., Lowry, C. A., Bailey, J., Nutt, D., & Lightman, S. L. (2004) · Journal of Neuroendocrinology · doi:10.1111/j.0953-8194.2004.01158.x · Cited by 134 · cited 2×
“CO2 is the key regulator of respiration and arousal of behavioral states in humans (Kaye et al. 2004).”
Background
Research works printed but not linked: 7
- ACGIH (American Conference of Governmental Industrial Hygienists), 2011, TLVs and BEIs
- Corsi, 2002, Carbon dioxide levels and dynamics in elementary schools: results of the TESIAS Study. In: Indoor Air 2002, 9th International Conference on Indoor Air Quality and Climate (Levin H, ed)
- Knibbs, 2008, On-road quantification of the key characteristics of automobile HVAC systems in relation to in-cabin submicrometer particle pollution [Abstract]. In: 11th International Conference on Indoor Air Quality and Climate: Indoor Air 2008. Copenhagen, Denmark.
- Mudarri, 1997, Potential correction factors for interpreting CO2 measurements in buildings., ASHRAE Transactions, 103, 244
- Persily, 1997, Evaluating building IAQ and ventilation with carbon dioxide., ASHRAE Transactions, 103, 193
- Satish, 2009, Novel assessment of psychiatry residents: SMS simulations. Accreditation Council for Graduate Medical Education (ACGME) Bulletin, 18–23 January.
- Swezey, 1998, Preliminary development of a computer-based team performance assessment simulation., Int J Cogn Ergonomics, 2, 163
Cited by
Items 101–200 of 1,000
Carratt, A., Kokogiannakis, G., & Daly, D. (2020) · Journal of Cleaner Production · doi:10.1016/j.jclepro.2020.121408 · Cited by 74
The ventilation of buildings and other mitigating measures for COVID-19: a focus on wintertime.
Burridge, H. C., Bhagat, R. K., Stettler, M. E. J., Kumar, P., Mel, I. D., Demis, P., Hart, A., Johnson-Llambias, Y., King, M., Victorovich, K. O., et al. (2021) · Apollo (University of Cambridge) · doi:10.17863/cam.66124 · Cited by 69
Cement Industry Pollution and Its Impact on the Environment and Population Health: A Review
Bărbulescu, A., & Hosen, K. (2025) · Toxics · doi:10.3390/toxics13070587 · Cited by 107
Rackes, A., & Waring, M. S. (2014) · Energy and Buildings · doi:10.1016/j.enbuild.2014.02.024 · Cited by 69
A fog-computing architecture for preventive healthcare and assisted living in smart ambients
Cerina, L., Notargiacomo, S., Paccanit, M. G., & Santambrogio, M. D. (2017) · IEEE International Forum on Research and Technology for Society and Industry (RTSI) · doi:10.1109/rtsi.2017.8065939 · Cited by 70
“In particular every day insides offices, houses, classrooms, people are routinely exposed to high levels of carbon dioxide (CO2) that has direct and negative impact on human cognition and decisionmaking processes [18].”
BackgroundLee, E. S., & Zhu, Y. (2014) · Environmental Science & Technology · doi:10.1021/es404952q · Cited by 74
Fadeyi, M. O., Alkhaja, K., Sulayem, M. B., & Abu-Hijleh, B. (2014) · Frontiers of Architectural Research · doi:10.1016/j.foar.2014.03.001 · Cited by 83
Carbon dioxide generation rates of different age and gender under various activity levels
Yang, L., Wang, X., Li, M., Zhou, X. J., Liu, S., Zhang, H., Arens, E. A., & Zhai, Y. (2020) · Building and Environment · doi:10.1016/j.buildenv.2020.107317 · Cited by 71
Treesubsuntorn, C., & Thiravetyan, P. (2018) · Journal of Cleaner Production · doi:10.1016/j.jclepro.2018.05.141 · Cited by 66
Haverinen‐Shaughnessy, U., Pekkonen, M., Leivo, V., Prasauskas, T., Turunen, M., Kiviste, M., Aaltonen, A., & Martuzevičius, D. (2018) · International Journal of Hygiene and Environmental Health · doi:10.1016/j.ijheh.2018.05.009 · Cited by 70
“Limitations of occupant surveys include that they provide subjective measures prone to bias such as self-selection bias and misclassification (Rothman et al., 2008).”
BackgroundAlmeida, R. M. S. F., Pinto, M., Pinho, P., & de Lemos, L. T. (2016) · Energy Efficiency · doi:10.1007/s12053-016-9485-0 · Cited by 72
Indoor air quality of non-residential urban buildings in Delhi, India
Datta, A., Suresh, R., Gupta, A., Singh, D., & Kulshrestha, P. (2017) · International Journal of Sustainable Built Environment · doi:10.1016/j.ijsbe.2017.07.005 · Cited by 74
Real-Time In-Vehicle Air Quality Monitoring System Using Machine Learning Prediction Algorithm
Cheik, G. C., Kamarudin, L. M., Zakaria, A., Nishizaki, H., Ramli, N., Mao, X., Zakaria, S. M. M. S., Kanagaraj, E., Sukor, A. S. A., & Elham, M. F. (2021) · Sensors · doi:10.3390/s21154956 · Cited by 67
“The high concentration of CO2 reduces human cognitive ability, causes drowsiness, dizziness, and fatigue [8,9].”
BackgroundStahn, A. C., & Kühn, S. (2021) · Cognitive Processing · doi:10.1007/s10339-021-01050-5 · Cited by 73
Barnes, N. M., Ng, T. W., Ma, K. K., & Lai, K. M. (2018) · International Journal of Environmental Research and Public Health · doi:10.3390/ijerph15040611 · Cited by 64
“, >2000 ppm of CO2) [27], as well as lower the overall decision-making performance (studies conducted in a controlled environmental chamber with 1000 and 2500 ppm of CO2) [28].”
BackgroundA multi-criteria assessment of the passengers’ level of comfort in urban railway rolling stock
Mohammadi, A., Amador-Jiménez, L., & Nasiri, F. (2019) · Sustainable Cities and Society · doi:10.1016/j.scs.2019.101892 · Cited by 64
Korsavi, S. S., Montazami, A., & Mumovic, D. (2020) · Indoor Air · doi:10.1111/ina.12740 · Cited by 73
Effect of Wearing Face Masks on the Carbon Dioxide Concentration in the Breathing Zone
Geiss, O. (2020) · Aerosol and Air Quality Research · doi:10.4209/aaqr.2020.07.0403 · Cited by 68
“Satish et al. (2012) suggested in their study that even moderately elevated CO 2 concentrations (approximately 2500 ppm) have the potential to affect decision-making.”
Recent advances in biological systems for improving indoor air quality
Kraakman, N. J. R., González-Martín, J., Pérez, C., Lebrero, R., & Muñoz, R. (2021) · Reviews in Environmental Science and Bio/Technology · doi:10.1007/s11157-021-09569-x · Cited by 74
Heebøll, A., Wargocki, P. L., & Toftum, J. (2018) · Science and Technology for the Built Environment · doi:10.1080/23744731.2018.1432938 · Cited by 68
“2016, 2017), although demanding cognitive tasks have been shown to be affected (Allen et al. 2016; Satish et al. 2012).”
BackgroundKim, H., Hong, T., & Kim, J. (2019) · Building and Environment · doi:10.1016/j.buildenv.2019.02.032 · Cited by 66
Laurent, J. G. C., MacNaughton, P., Jones, E. R., Young, A. S., Bliss, M., Flanigan, S. S., Vallarino, J., Chen, L., Cao, X., & Allen, J. G. (2021) · Environmental Research Letters · doi:10.1088/1748-9326/ac1bd8 · Cited by 118
Control of airborne infectious disease in buildings: Evidence and research priorities
de Mesquita, P. J. B., Delp, W. W., Chan, W. R., Bahnfleth, W. P., & Singer, B. C. (2021) · Indoor Air · doi:10.1111/ina.12965 · Cited by 69
Winter Ventilation Rates at Primary Schools: Comparison Between Portugal and Finland
Canha, N., Almeida, S. M., Freitas, M. C., Täubel, M., & Hänninen, O. (2013) · Journal of Toxicology and Environmental Health · doi:10.1080/15287394.2013.765372 · Cited by 64
Mendell, M. J., Eliseeva, E. A., Davies, M. M., & Lobscheid, A. B. (2015) · Indoor Air · doi:10.1111/ina.12241 · Cited by 70
Self-citationJia, M., Srinivasan, R. S., Ries, R. J., Weyer, N., & Bharathy, G. K. (2019) · Energy and Buildings · doi:10.1016/j.enbuild.2019.07.009 · Cited by 60
Ibrahim, A. M. M., Li, W., MOurad, A.-H. I., Omer, M. A. E., Essa, F. A., Nabi, A. M. A.-E., SOUFI, M. S. A., Ezzat, M. F., & Elsheikh, A. H. (2023) · Chinese Journal of Aeronautics · doi:10.1016/j.cja.2023.03.026 · Cited by 64
Lee, J. K., Dios, Y. E. D., Kofman, I. S., Mulavara, A. P., Bloomberg, J. J., & Seidler, R. D. (2019) · Frontiers in Human Neuroscience · doi:10.3389/fnhum.2019.00355 · Cited by 63
“The environment aboard the ISS poses a potential risk to mission success and the long-term health of astronauts, as prolonged exposure to elevated ambient CO2 results in increased cerebral blood flow and mild performance impairments (Manzey and Lorenz, 1998; Satish et al., 2012; Fisk et al., 2013; Allen et al., 2015,…”
BackgroundWang, W., Liu, F., Zhang, Q., Yu, G., & Deng, S. (2020) · Chemical Engineering Journal · doi:10.1016/j.cej.2020.125734 · Cited by 61
Kumar, P., Hama, S. M. L., Abbass, R. A., Nogueira, T., Brand, V. S., Wu, H.-W., Abulude, F. O., Adelodun, A. A., Andrade, M. D. F., Asfaw, A., et al. (2022) · Journal of Building Engineering · doi:10.1016/j.jobe.2022.105254 · Cited by 62
Thom, S. R., Bhopale, V. M., Hu, J., & Yang, M. (2017) · Free Radical Biology and Medicine · doi:10.1016/j.freeradbiomed.2017.03.005 · Cited by 63
Investigations of Museum Indoor Microclimate and Air Quality. Case Study from Romania
Ilieș, D. C., Marcu, F. M., Caciora, T. I., Indrie, L., Ilieș, A. B., Albu, A., Costea, M., Burtă, L., Baias, Ș., Ilieş, M., et al. (2021) · Atmosphere · doi:10.3390/atmos12020286 · Cited by 57
“According to ANSI/ASHRAE Standard [30] a value above 1000 ppm can lead to health issues such as drowsiness, breathing problems, headaches, or increased sweating [17,57].”
BackgroundTemperature and indoor environments
Salthammer, T., & Morrison, G. (2022) · Indoor Air · doi:10.1111/ina.13022 · Cited by 71
Impact of indoor aroma on students’ mood and learning performance
Choi, N., Yamanaka, T., Takemura, A., Kobayashi, T., Eto, A., & Hirano, M. (2022) · Building and Environment · doi:10.1016/j.buildenv.2022.109490 · Cited by 61
CO2 based ventilation control in energy retrofit: An experimental assessment
Schibuola, L., Scarpa, M., & Tambani, C. (2017) · Energy · doi:10.1016/j.energy.2017.11.050 · Cited by 57
Costanzo, V., & Donn, M. (2017) · Energy and Buildings · doi:10.1016/j.enbuild.2017.02.003 · Cited by 56
“Looking at CO2 concentrations during ventilation (Figure 12, two bottom rows), they always stayed well below 2500 ppm, which according to [45] is considered to be the threshold value above which decision-making tasks are significantly worsened.”
BackgroundKim, J., Hong, T., Kong, M., & Jeong, K. (2019) · Building and Environment · doi:10.1016/j.buildenv.2019.106596 · Cited by 66
Franco, A., & Schito, E. (2020) · Buildings · doi:10.3390/buildings10080135 · Cited by 55
Makaremi, N., Yildirim, S., Morgan, G. T., Touchie, M. F., Jakubiec, J. A., & Robinson, J. (2024) · Building and Environment · doi:10.1016/j.buildenv.2024.111958 · Cited by 100
SmartVent: A Context Aware IoT System to Measure Indoor Air Quality and Ventilation Rate
Lohani, D., & Acharya, D. (2016) · IEEE International Conference on Mobile Data Management (MDM) · doi:10.1109/mdm.2016.91 · Cited by 55
“These pollutants can induce both short and long term adverse health effects to building occupants, collectively called sick building syndrome (SBS).”
BackgroundBen-David, T., & Waring, M. S. (2017) · Building and Environment · doi:10.1016/j.buildenv.2017.10.025 · Cited by 59
Seasonal variation in indoor concentrations of air pollutants in residential buildings
Abdel-Salam, M. M. M. (2021) · Journal of the Air & Waste Management Association · doi:10.1080/10962247.2021.1895367 · Cited by 68
Potentials and limitations of direct air capturing in the built environment
Baus, L., & Nehr, S. (2021) · Building and Environment · doi:10.1016/j.buildenv.2021.108629 · Cited by 60
Li, S., Zhang, X., Li, Y., Gao, W., Xiao, F., & Yang, X. (2023) · Journal of Building Engineering · doi:10.1016/j.jobe.2023.106417 · Cited by 65
Militello-Hourigan, R. E., & Miller, S. L. (2018) · Building and Environment · doi:10.1016/j.buildenv.2018.08.044 · Cited by 57
Jung, C., & Awad, J. (2021) · Buildings · doi:10.3390/buildings11070289 · Cited by 54
“Satish et al. (2012) also studied the effect of CO2 on human performance based on its economic importance, and confirmed that increased levels of CO2 affect decision-making performance [40].”
BackgroundCo-benefits of energy efficiency in residential buildings
Baniassadi, A., Heusinger, J., González, P. I., Weber, S., & Samuelson, H. W. (2021) · Energy · doi:10.1016/j.energy.2021.121768 · Cited by 53
Indoor air quality in sports center: Assessment of gaseous pollutants
Bralewska, K., Rogula–Kozłowska, W., & Bralewski, A. (2021) · Building and Environment · doi:10.1016/j.buildenv.2021.108589 · Cited by 65
Fan, Y., Cao, X., Zhang, J., Lai, D., & Pang, L. (2023) · Building and Environment · doi:10.1016/j.buildenv.2023.110331 · Cited by 64
Erickson, L. E., & Jennings, M. (2017) · AIMS Public Health · doi:10.3934/publichealth.2017.1.47 · Cited by 58
“[15] have investigated the effect of carbon dioxide concentration on human decision-making performance.”
BackgroundPantelic, J., Liu, S., Pistore, L., Licina, D., Vannucci, M., Sadrizadeh, S., Ghahramani, A., Gilligan, B., STERNBERG, E. M., Kampschroer, K., et al. (2019) · Journal of Exposure Science & Environmental Epidemiology · doi:10.1038/s41370-019-0179-5 · Cited by 55
Lowe, R., Huebner, G. M., & Oreszczyn, T. (2018) · Building Services Engineering Research and Technology · doi:10.1177/0143624418790129 · Cited by 52
“Future research should examine the effect of exposure duration systematically, should test the hypothesis suggested tentatively by Satish et al. that the sign and functional form of the relationship may depend on the nature of the cognitive task by testing across a wider range of cognitive functions of varying difficu…”
BackgroundMethodResultInfluentialAndamon, M. M., Rajagopalan, P., & Woo, J. (2023) · Building and Environment · doi:10.1016/j.buildenv.2023.110313 · Cited by 69
Ben-David, T., Rackes, A., & Waring, M. S. (2017) · Building and Environment · doi:10.1016/j.buildenv.2017.02.004 · Cited by 56
Ma, N., Waegel, A., Hakkarainen, M., Braham, W. W., Glass, L., & Aviv, D. (2022) · Applied Energy · doi:10.1016/j.apenergy.2022.120443 · Cited by 69
How Indoor Environment Affects Performance
Wyon, D. P., & Wargocki, P. L. (2013) · Technical University of Denmark, DTU Orbit (Technical University of Denmark, DTU) · Cited by 65
Royapoor, M., Pazhoohesh, M., Davison, P. J., Patsios, C., & Walker, S. L. (2020) · Energy and Buildings · doi:10.1016/j.enbuild.2020.109794 · Cited by 50
Tran, P. T. M., Adam, M. G., Tham, K. W., Schiavon, S., Pantelic, J., Linden, P. F., Sofianopoulou, E., Sekhar, C., Cheong, D. K. W., & Balasubramanian, R. (2021) · Sustainable Cities and Society · doi:10.1016/j.scs.2021.103052 · Cited by 59
The ventilation of buildings and other mitigating measures for COVID-19: a focus on wintertime
Burridge, H. C., Bhagat, R. K., Stettler, M. E. J., Kumar, P., Mel, I. D., Demis, P., Hart, A., Johnson-Llambias, Y., King, M., Victorovich, K. O., et al. (2021) · Proceedings of the Royal Society A Mathematical Physical and Engineering Sciences · doi:10.1098/rspa.2020.0855 · Cited by 83
“Much work has assessed the effects of CO 2 on human physiology with no negative consequences being associated with low CO 2 levels and some degradation of performance at high levels (e.g. [92,93]).”
Rodríguez, D., Urbieta, I. R., Velasco, Á., Campano, M. Á., & Jiménez, E. (2022) · Building and Environment · doi:10.1016/j.buildenv.2022.109717 · Cited by 58
Investigation of CO2 production depending on physical activity of students
Kapalo, P., Mečiarová, Ľ., Vilčeková, S., Burdová, E. K., Domniţa, F. V., Bacoţiu, C., & Péterfi, K.-E. (2018) · International Journal of Environmental Health Research · doi:10.1080/09603123.2018.1506570 · Cited by 49
“CO2 levels could cause following difficulties: above 20,000 ppm – deepened breathing; 40,000 ppm – increases respiration markedly; 100,000 ppm – visual disturbances and tremors, loss of consciousness; 250,000 ppm – death (Satish et al. 2012).”
BackgroundInfluentialHosseinloo, A. H., Ryzhov, A., Bischi, A., Ouerdane, H., Turitsyn, K. S., & Dahleh, M. A. (2020) · Applied Energy · doi:10.1016/j.apenergy.2020.115451 · Cited by 59
Cao, X., Zevitas, C. D., Spengler, J. D., Coull, B. A., McNeely, E., Jones, B., Loo, S. M., MacNaughton, P., & Allen, J. G. (2018) · Indoor and Built Environment · doi:10.1177/1420326x18793997 · Cited by 50
“Participants scored 15% and 50% lower on cognitive tests on days when they were exposed to 950 ppmv and 1400 ppmv of CO2, respectively, compared to the reference condition of 550 ppmv. Similar findings were shown by Satish et al.24 during 2.5-h exposure windows.”
ResultInfluentialCharacterization of Indoor Air Quality on a College Campus: A Pilot Study
Erlandson, G., Magzamen, S. L., Carter, E. M., Sharp, J. L., Reynolds, S. J., & Schaeffer, J. W. (2019) · International Journal of Environmental Research and Public Health · doi:10.3390/ijerph16152721 · Cited by 58
“found a decrease in computer-based decision making tests when participants were exposed to elevated levels of CO2 [22].”
BackgroundZhang, J., Jiang, L., Liu, Z., Li, Y., Liu, K., Fang, R., Li, H., Qu, Z., Liu, C., & Li, F. (2021) · Journal of Cleaner Production · doi:10.1016/j.jclepro.2021.126824 · Cited by 50
Indoor carbon dioxide capture technologies: a review
Yuan, J., Song, X., Yang, X., Yang, C., Wang, Y., Deng, G., Wang, Z., & Gao, J. (2023) · Environmental Chemistry Letters · doi:10.1007/s10311-023-01620-3 · Cited by 48
Hänninen, O., Canha, N., Kulinkina, A. V., Dume, I., Deliu, A., Mataj, E., Lusati, A., Krzyżanowski, M., & Egorov, A. I. (2017) · Air Quality Atmosphere & Health · doi:10.1007/s11869-017-0469-9 · Cited by 47
“observational studies, randomized controlled experiments have also shown that CO2 itself can adversely affect learning and cognitive performance at relatively low levels commonly found in indoor premises (Satish et al. 2012).”
BackgroundCan houseplants improve indoor air quality by removing CO2 and increasing relative humidity?
Gubb, C., Blanuša, T., Griffiths, A., & Pfrang, C. (2018) · Air Quality Atmosphere & Health · doi:10.1007/s11869-018-0618-9 · Cited by 59
The Effect of CO2 Concentration on Children’s Well-Being during the Process of Learning
Bogdanovica, S., Zemītis, J., & Bogdanovičs, R. (2020) · Energies · doi:10.3390/en13226099 · Cited by 52
“As a result, a relationship between CO2 levels in the air and human thinking ability was demonstrated [25].”
BackgroundKim, M. K., Cremers, B., Liu, J., Zhang, J., & Wang, J. (2022) · Sustainable Cities and Society · doi:10.1016/j.scs.2022.103981 · Cited by 46
Kim, J., Kong, M., Hong, T., Jeong, K., & Lee, M. (2018) · Building and Environment · doi:10.1016/j.buildenv.2018.09.018 · Cited by 48
Meiss, A., Jimeno-Merino, H., Poza-Casado, I., Álvarez, A. L., & Padilla-Marcos, M. Á. (2021) · Sustainability · doi:10.3390/su13158446 · Cited by 52
“CO2 must be taken into account as a pollutant, too, because, although not injurious at the levels that have been recorded in schools, it can cause adverse effects on the academic performance of the occupants [13].”
BackgroundLSTM-Based IoT-Enabled CO2 Steady-State Forecasting for Indoor Air Quality Monitoring
Zhu, Y., Al-Ahmed, S. A., Shakir, M. Z., & Olszewska, J. I. (2022) · Electronics · doi:10.3390/electronics12010107 · Cited by 53
Real-time monitoring of personal exposures to carbon dioxide
Gall, E. T., Cheung, T. C. T., Luhung, I., Schiavon, S., & Nazaroff, W. W. (2016) · Building and Environment · doi:10.1016/j.buildenv.2016.04.021 · Cited by 46
Occupant productivity and indoor environment quality: A case of GSAS
Alhorr, Y. M., Arif, M., Kaushik, A. K., Mazroei, A., Elsarrag, E., & Mishra, S. (2017) · International Journal of Sustainable Built Environment · doi:10.1016/j.ijsbe.2017.11.001 · Cited by 53
Hong, T., Kim, J., & Lee, M. (2018) · Applied Energy · doi:10.1016/j.apenergy.2018.07.063 · Cited by 47
User-Centred Healing-Oriented Conditions in the Design of Hospital Environments
Dovjak, M., Shukuya, M., & Krainer, A. (2018) · International Journal of Environmental Research and Public Health · doi:10.3390/ijerph15102140 · Cited by 48
“Higher indoor carbon dioxide concentrations have negative impact on human decision making performance and cause increased health symptoms and poorer perceived air quality [7].”
BackgroundSmart Desks to Promote Comfort, Health, and Productivity in Offices: A Vision for Future Workplaces
Aryal, A., Becerik-Gerber, B., Anselmo, F., Roll, S. C., & Lucas, G. (2019) · Frontiers in Built Environment · doi:10.3389/fbuil.2019.00076 · Cited by 56
Double skin façade with Azolla; ventilation, Indoor Air Quality and Thermal Performance Assessment
Parhizkar, H., Khoraskani, R. A., & Tahbaz, M. (2019) · Journal of Cleaner Production · doi:10.1016/j.jclepro.2019.119313 · Cited by 51
Shan, X. J., Yang, E., Zhou, J. Z., & Chang, V. W.-C. (2019) · Energy and Buildings · doi:10.1016/j.enbuild.2019.05.055 · Cited by 51
On-Chip Non-Dispersive Infrared CO2 Sensor Based on an Integrating Cylinder †
Jia, X., Roels, J., Baets, R., & Roelkens, G. (2019) · Sensors · doi:10.3390/s19194260 · Cited by 45
“5 h can lead to decline in cognitive abilities and basic activity level [9,10].”
BackgroundA Visual and Persuasive Energy Conservation System Based on BIM and IoT Technology
Wu, I.-C., & Liu, C.-C. (2019) · Sensors · doi:10.3390/s20010139 · Cited by 48
Indoor air quality in residential buildings in Upper Silesia, Poland
Kozielska, B., Mainka, A., Żak, M., Kaleta, D., & Mucha, W. (2020) · Building and Environment · doi:10.1016/j.buildenv.2020.106914 · Cited by 52
Abdel-Salam, M. M. M. (2020) · Journal of the Air & Waste Management Association · doi:10.1080/10962247.2020.1834009 · Cited by 53
Sharma, S., Bakht, A., Jahanzaib, M., Lee, H., & Park, D. (2022) · Atmosphere · doi:10.3390/atmos13111863 · Cited by 57
Sharma, S., Bakht, A., Jahanzaib, M., Lee, H., & Park, D. (2022) · doi:10.21203/rs.3.rs-2091762/v1 · Cited by 44
Sustainable carbon emissions: The geologic perspective
DePaolo, D. J. (2015) · MRS Energy & Sustainability · doi:10.1557/mre.2015.10 · Cited by 46
Xiong, Y., Krogmann, U., Mainelis, G., Rodenburg, L. A., & Andrews, C. J. (2015) · Journal of Environmental Science and Health Part A · doi:10.1080/10934529.2015.981101 · Cited by 46
Impact of physical and microbiological parameters on proper indoor air quality in nursery
Basińska, M., Michałkiewicz, M., & Ratajczak, K. (2019) · Environment International · doi:10.1016/j.envint.2019.105098 · Cited by 50
Air quality in a school with dampness and mould problems
Alves, C. A., Duarte, M., Ferreira, M., Alves, A., Almeida, A., & Cunha, Â. (2015) · Air Quality Atmosphere & Health · doi:10.1007/s11869-015-0319-6 · Cited by 48
Slezáková, K., Peixoto, C., Pereira, M. D. C., & Morais, S. (2018) · Journal of Hazardous Materials · doi:10.1016/j.jhazmat.2018.07.015 · Cited by 51
“Whereas CO2 is not a hazardous pollutant at the levels detected in HC [69], exposure to moderate concentrations of CO2 can cause changes in human performances and influence decision-making [70].”
BackgroundLeivo, V., Prasauskas, T., Du, L., Turunen, M., Kiviste, M., Aaltonen, A., Martuzevičius, D., & Haverinen‐Shaughnessy, U. (2017) · The Science of The Total Environment · doi:10.1016/j.scitotenv.2017.11.227 · Cited by 42
“However, a recent experimental study [12] of healthy individuals performing computer-based tests indicated a significant decrease in decision-making performance at 1800 mg/m3 (approx.”
BackgroundIndoor Air Quality: A Bibliometric Study
Pierpaoli, M., & Ruello, M. L. (2018) · Sustainability · doi:10.3390/su10113830 · Cited by 45
Kim, M. K., & Choi, J.-H. (2019) · Atmospheric Environment · doi:10.1016/j.atmosenv.2019.04.015 · Cited by 44
Zhang, J., Pang, L., Cao, X., Wanyan, X., Wang, X., Liang, J., & Zhang, L. (2020) · Building and Environment · doi:10.1016/j.buildenv.2020.106938 · Cited by 46
Roskams, M., & Haynes, B. (2020) · Building Research & Information · doi:10.1080/09613218.2020.1775065 · Cited by 43
“…the 800 ppm threshold is also approximately consistent with research demonstrating that cognitive performance and decision-making abilities are highest when CO2 concentrations are at 600 ppm, and progressively deteriorate at higher concentrations (Allen et al., 2016; Satish et al., 2012).”
BackgroundPoirier, B., Guyot, G., Woloszyn, M., Geoffroy, H., Ondarts, M., & Gonze, E. (2021) · Journal of Building Engineering · doi:10.1016/j.jobe.2021.103140 · Cited by 48
Honan, D., Gallagher, J., Garvey, J., & Littlewood, J. R. (2024) · Buildings · doi:10.3390/buildings14124003 · Cited by 60
Fan, G., Xie, J., Liu, J., & Yoshino, H. (2016) · Indoor and Built Environment · doi:10.1177/1420326x16636184 · Cited by 42
“headache, mucosal irritation) and degraded human decision-making performance.(42) So indoor CO2 concentration in homes should be well controlled for children’s health.”
BackgroundZhang, J., Cao, X., Wang, X., Pang, L., Liang, J., & Zhang, L. (2021) · Building and Environment · doi:10.1016/j.buildenv.2021.107752 · Cited by 44
Metadata
- Authors
- Satish, U., Mendell, M. J., Shekhar, K., Hotchi, T., Sullivan, D., Streufert, S., & Fisk, W. J.
- Affiliations
- SUNY Upstate Medical University (US)
- Lawrence Berkeley National Laboratory (US)
- Corresponding author
- Mendell, Mark J.
- Venue
- Environmental Health Perspectives
- Publisher
- American Chemical Society (ACS)
- Published
- 2012-09-20
- Volume
- 120
- Issue
- 12
- Pages
- 1671-1677
- ISSN
- 0091-6765 (ISSN-L)
- 1552-9924
- PMC
- PMC3548274
- OpenAlex
- W2089734242
- Cited by
- 1,064
- References
- 24
- Citations by year
- 2026: 105 · 2025: 119 · 2024: 103 · 2023: 108 · 2022: 92 · 2021: 123 · 2020: 94 · 2019: 80 · 2018: 63 · 2017: 47 · 2016: 44 · 2015: 34 · 2014: 33 · 2013: 16 · 2012: 1
- FWCI
- 18.60
- Type
- journal article
- Language
- en
- Open access
- gold
- doi.org
- Licence
- public-domain
- creativecommons.org/licenses/by/4.0/ (vor, 1926 d)
- Locations
- Environmental Health Perspectives (publishedVersion, public-domain)
- Europe PMC (PubMed Central) (publishedVersion, public-domain)
- PubMed Central (publishedVersion, public-domain)
- PubMed (publishedVersion)
- eScholarship (California Digital Library) (submittedVersion)
- OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) (submittedVersion)
- Funders
- U.S. Environmental Protection Agency
- Syracuse University
- Topics
- Physical Sciences › Environmental Science › Health, Toxicology and Mutagenesis › Indoor Air Quality and Microbial Exposure
- Physical Sciences › Environmental Science › Health, Toxicology and Mutagenesis › Air Quality and Health Impacts
- Health Sciences › Medicine › Pulmonary and Respiratory Medicine › Infection Control and Ventilation
- Keywords
- indoor carbon dioxide, decision performance, cognitive performance, indoor air quality, ventilation rate, health symptoms, perceived air quality, CO2 exposure, office buildings
- MeSH terms
- Adolescent, Adult, Air Pollutants, Analysis of Variance, Carbon Dioxide, Decision Making, Dose-Response Relationship, Drug, Environmental Exposure, Environmental Monitoring, Female, Humans, Male, Surveys and Questionnaires, Ventilation, Air Pollution, Indoor, Young Adult
About these checks
Registry, retraction, Cites and statistics results are computed, not judged, with one exception: a printed reference that no index lists is read once by a model before it counts as a citation error. Claims are extracted by a model and kept only when their quote appears verbatim in the text; each cited source is then checked, with a model’s help, for whether it says what the claim relies on. Those verdicts can be wrong — read the claim’s quote and the cited source before relying on one.
Statistics and arithmetic are recomputed, not judged.
Confidence bands are shown only for fields calibrated on our annotated test set. None is calibrated yet, so no band is shown.
What counts as a claim ›How we measure confidence ›How we check this ›
Are you an author, or do you see a problem with this page? Request a review
Data sources
Bibliographic data: Semantic Scholar, OpenAlex, Crossref.
Contains information from the Semantic Scholar Academic Graph Datasets, made available under the ODC Attribution License (ODC-BY 1.0).
Semantic Scholar’s data is described in: Kinney, R., et al. (2023). The Semantic Scholar Open Data Platform. arXiv:2301.10140.